The voltage drop formula for a single-phase circuit is VD = 2 × K × I × L ÷ CM, and for a three-phase circuit it is VD = 1.732 × K × I × L ÷ CM. K is the resistivity constant (about 12.9 for copper, 21.2 for aluminum), I is the current in amperes, L is the one-way length in feet, and CM is the conductor's area in circular mils from NEC Chapter 9, Table 8.
This guide starts with two lookup tables that answer most field questions in seconds, then shows both methods the exam uses, the K-factor method and the Chapter 9 Table 8 resistance method, for single- and three-phase circuits. You will also learn to flip the formula around to find the wire size you need or the longest run you can make, with eight worked examples and the rounding rules that decide multiple-choice answers.
Voltage drop quick reference tables
Table 1: volts dropped per amp, per 100 feet of one-way run (copper, K = 12.9). Multiply the number by the load in amperes and by the one-way distance in hundreds of feet.
| Copper size | Single-phase | Three-phase |
|---|---|---|
| 14 AWG | 0.628 | 0.544 |
| 12 AWG | 0.395 | 0.342 |
| 10 AWG | 0.249 | 0.215 |
| 8 AWG | 0.156 | 0.135 |
| 6 AWG | 0.098 | 0.085 |
| 4 AWG | 0.062 | 0.054 |
| 3 AWG | 0.049 | 0.042 |
| 2 AWG | 0.039 | 0.034 |
| 1 AWG | 0.031 | 0.027 |
| 1/0 | 0.024 | 0.021 |
| 2/0 | 0.019 | 0.017 |
| 3/0 | 0.015 | 0.013 |
Example: 12 AWG, 16 A, 100 feet one way, single-phase: 0.395 × 16 × 1.00 = 6.3 V. The same run at 150 feet: 0.395 × 16 × 1.5 = 9.5 V. For aluminum, multiply the copper figure by about 1.64.
Table 2: longest one-way run that stays at or under 3%, copper, load equal to the circuit rating (1ph = single-phase, 3ph = three-phase).
| Size / load | 120 V 1ph | 240 V 1ph | 208 V 3ph | 480 V 3ph |
|---|---|---|---|---|
| 14 AWG / 15 A | 38 ft | 76 ft | 76 ft | 176 ft |
| 12 AWG / 20 A | 45 ft | 91 ft | 91 ft | 210 ft |
| 10 AWG / 30 A | 48 ft | 96 ft | 96 ft | 222 ft |
| 8 AWG / 40 A | 57 ft | 115 ft | 115 ft | 266 ft |
| 6 AWG / 60 A | 61 ft | 122 ft | 122 ft | 281 ft |
| 4 AWG / 80 A | 72 ft | 145 ft | 145 ft | 336 ft |
| 3 AWG / 100 A | 73 ft | 146 ft | 146 ft | 339 ft |
| 1/0 / 150 A | 98 ft | 196 ft | 196 ft | 453 ft |
| 3/0 / 200 A | 117 ft | 234 ft | 234 ft | 540 ft |
Distances are rounded down. Distance scales inversely with current, so at 80% load (a continuous load on the full circuit), multiply the distance by 1.25; at half load, double it. Both tables use the K-factor approximation, which is close enough for planning and for exam checks; the sections below show how to calculate any circuit exactly.
What voltage drop is and why it matters
Every conductor has resistance. When current flows through that resistance, some voltage is "used up" in the wire before it ever reaches the load. That lost voltage is voltage drop, and it follows Ohm's law: E = I × R. If you need a refresher, see Ohm's law and the power formula wheel.
Too much voltage drop means motors run hot and draw more current, lighting dims, electronics misbehave and the wire wastes energy as heat. That is why voltage drop shows up on almost every journeyman exam, and why long runs on real jobs often end up one or two sizes larger than ampacity alone would require.
Two things drive voltage drop: how much current flows and how much resistance the conductor has. Resistance goes up with length and down with conductor area. Every version of the formula is just those four quantities arranged differently.
The voltage drop formula: K-factor method
The K-factor method is the one you will use most on the exam because it needs only one table lookup: the circular mil area of the conductor.
Single-phase (and DC)
VD = 2 × K × I × L ÷ CM
Three-phase
VD = 1.732 × K × I × L ÷ CM
Here is what each letter means:
| Symbol | Meaning | Where you get it |
|---|---|---|
| VD | Voltage drop in volts | What you are solving for |
| K | Resistivity constant (ohm-cmil per foot) | 12.9 copper, 21.2 aluminum (approximate) |
| I | Load current in amperes | The question, or P ÷ E |
| L | One-way length in feet | The question (source to load) |
| CM | Conductor area in circular mils | NEC Chapter 9, Table 8 |
Where K = 12.9 and K = 21.2 come from
K is the resistance of a conductor one foot long and one circular mil in area. You can back it out of Chapter 9, Table 8, which lists DC resistance at 75°C. Multiply a conductor's resistance per foot by its area and you get roughly the same number for every copper size:
- 12 AWG stranded copper: 1.98 Ω per 1,000 ft × 6,530 cmil ÷ 1,000 = 12.93
- 1/0 stranded copper: 0.122 × 105,600 ÷ 1,000 = 12.88
- 1/0 aluminum: 0.201 × 105,600 ÷ 1,000 = 21.23
So 12.9 and 21.2 are conventional approximations, not values printed in the NEC. They are close enough for exam work and for most field estimates. Some textbooks round to K = 12 for copper or use other values based on a different conductor temperature. If a test question gives you a K value, use the one in the question.
Circular mils you will use constantly
These areas come straight from Chapter 9, Table 8. They are the same for copper and aluminum.
| Size | Area (cmil) | Size | Area (cmil) |
|---|---|---|---|
| 14 AWG | 4,110 | 2 AWG | 66,360 |
| 12 AWG | 6,530 | 1 AWG | 83,690 |
| 10 AWG | 10,380 | 1/0 | 105,600 |
| 8 AWG | 16,510 | 2/0 | 133,100 |
| 6 AWG | 26,240 | 3/0 | 167,800 |
| 4 AWG | 41,740 | 4/0 | 211,600 |
| 3 AWG | 52,620 | 250 kcmil | 250,000 |
The Chapter 9 Table 8 method (resistance per 1,000 feet)
Instead of K and circular mils, you can use the resistance value printed in Chapter 9, Table 8 directly. This is plain Ohm's law: find the total resistance of the wire, multiply by the current.
Single-phase, Table 8 method
VD = 2 × I × R × L ÷ 1,000
Three-phase, Table 8 method
VD = 1.732 × I × R × L ÷ 1,000
R is the DC resistance in ohms per 1,000 feet at 75°C. Table 8 gives separate values for copper (uncoated and coated) and aluminum, and for solid and stranded small conductors, so read the right column.
| Size (stranded) | Uncoated copper Ω/kFT | Aluminum Ω/kFT |
|---|---|---|
| 12 AWG | 1.98 | 3.25 |
| 10 AWG | 1.24 | 2.04 |
| 8 AWG | 0.778 | 1.28 |
| 6 AWG | 0.491 | 0.808 |
| 4 AWG | 0.308 | 0.508 |
| 2 AWG | 0.194 | 0.319 |
| 1/0 | 0.122 | 0.201 |
| 2/0 | 0.0967 | 0.159 |
| 3/0 | 0.0766 | 0.126 |
| 4/0 | 0.0608 | 0.100 |
Both methods give nearly identical answers. Use whichever the question points you to: if it gives you "Ω per 1,000 ft" or tells you to use Table 8 resistance, use this method. If it gives you K, use the K-factor method.
What about Chapter 9, Table 9?
Table 8 is DC resistance. On AC circuits, especially with large conductors in steel raceway, inductive reactance adds to the drop. Chapter 9, Table 9 lists AC resistance (R) and inductive reactance (XL) in ohms per 1,000 feet for conductors in PVC, aluminum and steel conduit, plus an "effective Z at 0.85 power factor" column. The notes to Table 9 give the effective impedance for any other power factor:
Effective impedance, Chapter 9 Table 9 notes
Ze = R × PF + XL × sin(arccos PF)
Then use Ze exactly where you would use R in the Table 8 method: VD = 2 × I × Ze × L ÷ 1,000 for single-phase and VD = 1.732 × I × Ze × L ÷ 1,000 for three-phase. At unity power factor, Ze is simply R. For small conductors (roughly 1/0 and smaller), reactance is small and the AC and DC answers are close. For large feeders in steel conduit at a lagging power factor, Table 9 gives a noticeably higher drop, which is why engineers use it for big feeders.
Most journeyman exam questions stick to K or Table 8 unless they tell you otherwise, so read the question for the words "AC resistance," "Table 9," "impedance" or "power factor."
The same formula in metric units
Outside the NEC world you will see the formula written with resistivity: VD = 2 × ρ × L × I ÷ A for single-phase (use √3 instead of 2 for three-phase), with L in meters, A in mm² and ρ in Ω·mm²/m. For copper, ρ is about 0.0172 at 20°C and about 0.021 at 75°C. It is the same physics as the K-factor formula, just a different unit for the conductor area. DC and low-voltage circuits (12 V landscape lighting, a solar array's DC wiring) use the single-phase form with the factor of 2, and because the system voltage is so low, the same 3% allows only a fraction of a volt.
Single-phase vs three-phase: 2 or 1.732?
In a single-phase circuit (120 V, 240 V, or a two-wire DC circuit), the current goes out on one conductor and comes back on the other. Both conductors drop voltage, so the length is doubled: multiplier 2.
In a balanced three-phase circuit, the line-to-line voltage drop works out to √3 × I × R for one conductor's length. That is why the three-phase formula uses 1.732 instead of 2. For the theory behind √3, see single-phase vs three-phase power.
Single-phase
- 120 V, 240 V, 120/240 V circuits
- Multiplier: 2
- VD = 2 × K × I × L ÷ CM
- Current = watts ÷ volts
Three-phase
- 208 V, 240 V, 480 V three-phase
- Multiplier: 1.732 (√3)
- VD = 1.732 × K × I × L ÷ CM
- Current = watts ÷ (volts × 1.732)
Converting volts to percent (and back)
Exam questions mix volts and percent freely. The conversion is simple:
Percent voltage drop
VD% = VD ÷ source voltage × 100
Allowed volts
Allowed VD = system voltage × percent ÷ 100
| System | 3% allowed | 5% allowed |
|---|---|---|
| 120 V | 3.6 V | 6.0 V |
| 208 V | 6.24 V | 10.4 V |
| 240 V | 7.2 V | 12.0 V |
| 277 V | 8.31 V | 13.85 V |
| 480 V | 14.4 V | 24.0 V |
The 3% and 5% figures come from informational notes in the NEC. They are recommendations for general circuits, not requirements. The full story, including the places where voltage drop is mandatory, is in NEC voltage drop rules: where the 3% and 5% come from.
Worked examples: finding the voltage drop
1. Single-phase 120 V branch circuit, both methods
- 1
The question
A 120-volt branch circuit supplies a 16-ampere load 100 feet from the panel using 12 AWG stranded copper. What is the voltage drop and the percent drop?
- 2
K-factor method
VD = 2 × 12.9 × 16 × 100 ÷ 6,530 = 41,280 ÷ 6,530 = 6.32 V
- 3
Table 8 method
R = 1.98 Ω per 1,000 ft. VD = 2 × 16 × 1.98 × 100 ÷ 1,000 = 6.34 V
- 4
Percent
6.32 ÷ 120 × 100 = 5.27%. The two methods differ by only 0.02 V.
2. Three-phase 208 V feeder
- 1
The question
A 208-volt, three-phase feeder supplies a 60-ampere balanced load 200 feet away with 4 AWG copper conductors. Find the voltage drop.
- 2
Plug in
VD = 1.732 × 12.9 × 60 × 200 ÷ 41,740
- 3
Work it out
1.732 × 12.9 = 22.34. 22.34 × 60 = 1,340.6. 1,340.6 × 200 = 268,113. 268,113 ÷ 41,740 = 6.42 V
- 4
Percent
6.42 ÷ 208 × 100 = 3.09%
3. Aluminum feeder with the Table 8 method
- 1
The question
A 240-volt single-phase feeder uses 1/0 aluminum conductors to carry 100 amperes over 175 feet. Use Chapter 9, Table 8 to find the voltage drop.
- 2
Look up R
1/0 aluminum = 0.201 Ω per 1,000 ft.
- 3
Calculate
VD = 2 × 100 × 0.201 × 175 ÷ 1,000 = 7,035 ÷ 1,000 = 7.04 V
- 4
Check with K
2 × 21.2 × 100 × 175 ÷ 105,600 = 742,000 ÷ 105,600 = 7.03 V. Same answer.
4. Large three-phase 480 V feeder
- 1
The question
A 480-volt, three-phase feeder carries 150 amperes over 300 feet on 3/0 copper. What is the voltage drop using Table 8?
- 2
Look up R
3/0 uncoated copper = 0.0766 Ω per 1,000 ft.
- 3
Calculate
VD = 1.732 × 150 × 0.0766 × 300 ÷ 1,000. 1.732 × 150 = 259.8. 259.8 × 300 = 77,940. 77,940 × 0.0766 = 5,970.2. ÷ 1,000 = 5.97 V
Solving for wire size (circular mils)
The most useful version of the formula on the job and on the exam is the one that tells you what size wire you need. Rearrange it to solve for CM:
Minimum area, single-phase
CM = 2 × K × I × L ÷ VD
Minimum area, three-phase
CM = 1.732 × K × I × L ÷ VD
VD here is the allowed voltage drop in volts, not a percent. Convert first.
5. Size the wire for a 3% drop
- 1
The question
A 240-volt single-phase load draws 40 amperes and is 150 feet from the panel. Using copper and limiting the drop to 3%, what is the minimum conductor size?
- 2
Allowed volts
240 × 0.03 = 7.2 V
- 3
Solve for CM
CM = 2 × 12.9 × 40 × 150 ÷ 7.2 = 154,800 ÷ 7.2 = 21,500 cmil
- 4
Pick from Table 8
8 AWG is 16,510 cmil, too small. 6 AWG is 26,240 cmil, the first size at or above 21,500.
7. Three-phase: size the wire for a 3% drop
- 1
The question
A 480-volt, three-phase feeder supplies a 65-ampere load 400 feet away. Using copper (K = 12.9) and 75°C terminations, what is the minimum conductor size for a 3% voltage drop?
- 2
Allowed volts
480 × 0.03 = 14.4 V
- 3
Solve for CM
CM = 1.732 × 12.9 × 65 × 400 ÷ 14.4 = 580,913 ÷ 14.4 = 40,341 cmil
- 4
Pick from Table 8, then check ampacity
6 AWG (26,240 cmil) is too small. 4 AWG is 41,740 cmil, just enough. Ampacity alone needed only 6 AWG (65 A at 75°C).
If you upsize ungrounded conductors for voltage drop, a wire-type equipment grounding conductor must be increased proportionally by circular mil area under NEC 250.122(B). That rule is covered in equipment grounding conductor sizing.
Solving for maximum distance
Sometimes the question is how far you can go with a given wire. Solve for L:
Maximum one-way length, single-phase
L = VD × CM ÷ (2 × K × I)
Maximum one-way length, three-phase
L = VD × CM ÷ (1.732 × K × I)
6. How far can a 12 AWG circuit run?
- 1
The question
A 120-volt circuit uses 12 AWG copper to supply a 16-ampere load. What is the maximum one-way length that keeps the drop at or below 3%?
- 2
Allowed volts
120 × 0.03 = 3.6 V
- 3
Solve for L
L = 3.6 × 6,530 ÷ (2 × 12.9 × 16) = 23,508 ÷ 412.8 = 56.9 ft
- 4
Round down
Any longer and the drop exceeds 3%, so you round down.
8. Three-phase: how far can 4 AWG go?
- 1
The question
A 208-volt, three-phase feeder uses 4 AWG copper (41,740 cmil) to carry 70 amperes. What is the longest one-way run that keeps the drop at or below 3%?
- 2
Allowed volts
208 × 0.03 = 6.24 V
- 3
Solve for L
L = 6.24 × 41,740 ÷ (1.732 × 12.9 × 70) = 260,458 ÷ 1,564.0 = 166.5 ft
You can also solve for the maximum current: I = VD × CM ÷ (2 × K × L) for single-phase, or with 1.732 in place of 2 for three-phase. The same rule applies: round down.
Exam traps and how the questions are worded
"Distance" vs "total length." Most questions give the one-way distance from source to load. If a question says "the total length of conductor is 300 feet" for a two-wire circuit, the one-way length is 150 feet. Read carefully.
Watts instead of amps. If the load is given in watts or kVA, find current first. Single-phase: I = P ÷ E. Three-phase: I = P ÷ (E × 1.732). See the electrical formulas cheat sheet.
Wrong voltage for percent. Percent drop is based on the source (nominal) voltage, not the voltage at the load.
Copper K on an aluminum question. Aluminum has about 1.64 times the resistance of copper of the same size. If the conductors are aluminum, use 21.2.
Using the wrong Table 8 column. Table 8 lists uncoated copper, coated copper and aluminum, and solid vs stranded for small sizes. Unless the question says otherwise, use uncoated copper and stranded conductors.
How to reduce voltage drop
Every term in the formula is a lever:
- Increase conductor size (CM). The most common fix. Doubling the area halves the drop.
- Shorten the run (L). Relocate the panel, add a subpanel closer to the loads, or route more directly.
- Reduce current (I). Split the load across more circuits.
- Raise the voltage. The same power at 240 V draws half the current it would at 120 V, and the allowed drop in volts doubles. Three-phase 480 V feeders are the extreme case.
- Use copper instead of aluminum of the same size, or upsize aluminum by about two AWG sizes to match. The trade-offs are covered in aluminum vs copper wire.
Practice: voltage drop questions
Exam-style question
A 240-volt single-phase circuit supplies a 30-ampere load 120 feet away using 10 AWG copper conductors (10,380 cmil). Using K = 12.9, what is the approximate voltage drop?
Pick an answer to see the explanation.
Exam-style question
A three-phase, 480-volt feeder carries 52 amperes over 250 feet. Using copper (K = 12.9) and limiting voltage drop to 3%, what is the minimum conductor size?
Pick an answer to see the explanation.
Exam-style question
Which statement about the voltage drop formula is correct?
Pick an answer to see the explanation.
Exam-style question
Using the Chapter 9, Table 8 method, what is the voltage drop on a 120-volt circuit carrying 12 amperes over 80 feet of 14 AWG stranded copper (3.14 Ω per 1,000 ft)?
Pick an answer to see the explanation.
How to find this fast in the code book
Voltage drop questions live in Chapter 9, the tables at the back of the book. Tab Chapter 9, Table 8 (conductor properties: circular mils and DC resistance) and Table 9 (AC resistance and reactance). Table 8 is also the table you use for conductor areas in conduit fill calculations for bare conductors, so it earns its tab twice. For a complete tabbing plan, see how to tab your NEC code book.
Write the two formulas on the Table 8 page margin if your exam rules allow handwritten notes in the book (many do not, so check your candidate bulletin). Otherwise, memorize them: "2 K I L over CM" for single-phase and "1.732 K I L over CM" for three-phase.
→Size for ampacity firstWire Ampacity Chart: How to Read NEC Table 310.16Voltage drop is the second check, not the first
Voltage drop never replaces ampacity. The correct order is:
- Size the conductor for ampacity with Table 310.16, applying ampacity correction and adjustment factors and the termination temperature limits of 110.14(C).
- Check voltage drop for the run length. If it is too high, upsize.
- If you upsized, increase the wire-type equipment grounding conductor proportionally.
For common sizes, see 10 gauge wire amps and 8 AWG wire ampacity, and for service and feeder conductors, wire size for a 100 amp service.
→What the NEC actually requiresNEC Voltage Drop Rules: Where the 3% and 5% Come FromVoltage drop is one of the calculation topics that most often decides a pass or a fail, because it is easy to set up wrong under time pressure. Work a dozen of these until the setup is automatic, then test yourself with a free journeyman practice test or go straight to the timed practice tests.