NEC 240.4 is the rule that ties the breaker to the wire. It says conductors must be protected against overcurrent in accordance with their ampacities, then lists seven situations, (A) through (G), where the overcurrent device may be sized differently. If you understand those seven subsections, you can answer almost any "what size breaker for this conductor" question on the exam.

This guide walks through each subsection in plain language, shows a decision flow you can run in your head in ten seconds, and works through the calculations the exam uses to test them.

The general rule of NEC 240.4

The opening paragraph of NEC 240.4 covers conductors other than flexible cords, flexible cables and fixture wires (those are handled by NEC 240.5). It requires them to be protected against overcurrent in accordance with their ampacities as specified in 310.14, unless 240.4(A) through (G) permits or requires something else.

"Ampacity" here means the final ampacity after you apply everything that applies: the right temperature column, ambient temperature correction, the adjustment for more than three current-carrying conductors, and the termination limits of NEC 110.14(C). If any of that is shaky, review the wire ampacity chart guide for Table 310.16 and ampacity correction and adjustment factors first.

Find conductor ampacityMotor, A/C or other Table 240.4(G) load?Its articleTap or transformer secondary?(E) / (F)14, 12 or 10 AWG (or smaller)?(D) capsDevice over 800 A?(C) no roundMulti-receptacle branch circuit?No round upOtherwise: (B) next standard size up is allowedyesno
A quick decision flow for NEC 240.4: which subsection decides the maximum overcurrent device for a conductor.

240.4(A): Power loss hazard

NEC 240.4(A) covers circuits where opening the circuit on overload would be more dangerous than the overload itself. The classic example is a fire pump: you would rather the motor run to destruction than stop during a fire. In those cases, overload protection is not required, but the conductors must still have short-circuit protection.

This shows up on exams as a definition question. Remember the key phrase: overload protection may be omitted, short-circuit protection may not.

240.4(B): The next-size-up rule (800 A or less)

NEC 240.4(B) allows the next higher standard overcurrent device rating above the conductor ampacity, if all three conditions are met:

  1. The conductors are not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads.
  2. The conductor ampacity does not correspond with a standard rating of a fuse or circuit breaker without overload trip adjustments above its rating (other trip or rating adjustments are allowed).
  3. The next higher standard rating does not exceed 800 A.

"Standard rating" means the list in NEC 240.6(A). If you do not know that list cold, read standard breaker sizes under NEC 240.6(A) before going further.

Worked example

Next size up on a feeder

  1. 1

    The question

    A feeder uses 500 kcmil copper conductors with 75°C terminations, no adjustment or correction required. What is the largest overcurrent device permitted?

  2. 2

    Ampacity

    Table 310.16, 75°C column: 500 kcmil copper = 380 A.

  3. 3

    Check 240.4(B)

    380 A is not a standard rating. The next higher standard rating is 400 A, which is 800 A or less, and this is a feeder, not a multi-receptacle branch circuit.

  4. ✓ Answer: 400 A.

240.4(C): Over 800 A, the conductor must carry the full rating

NEC 240.4(C) is the other side of the 800 A line. If the overcurrent device is rated over 800 A, the conductor ampacity must be equal to or greater than the rating of the device. No rounding up.

Example: a 1,200 A service with four parallel sets of 350 kcmil copper at 75°C gives 4 × 310 = 1,240 A, which works. Four sets of 300 kcmil give 4 × 285 = 1,140 A, which does not, even though 1,140 A would round to 1,200 A under the 800 A rule.

240.4(D): Small conductors

NEC 240.4(D) is the most-tested part of 240.4. Unless NEC 240.4(E) or NEC 240.4(G) applies, the overcurrent protection for these conductors may not exceed the values below, after any correction and adjustment factors have been applied:

ConductorMax overcurrent protectionTable 310.16 ampacity (60 / 75 / 90°C)
14 AWG copper15 A15 / 20 / 25 A
12 AWG copper20 A20 / 25 / 30 A
10 AWG copper30 A30 / 35 / 40 A
12 AWG aluminum and copper-clad aluminum15 A15 / 20 / 25 A
10 AWG aluminum and copper-clad aluminum25 A25 / 30 / 35 A

240.4(D) also covers 18 AWG copper (7 A) and 16 AWG copper (10 A), but only when the specific conditions listed for those sizes in 240.4(D) are met. On a journeyman exam, the 14, 12 and 10 AWG rows are the ones that matter.

Worked example

Using the 90°C column with a small conductor

  1. 1

    The question

    Nine current-carrying 12 AWG THHN copper conductors are installed in one raceway in a 30°C ambient. Each circuit is a 120 V receptacle circuit. What is the maximum breaker for each circuit?

  2. 2

    Start at 90°C

    Table 310.16: 12 AWG THHN = 30 A.

  3. 3

    Adjust for 7 to 9 conductors

    Table 310.15(C)(1): 70%. 30 × 0.70 = 21 A.

  4. 4

    Apply 240.4(D)

    21 A is above the 20 A cap, so the cap governs. These are multi-receptacle circuits, so 240.4(B) rounding does not apply either.

  5. ✓ Answer: 20 A. If the adjusted ampacity had dropped below 20 A, you would need a smaller breaker or a larger conductor.

Why the extra cap? Small conductors have little thermal mass and are the wires most often overloaded by plug-in loads. The rule is explained in more depth in 12 vs 14 gauge wire and the small-conductor rule and 10 gauge wire amps.

240.4(E): Tap conductors

NEC 240.4(E) allows tap conductors to be protected under the rules written specifically for them rather than at their own ampacity. It points to the household cooking-appliance and other branch-circuit taps covered in 210.19, the fixture wire rules in 240.5, the feeder tap rules in 240.21, busway taps in 368.17 and motor-circuit taps in 430.53(D).

The one you must know for the exam is 240.21: the 10-foot tap, 25-foot tap, transformer tap and outside tap. Each has its own length limit and sizing condition, covered step by step in feeder tap rules under NEC 240.21.

240.4(F): Transformer secondary conductors

Normally a transformer secondary needs its own protection, because the primary device cannot "see" the secondary current one-to-one. NEC 240.4(F) makes an exception for two configurations:

  • a single-phase transformer with a 2-wire primary and a 2-wire secondary, and
  • a three-phase, delta-delta, 3-wire transformer.

For those, the secondary conductors may be protected by the primary overcurrent device, provided the primary protection complies with NEC 450.3 and does not exceed the secondary conductor ampacity multiplied by the secondary-to-primary voltage ratio.

Worked example

Secondary conductors protected by the primary device

  1. 1

    The question

    A single-phase transformer has a 2-wire 480 V primary and a 2-wire 240 V secondary. The primary is protected at 20 A in compliance with 450.3. What minimum secondary conductor ampacity lets the primary device protect the secondary conductors?

  2. 2

    Voltage ratio

    Secondary-to-primary ratio = 240 ÷ 480 = 0.5.

  3. 3

    Solve

    Primary OCPD ≤ secondary ampacity × 0.5, so secondary ampacity ≥ 20 ÷ 0.5 = 40 A.

  4. ✓ Answer: 40 A minimum, for example 8 AWG copper at 75°C (50 A).

A 120/240 V single-phase secondary is 3-wire, and a delta-wye transformer is not delta-delta, so neither qualifies. Those secondaries are covered by 240.21(C). For the transformer side of this, see transformer calculations and NEC 450.3.

240.4(G): Specific conductor applications

NEC 240.4(G) and its table send certain conductors to other articles for their overcurrent protection. The breaker may legally be larger than the conductor ampacity when that article allows it. Common entries:

  • Air-conditioning and refrigerating equipment (Article 440)
  • Motors and motor-control circuits (Article 430)
  • Motor-operated appliances (Article 422)
  • Electric welders (Article 630)
  • Fire alarm circuits (Article 760) and remote-control, signaling and power-limited circuits (the Class 1, 2 and 3 circuit articles)
  • Capacitor circuits, phase converters and secondary ties

That is why a condenser with a 12 AWG circuit can carry a 30 A or 35 A breaker: the conductor is sized from the minimum circuit ampacity and the breaker from the nameplate maximum. Read MCA vs MOCP and motor calculations under Article 430 for the full method.

Exam-style questions on NEC 240.4

Exam-style question

A 10 AWG copper conductor with THHN insulation supplies a general-purpose receptacle circuit. Ignoring any adjustment, what is the maximum overcurrent protection permitted?

Pick an answer to see the explanation.

Exam-style question

A conductor's ampacity is 85 A after adjustment. It supplies a single piece of fixed equipment. What is the maximum standard overcurrent device permitted?

Pick an answer to see the explanation.

Exam-style question

A 1,600 A overcurrent device protects parallel conductors. What is the minimum total ampacity of the conductors?

Pick an answer to see the explanation.

How to find NEC 240.4 fast

240.4 sits in Part I of Article 240, just ahead of the standard ratings table in 240.6(A). Tab the start of Article 240 and you have both on the same few pages. Highlight the words "800 amperes or less" in (B), the five small-conductor values in (D), and the heading of Table 240.4(G).

→Category hub: branch circuits and protectionBranch Circuits Explained: NEC Article 210 for the Exam

Conductor protection is where Article 210 and Article 240 meet. For the big picture, start with the branch circuits guide to NEC Article 210. For the tap and transformer cases, continue with the tap rules. Then test yourself with a free journeyman practice test.