The standard breaker sizes in the NEC are the ampere ratings listed in Table 240.6(A): 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000 and 6000 amperes. The same list applies to fuses, which also have standard ratings of 1, 3, 6 and 601 A.
On the exam, this list is rarely the question. It is the last step of the question: after you calculate a load or derate a conductor, the answer is the standard size that the rules allow. This guide gives you the full list, shows how the next-size-up rule works, and walks through the traps that turn a correct calculation into a wrong answer.
The complete list of standard breaker sizes (NEC Table 240.6(A))
NEC 240.6(A) lists the standard ampere ratings for fuses and inverse-time circuit breakers. Inverse-time is the normal thermal-magnetic breaker you find in every panel: the higher the overload, the faster it trips.
| Range | Standard ratings (amperes) | Step |
|---|---|---|
| 10 to 50 A | 10, 15, 20, 25, 30, 35, 40, 45, 50 | 5 A |
| 50 to 110 A | 60, 70, 80, 90, 100, 110 | 10 A |
| 110 to 250 A | 125, 150, 175, 200, 225, 250 | 25 A (15 A from 110 to 125) |
| 250 to 500 A | 300, 350, 400, 450, 500 | 50 A |
| 500 to 800 A | 600, 700, 800 | 100 A |
| Over 800 A | 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000 | varies |
| Fuses only | 1, 3, 6, 601 | — |
That is 38 ratings in the main list. The 601 A fuse rating exists because Class L fuses start above 600 A.
NEC 240.6(A) also says the use of fuses and inverse-time circuit breakers with nonstandard ratings is permitted. That is why you can buy, for example, a 17½ A time-delay fuse for a motor circuit. What the standard list controls is the meaning of "next higher standard rating" in NEC 240.4(B) and in other articles that refer to it, such as the motor rules.
Adjustable-trip breakers: 240.6(B) and (C)
Large breakers often have adjustable long-time pickup settings. Two rules decide which number counts as the rating:
- NEC 240.6(B): the rating is the maximum setting the breaker can be adjusted to. A 1,200 A frame adjustable down to 800 A is still a 1,200 A device for conductor protection.
- NEC 240.6(C): the rating may be the actual setting if access to the adjustment is restricted, for example behind removable and sealable covers, bolted equipment doors, locked doors accessible only to qualified personnel, or password protection with the password accessible only to qualified personnel.
This matters on master-level and industrial questions. On most journeyman exams, assume a plain thermal-magnetic breaker unless the question mentions adjustable trip.
The next-size-up rule: 240.4(B)
Conductor ampacities from Table 310.16 rarely match a breaker size. NEC 240.4(B) solves that: for devices rated 800 A or less, you may use the next higher standard rating above the conductor ampacity, if all three conditions are met:
- The conductors are not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads.
- The conductor ampacity does not correspond with a standard rating of a fuse or breaker (without overload trip adjustments above its rating).
- The next higher standard rating does not exceed 800 A.
The rule exists because forcing every conductor down to the next lower breaker would waste copper, and the small overshoot is acceptable when portable loads cannot be stacked onto multiple receptacles. The full set of conductor-protection rules, including the small-conductor limits, is in conductor overcurrent protection under NEC 240.4.
When you cannot round up
Rounding up is a permission with fences around it. These are the cases where the exam expects you to stop at or below the conductor ampacity:
- Branch circuits with more than one receptacle for cord-and-plug-connected portable loads. A general-purpose receptacle circuit gets a breaker no larger than its conductor ampacity.
- Above 800 A. NEC 240.4(C) requires the conductor ampacity to be equal to or greater than the rating of the device.
- Small conductors. NEC 240.4(D) caps copper at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG, regardless of Table 310.16, unless 240.4(E) or (G) applies. The background is in 12 vs 14 gauge wire and the small-conductor rule.
- Tap conductors. NEC 240.21 says 240.4(B) does not apply to taps. See feeder tap rules under NEC 240.21.
Worked examples: picking the right standard size
Rounding up after derating
- 1
The question
Six current-carrying 4 AWG THHN copper conductors share a raceway feeding equipment (not receptacles). Terminations are rated 75°C. What is the largest standard overcurrent device permitted for each conductor?
- 2
Start from the 90°C column
Table 310.16: 4 AWG THHN copper at 90°C = 95 A.
- 3
Apply the adjustment factor
Four to six current-carrying conductors: 80% (Table 310.15(C)(1)). 95 × 0.80 = 76 A.
- 4
Check the termination limit
At 75°C, 4 AWG copper = 85 A. The adjusted 76 A is lower, so 76 A governs.
- 5
Apply 240.4(B)
76 A is not a standard rating. The next higher standard rating is 80 A, which is under 800 A, and the circuit does not supply receptacles.
Sizing up for a continuous load
- 1
The question
A feeder supplies 120 A of continuous load and 40 A of noncontinuous load. What is the minimum standard overcurrent device?
- 2
Apply 125% to the continuous part only
120 × 1.25 = 150 A. Add the noncontinuous: 150 + 40 = 190 A.
- 3
Choose from 240.6(A)
The device may not be smaller than 190 A. The next standard rating is 200 A.
Over 800 A: no rounding
- 1
The question
A 1,000 A feeder will use parallel sets of copper conductors with 75°C terminations. Are three sets of 350 kcmil enough? Three sets of 400 kcmil?
- 2
350 kcmil
Table 310.16, 75°C: 310 A × 3 = 930 A. Less than 1,000 A. Under NEC 240.4(C) you cannot round up above 800 A, so this fails.
- 3
400 kcmil
335 A × 3 = 1,005 A. That is at least 1,000 A.
Standard sizes in other parts of the code
The 240.6(A) list is referenced well beyond Article 240. Three places show up on exams:
- Motors. NEC 430.52(C)(1) sets the maximum short-circuit and ground-fault device as a percentage of motor full-load current. Where that value does not correspond to a standard size, an exception permits the next higher standard size. The full method is in motor calculations under Article 430.
- HVAC equipment. The nameplate gives a maximum overcurrent protection (MOCP). You may not exceed it, so this is a "round down if needed" situation. See MCA vs MOCP.
- Equipment grounding conductors. NEC Table 250.122 is organized by the rating of the overcurrent device, so the standard size you pick also sets the EGC. See equipment grounding conductor sizing.
Common breaker sizes by application
These are typical pairings with copper conductors and 75°C terminations, for individual circuits that are not limited by the multi-receptacle rule. Always check the equipment nameplate and the actual load.
| Breaker | Typical copper conductor | Typical use |
|---|---|---|
| 15 A | 14 AWG | General lighting and receptacle circuits |
| 20 A | 12 AWG | Kitchen, laundry, bathroom, garage receptacles |
| 30 A | 10 AWG | Water heaters, dryers |
| 40 A | 8 AWG | Ranges, cooktops |
| 50 A | 8 AWG (6 AWG in NM cable) | Ranges, EV chargers, subpanels |
| 60 A | 6 AWG | Subpanels, tankless heaters |
| 100 A | 3 AWG | Subpanels and small services |
The feeder rows are covered in more detail in wire size for a 60 amp subpanel and wire size for a 100 amp service.
Exam-style questions
Exam-style question
Which of the following is NOT a standard ampere rating for an inverse-time circuit breaker?
Pick an answer to see the explanation.
Exam-style question
A conductor has an ampacity of 260 A after all adjustments. It feeds a panelboard and is not part of a multi-receptacle branch circuit. What is the maximum standard overcurrent device permitted?
Pick an answer to see the explanation.
Exam-style question
An adjustable-trip circuit breaker has a 1,200 A frame and its long-time setting can be adjusted from 600 A to 1,200 A. It is set at 800 A, and the adjustment is not behind any restricted-access means. What is its rating for conductor protection?
Pick an answer to see the explanation.
How to find the list fast on exam day
Table 240.6(A) sits in Part I of Article 240, only a few pages into the article. Tab it. It is one of the most-used tables in the book, and every breaker-sizing calculation ends there.
Write the gaps (55, 65, 75, 85, 95) in the margin if your testing rules allow handwritten notes in the book; many do not, so check your candidate bulletin. Either way, know that the list steps by 5 A up to 50, by 10 A up to 110, and by 25 A from 125 to 250.
→Category hub: branch circuits and protectionBranch Circuits Explained: NEC Article 210 for the ExamBreaker sizing connects to everything else in the branch-circuit category. Start from the branch circuits guide to NEC Article 210 to see how ratings, loads and receptacles fit together, then read NEC 240.4 for the conductor-protection side. When you are ready, put it under the clock with a free journeyman practice test.