MCA vs MOCP comes down to this: MCA (minimum circuit ampacity) tells you the smallest wire you may install, and MOCP (maximum overcurrent protection) tells you the largest breaker or fuse you may install. Both numbers are printed on the nameplate of the air conditioner, heat pump or other HVAC equipment, and the NEC requires you to use them instead of sizing the circuit like an ordinary load.
This guide explains where each number comes from, how to turn a nameplate into a wire size and a breaker size in under a minute, why a 35 A breaker on 12 AWG wire is not a mistake on an A/C circuit, and how the exam tests it.
What the two numbers mean
MCA: minimum circuit ampacity
- Sizes the conductors
- Wire ampacity must be equal to or greater than the MCA
- Already includes the 125% for the compressor
- Use Table 310.16 in the correct temperature column
MOCP: maximum overcurrent protection
- Sizes the fuse or breaker
- Device rating must be equal to or less than the MOCP
- Sized to let the compressor start
- May be marked 'Max fuse' or 'Max fuse or HACR breaker'
Equipment nameplates also show the compressor's RLA (rated-load amps), its LRA (locked-rotor amps) and the FLA of each fan motor. Those are the inputs the manufacturer used to calculate the MCA and MOCP. You normally only need them for disconnect sizing and for exam questions that ask you to do the calculation yourself.
How MCA is calculated (440.33)
The MCA is the 125% rule from motor circuits, applied to a hermetic compressor plus its fans. NEC 440.33 sizes conductors for several motor-compressors and motors at 125% of the largest motor-compressor's rated-load current (or branch-circuit selection current, if marked and larger) plus the sum of the other loads.
Typical MCA
MCA = 1.25 × compressor RLA + fan FLA + other loads
Check the nameplate MCA
- 1
Compressor
RLA 16.7 A × 1.25 = 20.875 A
- 2
Condenser fan
FLA 1.2 A at 100% = 1.2 A
- 3
Add
20.875 + 1.2 = 22.075 A → 22.1 A, which matches the nameplate
The term branch-circuit selection current (BCSC) shows up on some nameplates. It is a value the manufacturer marks when the compressor's protection allows a sustained current higher than the usual percentage of RLA. When BCSC is marked, it is used instead of RLA for conductors, the disconnect and the short-circuit protection, and it is always at least as large as the RLA.
How MOCP is set (440.22)
The breaker on an A/C circuit only has to clear short circuits and ground faults. The compressor has its own internal or external overload protection, so the breaker can be sized well above the running current to ride through the compressor's starting inrush.
For a single motor-compressor that you size yourself, NEC 440.22(A) permits a short-circuit and ground-fault device up to 175% of the rated-load current (or BCSC, whichever is greater). Its exceptions allow the next higher standard size where 175% doesn't land on one, up to 225% if the compressor still won't start, and never require a device smaller than 15 A.
For packaged equipment with a nameplate MOCP, NEC 440.22(C) makes the marked value the ceiling: the device may not exceed it, and the 175%/225% math no longer matters.
From nameplate to wire and breaker in three steps
Condensing unit: MCA 22.1 A, MOCP 35 A
- 1
Choose the wire from the MCA
Need an ampacity of at least 22.1 A. In Table 310.16: 12 AWG copper is 20 A (60°C) and 25 A (75°C); 10 AWG copper is 30 A (60°C).
- 2
Check the temperature column
THHN/THWN-2 in conduit with 75°C-rated terminations at both ends: 12 AWG copper (25 A) is acceptable. NM cable or 60°C terminations: 10 AWG copper (30 A).
- 3
Choose the breaker from the MOCP
Any standard breaker size up to 35 A that holds the compressor's start. If the nameplate says "HACR breaker," use a breaker marked HACR.
The temperature-column choice is covered in detail in our termination temperature ratings (110.14(C)) guide. The available breaker sizes are listed in standard breaker sizes.
Why 12 AWG on a 35 A breaker is legal
On a general-purpose circuit, NEC 240.4(D) limits 12 AWG copper to a 20 A overcurrent device. But NEC 240.4(G) lists specific conductor applications that follow their own articles instead, and air-conditioning and refrigeration equipment circuit conductors are on that list, pointing to Parts III and VI of Article 440.
The logic is the same as for motors:
- The breaker protects the conductors against short circuits and ground faults, so it can be large enough to start the compressor.
- The compressor's overload protection protects the conductors against overload, because the conductors were sized at 125% of the compressor current (that's what the MCA is).
Inspectors see this every day, and exam writers like it because candidates trained on the 240.4(D) rule instinctively reject it. The 240.4 overcurrent protection guide explains the full list in 240.4(G).
The disconnect for A/C equipment
Article 440, Part II, covers the disconnecting means:
- Location: within sight of the equipment and readily accessible NEC 440.14. That is why every condensing unit has a pull-out or fused disconnect on the wall next to it.
- Rating: the disconnect's ampere rating must be at least 115% of the nameplate rated-load current or branch-circuit selection current, whichever is greater NEC 440.12(A), and it must have an equivalent horsepower rating that accounts for the locked-rotor current.
For our 16.7 A RLA unit: 16.7 × 1.15 = 19.2 A minimum, so a standard 30 A or 60 A A/C disconnect easily qualifies.
Heat pumps and air handlers: two nameplates, two circuits
A split heat pump system usually has two pieces of equipment, each with its own MCA and MOCP:
- The outdoor unit (compressor and condenser fan).
- The indoor air handler with its blower and electric heat strips. The heat strips usually dominate this nameplate, and some air handlers list a different MCA/MOCP for each heat kit, or one per circuit if the heat kit is split.
Size each circuit from its own nameplate. Don't add the two together for the branch circuits. Adding them is a load calculation question (service or feeder), where you use the noncoincident and heat-pump rules in the standard method or in 220.82(C) of the optional method.
How MCA/MOCP differs from sizing a regular motor
| Ordinary motor (Article 430) | Hermetic A/C compressor (Article 440) | |
|---|---|---|
| Current you start from | Table FLC (430.248, 430.250) | Nameplate RLA or BCSC |
| Conductor sizing | 125% of table FLC (430.22) | Marked MCA (440.35) |
| Breaker/fuse | Table 430.52(C)(1), next size up allowed | Marked MOCP; may not exceed it |
| Overload | 430.32, from nameplate FLA | Built into the equipment |
How exam questions word MCA and MOCP
Exam items rarely say "MCA" and "MOCP" in plain terms. Learn to translate the phrasing:
| The question says | It means | You use |
|---|---|---|
| "minimum supply circuit conductor ampacity" | MCA | Wire ampacity at least this value |
| "maximum rating of the branch-circuit short-circuit and ground-fault protective device" | MOCP | Breaker or fuse no larger than this |
| "rated-load current" (RLA) | Compressor running current | 125% for conductors, 115% for the disconnect |
| "branch-circuit selection current" (BCSC) | Manufacturer's substitute for RLA | Use instead of RLA when it is marked |
| "locked-rotor current" (LRA) | Starting current | Disconnect horsepower equivalence |
If a question gives you RLA and fan FLA but no MCA, it wants the 440.33 calculation. If it gives you the MCA and MOCP, it wants you to read them and pick from Table 310.16 and the standard breaker list. Either way, the wire never comes from the MOCP.
Mistakes that cost points on HVAC questions
Sizing the wire from the MOCP. The MOCP is the breaker. The wire comes from the MCA.
Multiplying the MCA by 125% again. The 125% is already in the MCA. Wire ampacity ≥ MCA, nothing more.
Rounding the MOCP up to the next standard size. It's a maximum. The next-size-up exception in 440.22(A) is for a bare compressor you size at 175% yourself, not for a marked MOCP.
Applying 240.4(D) to A/C conductors. 240.4(G) sends them to Article 440.
Looking up the compressor in Table 430.250. Hermetic compressors use their nameplate RLA, not horsepower tables. See horsepower to amps for where those tables do apply.
Exam-style questions
Exam-style question
An air conditioner nameplate shows MCA 26.4 A and MOCP 40 A. Using copper THWN-2 with all terminations rated 75°C, what is the minimum conductor size?
Pick an answer to see the explanation.
Exam-style question
The same unit (MCA 26.4 A, MOCP 40 A) is wired with 10 AWG copper. What is the largest breaker permitted?
Pick an answer to see the explanation.
Exam-style question
A condensing unit has a compressor rated-load current of 18 A and a condenser fan of 1.5 A. What minimum circuit ampacity would be calculated under 440.33?
Pick an answer to see the explanation.
Next steps
HVAC nameplates show up on the exam as both branch-circuit questions (this guide) and as load lines in a service calculation. To see where the A/C load lands in a whole-house calculation, work through the dwelling load calculation standard method. For a second look at circuits where wire and breaker sizes don't match the usual pairs, read 10 gauge wire amps.
Article 440 is part of NFPA 70, readable through the NFPA 70 page. Then test yourself on nameplate questions with a free journeyman practice test.