The 60 amp sub panel wire size is 6 AWG copper or 4 AWG aluminum, with a 10 AWG copper (or 8 AWG aluminum) equipment ground. In conduit with THHN/THWN-2 and 75°C terminals, 6 AWG copper is good for 65 A. As 6/3 NM cable, it is rated 55 A, and the next-size-up rule lets it sit on a 60 A breaker as long as the calculated load stays at or under 55 A.

This guide shows where each of those numbers comes from in the 2023 NEC, why 8 AWG fails, how NM and THHN differ, how to wire the neutral and ground in the subpanel, and when distance forces you to go bigger. Every rule is followed by a worked example and exam-style questions.

Quick answer: 60 amp subpanel wire size chart

Wiring methodColumn usedCopperAluminum
THHN/THWN-2 in conduit, 75°C terminals75°C6 AWG (65 A)4 AWG (65 A)
NM cable (Romex), indoors, dry60°C (NEC 334.80)6/3 with ground (55 A → 60 A by 240.4(B))—
UF cable, direct burial60°C (NEC 340.80)6/3 UF with ground (55 A → 60 A by 240.4(B))—
Aluminum SER, e.g. 4-4-4-6, indoors75°C, or 60°C in thermal insulation (NEC 338.10(B)(4))—4 AWG (65 A, or 55 A in insulation)
Equipment grounding conductorNEC Table 250.12210 AWG8 AWG

Every ampacity above comes from NEC Table 310.16. If you need a refresher on how the columns work, see the wire ampacity chart guide for Table 310.16.

Why 6 AWG copper works for 60 amps

Two rules decide which number you read in Table 310.16.

1. The termination limit, NEC 110.14(C)(1). For circuits of 100 A or less, or conductors 14 through 1 AWG, you use the 60°C column unless the equipment is listed and marked for 75°C. Most modern panelboards and breakers are marked 60/75°C, so with THHN/THWN-2 you can use 75°C. The termination temperature ratings guide explains this in detail.

2. The cable's own limit. NM cable is always read at 60°C (NEC 334.80), no matter what the terminals allow. UF too (NEC 340.80).

Size60°C75°C90°C60 A feeder?
8 AWG Cu40 A50 A55 ANo
6 AWG Cu55 A65 A75 AYes
6 AWG Al40 A50 A55 ANo
4 AWG Al55 A65 A75 AYes

NEC 240.4(B) lets you protect a conductor at the next higher standard rating when its ampacity does not match a standard size, the device is 800 A or less, and it is not a multi-outlet branch circuit for cord-and-plug loads. A feeder qualifies.

6 AWG Cu at 60°C = 55 A. 55 is not on the list in NEC 240.6(A); the next standard size is 60 A. So 6/3 NM on a 60 A breaker is code-compliant, provided the calculated load is 55 A or less.

Why 8 AWG never works

8 AWG copper at 75°C is 50 A, and 50 A is a standard breaker size. There is no "next size up" to take: the maximum breaker is 50 A. The 55 A in the 90°C column is only a starting point for derating; 110.14(C) never lets you use it as the final ampacity. The 8 AWG wire ampacity guide covers this trap in depth.

Main panel (service)60 A 2-poleNeutral barGround barMBJ60 A subpanelLugs L1 L2Isolated NGround bar6 AWG Cu hots6 AWG Cu neutral10 AWG Cu EGCNo neutral-to-ground bond in the subpanel
A 60 A subpanel feeder: four conductors, with the neutral-to-ground bond only at the service.

Ground wire size for a 60 amp subpanel: Table 250.122

The equipment grounding conductor is sized from the rating of the overcurrent device protecting the feeder, not from the size of the hots. In NEC Table 250.122, the 60 A row gives 10 AWG copper or 8 AWG aluminum (or copper-clad aluminum).

That is why a 6/3 NM cable carries a 10 AWG bare ground: it is exactly what the table requires.

Other EGC options from NEC 250.118: a metal raceway such as EMT, rigid or IMC, properly installed with listed fittings, can itself serve as the EGC. PVC cannot, so a PVC run always needs a wire-type EGC.

Separate neutral and ground in the subpanel

This is the part DIY guides most often get wrong, and inspectors check it first.

At the service, the neutral and the equipment grounding system are bonded together by the main bonding jumper. Everywhere downstream, they must stay separate:

  • NEC 250.24(B): no grounding connection to the grounded (neutral) conductor on the load side of the service disconnecting means, except where the code specifically permits it.
  • NEC 250.142(B): the neutral may not be used to ground equipment on the load side of the service disconnect, with limited exceptions.

In practice, in the subpanel:

  1. Remove or never install the bonding screw or strap that ties the neutral bar to the enclosure.
  2. Land neutrals only on the isolated neutral bar.
  3. Install a ground bar bonded to the enclosure and land every EGC and bare ground there.
  4. Run a four-wire feeder: L1, L2, neutral, EGC.

If the neutral is bonded in the subpanel, normal neutral current splits onto the grounding path, metal raceways and enclosures. That is objectionable current under NEC 250.6, and it puts voltage on metal parts if the neutral opens. For a clear explanation of where the bond belongs, read main bonding jumper vs system bonding jumper and grounded vs grounding conductor.

Detached garage or shop

A subpanel in a separate building adds two requirements:

  • Grounding electrode system, NEC 250.32(A): required at the building, unless it is supplied by only one branch circuit or multiwire branch circuit with an EGC. Connect the electrode to the ground bar, not to the neutral. See ground rod requirements.
  • EGC with the feeder, NEC 250.32(B)(1): the EGC runs with the feeder and the neutral stays isolated. An exception allows certain existing three-wire installations to remain; it does not apply to new work.

Part II of Article 225 also requires a disconnecting means at the building. A main-breaker subpanel often serves that purpose.

NM cable vs THHN in conduit for a 60 amp subpanel

Both work. They are rated differently and allowed in different places.

6/3 NM cable

  • 60°C column: 55 A
  • 60 A breaker only through 240.4(B), load ≤ 55 A
  • Includes 10 AWG ground
  • Dry locations only, not in wet locations or underground conduit
  • Fast to install inside a house

6 AWG THHN/THWN-2 in conduit

  • 75°C column (with 75°C terminals): 65 A
  • Full 60 A with margin
  • EGC: 10 AWG wire, or the metal raceway itself
  • THWN-2 rated for wet locations, so OK in underground conduit
  • Required where NM is not permitted

Two location rules matter most:

  • NEC 334.12 does not permit NM cable in wet or damp locations.
  • NEC 300.5(B) says the interior of an underground raceway is a wet location. So NM is never pulled through underground conduit to a garage. Use THWN-2 or another wet-rated conductor, or UF or a direct-burial-rated cable.

The difference between THHN and THWN-2 is explained in THHN vs THWN.

Aluminum SER or aluminum conductors

Aluminum is a common, legal choice for a 60 A feeder: 4 AWG aluminum is 65 A at 75°C, the same as 6 AWG copper. Two cautions:

  • SER cable indoors. Under NEC 338.10(B)(4), interior SE cable follows the NM installation rules but not the NM 60°C limit, except where it runs through thermal insulation, where it drops to the 60°C column. 4 AWG aluminum SER in an insulated wall is a 55 A conductor, which still reaches a 60 A breaker through 240.4(B) if the load is 55 A or less.
  • Terminations. Use lugs marked AL/CU (most 60 A panel lugs and breakers are), never mix copper and aluminum under one screw, and tighten to the marked torque with an approved means such as a calibrated torque tool (NEC 110.14(D)). The aluminum vs copper wire guide covers the rest.

What conduit size for 6 AWG THHN?

Three 6 AWG THHN plus one 10 AWG THHN EGC, from Chapter 9, Table 5: 3 × 0.0507 + 0.0211 = 0.1732 in². Chapter 9, Table 4 gives 40% fill for EMT as 0.122 in² for ½ in. and 0.213 in² for ¾ in. So ¾ in. EMT is the minimum. The full method is in the conduit fill calculation guide.

Distance and voltage drop on a 60 amp feeder

Table 310.16 sizes the conductor for heat. It says nothing about distance. The NEC addresses voltage drop for feeders in informational notes, which recommend 3% on a feeder and 5% total; they are guidance, not enforceable requirements, unless your jurisdiction or the job specs say otherwise.

Single-phase voltage drop

VD = (2 × K × I × L) ÷ CM

K = 12.9 for copper, I = load in amps, L = one-way length in feet, CM = circular mils from Chapter 9, Table 8.

Worked example

60 A subpanel 250 feet away

  1. 1

    The question

    A detached shop 250 ft (one way) from the house has a 60 A, 240 V subpanel with a 48 A calculated load. Copper THWN-2 in PVC. Size the conductors for 3% maximum voltage drop.

  2. 2

    Try 6 AWG (26,240 cmil)

    (2 × 12.9 × 48 × 250) ÷ 26,240 = 309,600 ÷ 26,240 = 11.80 V → 11.80 ÷ 240 = 4.92%. Too high.

  3. 3

    Try 4 AWG (41,740 cmil)

    309,600 ÷ 41,740 = 7.42 V → 3.09%. Still just over 3%.

  4. 4

    Try 3 AWG (52,620 cmil)

    309,600 ÷ 52,620 = 5.88 V → 2.45%. Meets 3%.

  5. 5

    Upsize the EGC, 250.122(B)

    Ratio = 52,620 ÷ 26,240 = 2.005. Base EGC 10 AWG = 10,380 cmil × 2.005 = 20,815 cmil. 8 AWG (16,510) is too small, so use 6 AWG copper (26,240).

  6. ✓ Answer: 3 AWG copper hots and neutral, with a 6 AWG copper EGC.

How far can you run each size? Quick chart

Maximum one-way distance to stay at or under 3% (7.2 V) at 240 V, using K = 12.9 for copper and 21.2 for aluminum:

Conductor48 A load (80% of 60 A)60 A load
6 AWG Cu153 ft122 ft
4 AWG Cu243 ft194 ft
3 AWG Cu306 ft245 ft
4 AWG Al148 ft118 ft
2 AWG Al235 ft188 ft
1 AWG Al296 ft237 ft

Size for the load you actually expect, not the breaker. Remember the 3% figure is a recommendation, and any upsizing of the hots also upsizes a wire-type EGC.

The voltage drop formula guide explains the K-factor and Chapter 9, Table 9 methods.

What a 60 amp subpanel can actually carry

The feeder conductors must handle the calculated load, with 125% of any continuous load added to the noncontinuous load (NEC 215.2(A)). The breaker must meet the same 125% rule (NEC 215.3).

Worked example

EV charger in the garage subpanel

  1. 1

    The question

    A garage subpanel will serve an EV charger rated 32 A continuous plus 15 A of noncontinuous load. Is 6/3 NM on a 60 A breaker enough?

  2. 2

    Minimum conductor ampacity

    (32 × 1.25) + 15 = 40 + 15 = 55 A.

  3. 3

    Compare

    6 AWG Cu NM at 60°C = 55 A ≥ 55 A. ✓

  4. 4

    Breaker

    Minimum 55 A; 55 A is not standard, so 60 A is permitted under 240.4(B).

  5. ✓ Answer: Yes, but with zero margin. Adding any load means THHN in conduit (65 A) or a larger feeder.

Exam-style practice

Exam-style question

A 60 A feeder to a subpanel is installed with THHN copper conductors in EMT. All terminations are rated 75°C and no derating applies. What is the minimum conductor size?

Pick an answer to see the explanation.

Exam-style question

What is the minimum size copper equipment grounding conductor for a feeder protected by a 60 A circuit breaker?

Pick an answer to see the explanation.

Exam-style question

In a subpanel fed from the service panel of the same building, where must the neutral be bonded to the equipment grounding conductors?

Pick an answer to see the explanation.

Exam-style question

A 60 A feeder uses Type NM cable with 6 AWG copper conductors. The calculated load is 52 A. What is the maximum standard breaker size permitted?

Pick an answer to see the explanation.

How to find this fast in the code book

Three tabs answer almost every subpanel question: NEC Table 310.16 for the conductors, NEC 240.4(B) for the breaker, and NEC Table 250.122 for the ground. Add NEC 250.32 if the panel is in a separate building. You can read the code text on the NFPA free access page, and always check local amendments before you wire.

→Going bigger: the 100 A subpanelWire Size for a 100 Amp Service or Subpanel

If the subpanel might grow, compare this with the 100 amp subpanel wire size and the 125 amp wire size guide. Then put these rules under the clock with the free journeyman electrician practice test.