10 gauge wire (10 AWG copper) is rated 30 amps in the 60°C column, 35 amps at 75°C and 40 amps at 90°C of NEC Table 310.16, but in almost every installation it goes on a 30-amp breaker. The reason is NEC 240.4(D)(8), which limits the overcurrent protection for 10 AWG copper to 30 amperes unless a specific exception applies.

This guide explains where each of those three numbers comes from, when (rarely) 10 AWG can land on a larger breaker, how derating and voltage drop affect it, and how the exam tests it. By the end, you will be able to answer "how many amps is 10 gauge wire" correctly for any wiring method.

10 gauge wire amps at a glance

10 AWG conductorTable ampacityMax. breaker (general use)
Copper, 60°C column (TW, UF, NM)30 A30 A
Copper, 75°C column (THW, THWN, XHHW)35 A30 A
Copper, 90°C column (THHN, THWN-2, XHHW-2)40 A30 A
Aluminum, 60°C / 75°C / 90°C25 / 30 / 35 A25 A

Values from 2023 NEC Table 310.16; breaker limits from NEC 240.4(D).

30 A35 A40 A60°C75°C90°C240.4(D)30 A10 AWG copper, Table 310.16
10 AWG copper: three table ampacities, one overcurrent limit. The 35 A and 40 A values are useful only as headroom for derating.

Why 10 AWG copper is limited to 30 amps

Two rules work together.

First, the small-conductor rule. NEC 240.4(D) sets a maximum overcurrent device rating for the small conductors marked with an asterisk in Table 310.16. For 10 AWG copper it is 30 A, and for 10 AWG aluminum or copper-clad aluminum it is 25 A. This applies even though the table shows 35 A and 40 A in the higher columns. (Item numbers here are from the 2023 NEC. The 2023 edition added 14 AWG copper-clad aluminum to the list, so 10 AWG copper moved from (D)(7) in the 2020 NEC to (D)(8). If your state still uses the 2020 or 2017 code, the rule is the same and only the number differs.)

Second, the termination rule. Under NEC 110.14(C)(1)(a), terminations on circuits rated 100 A or less, or marked for 14 through 1 AWG conductors, use the 60°C column unless the equipment is listed and identified for higher-rated conductors (typically marked 75°C or 60/75°C). For 10 AWG copper the 60°C value is exactly 30 A, so even without 240.4(D), many installations would stop at 30 A. You can read the full termination rule in termination temperature ratings, NEC 110.14(C).

Note the end of that rule: the 30 A limit applies after derating. If derating brings the conductor below 30 A, the breaker has to come down with it (subject to the next-size-up rule in 240.4(B) where that applies).

So what are the 35 A and 40 A numbers for?

They are headroom for derating. When you have more than three current-carrying conductors in a raceway, or a hot ambient, you multiply the table value by correction and adjustment factors. Starting from 40 A (90°C THHN) instead of 30 A lets 10 AWG survive a lot of derating and still support a 30 A circuit.

Worked example

Six 10 AWG THHN conductors in one conduit

  1. 1

    The question

    Six current-carrying 10 AWG THHN copper conductors share an EMT raceway at a normal 30°C ambient. Terminals are rated 75°C. Can each circuit still be protected at 30 A?

  2. 2

    Start at 90°C

    40 A from the 90°C column.

  3. 3

    Adjust for 4–6 conductors

    Table 310.15(C)(1): 80%. 40 × 0.80 = 32 A

  4. 4

    Check terminals and 240.4(D)

    75°C terminal limit = 35 A. 240.4(D) limit = 30 A. 32 A ≥ 30 A.

  5. ✓ Answer: Yes. The derated ampacity is 32 A, so a 30 A breaker is fine.
Worked example

Nine 10 AWG THHN conductors

  1. 1

    The question

    Same conductors, but nine current-carrying conductors in the raceway.

  2. 2

    Adjust for 7–9 conductors

    40 × 0.70 = 28 A

  3. ✓ Answer: 28 A. The conductors may not serve more than 28 A of load. Whether a 30 A breaker is still allowed depends on 240.4(B), the next-size-up rule: it is permitted only if the circuit is not a multioutlet branch circuit supplying receptacles for cord-and-plug-connected portable loads and the other conditions of 240.4(B) are met. On an exam, read the question for those conditions.

The complete method, with the temperature table and the neutral-counting rules, is in ampacity correction and adjustment factors.

10/2 and 10/3 NM cable (Romex)

NM cable is held to the 60°C ampacity by NEC 334.80, no matter that its conductors are 90°C rated. For 10 AWG, the 60°C value is 30 A, which happens to equal the 240.4(D) limit. So 10/2 and 10/3 NM cable is a 30-amp cable.

The 90°C rating of the conductors inside NM may be used as the starting point for derating, for example when several cables are bundled through bored holes that will be sealed with insulation or foam, but the final ampacity cannot exceed the 60°C value.

UF cable is also a 60°C wiring method under NEC 340.80, so 10 AWG UF is 30 A as well.

When 10 AWG can be on a breaker larger than 30 A

NEC 240.4(G) lists specific applications where conductor overcurrent protection is governed by other articles. The two you will see most on the job and on the exam:

Air-conditioning and refrigeration equipment (Article 440). The nameplate gives a minimum circuit ampacity (MCA) and a maximum overcurrent protection (MOCP). You size the conductor to the MCA and the breaker no larger than the MOCP. A unit with an MCA of 28 A and an MOCP of 45 A can be wired with 10 AWG copper (30 A at 60°C) on a 45 A breaker, as long as the nameplate allows it. The breaker protects against short circuits and ground faults; the unit's internal protection handles overload. See MCA vs MOCP.

Motor circuits (Article 430). Motor branch-circuit conductors are sized at 125% of the motor full-load current from the tables, and the short-circuit and ground-fault device is sized from Table 430.52, which often exceeds the conductor ampacity. Overload protection is provided separately. See motor calculations under Article 430.

Other items in 240.4(G) and 240.4(E), such as tap conductors, follow their own rules. Outside these listed cases, 30 A is the limit.

What 10 gauge wire is used for

Common 30-amp, 10 AWG applications:

LoadWhy 10 AWG
Electric clothes dryer (typical 30 A circuit)10/3 with ground for 120/240 V dryers
4,500 W water heater at 240 V4,500 ÷ 240 = 18.75 A × 125% = 23.4 A, more than 12 AWG's 20 A limit
240 V baseboard or wall heaters up to about 5,760 WFixed space heating is a continuous load per NEC 424.4(B): 24 A × 125% = 30 A
A/C condensers and heat pumpsSized from the nameplate MCA and MOCP
30 A RV receptacle (TT-30)30 A, 120 V circuit
Long 20 A runsUpsized from 12 AWG to control voltage drop

Storage water heaters of 120 gallons or less are treated as continuous loads by NEC 422.13, which is where the 125% factor above comes from.

Continuous loads: 24 amps, not 30

If a load runs for three hours or more, the branch circuit must be rated at least 125% of that load. Flip it around: a 30 A circuit can carry at most 30 × 0.80 = 24 A of continuous load. At 240 V that is 5,760 W; at 120 V, 2,880 W.

30 A

max breaker, 10 AWG copper

24 A

max continuous load on 30 A

5,760 W

continuous at 240 V

Voltage drop on 10 gauge wire

Ampacity keeps the wire cool. It does not keep the voltage up at the end of a long run. Using the single-phase formula L = VD × CM ÷ (2 × K × I), with K = 12.9 for copper and 10,380 circular mils for 10 AWG, here are the longest one-way runs that stay at or under 3%:

LoadAt 120 V (3.6 V)At 240 V (7.2 V)
16 A90 ft181 ft
20 A72 ft144 ft
24 A60 ft120 ft
30 A48 ft96 ft

Distances are rounded down. K = 12.9 is a conventional approximation, so treat these as planning numbers. For anything longer, step up to 8 AWG and run the numbers with the voltage drop formula. The 3% figure is a recommendation, not an NEC requirement; see NEC voltage drop: 3% and 5%.

Grounding, box fill and other 10 AWG details

  • Equipment grounding conductor: for a 30 A circuit, Table 250.122 requires at least 10 AWG copper (or 8 AWG aluminum). See equipment grounding conductor sizing.
  • Box fill: each 10 AWG conductor counts 2.50 in³ under Table 314.16(B)(1), compared with 2.25 in³ for 12 AWG. See box fill calculation.
  • Circular mils: 10,380 cmil (Chapter 9, Table 8), about 59% more area than 12 AWG (6,530 cmil).
  • Aluminum: 10 AWG aluminum is limited to 25 A by 240.4(D)(7). Small aluminum branch-circuit conductors need devices listed for aluminum. See aluminum vs copper wire.

Practice: 10 AWG exam questions

Exam-style question

Unless specifically permitted elsewhere, what is the maximum overcurrent protection for 10 AWG THHN copper conductors?

Pick an answer to see the explanation.

Exam-style question

An air-conditioning condenser nameplate lists an MCA of 27 A and an MOCP of 45 A. What is the minimum copper conductor size and maximum breaker size, with 60°C terminations?

Pick an answer to see the explanation.

Exam-style question

What is the maximum continuous load permitted on a 30-ampere branch circuit wired with 10 AWG copper?

Pick an answer to see the explanation.

How to find it fast in the code book

For any "how many amps" question on a small conductor, you need two places: Table 310.16 for the ampacity and 240.4(D) for the overcurrent limit. Tab both. Add 240.4(G) so you can quickly check whether the equipment in the question is one of the exceptions. For the bigger picture of how to read every column, start with the wire ampacity chart (NEC Table 310.16).

→The full ampacity chartWire Ampacity Chart: How to Read NEC Table 310.16

Next steps

10 AWG sits between the two sizes the exam tests most. Compare it with smaller conductors in 12 vs 14 gauge wire, and with the next size up in 8 AWG wire ampacity. If you are wiring a dryer or water heater, the standard breaker sizes guide covers the next-size-up rule in detail.

Then put it to work under the clock with the free journeyman practice test or the full timed practice tests.