Every feeder tap rule NEC 240.21(B) allows is an exception to one basic principle: conductors get their overcurrent protection where they receive their supply. A tap breaks that principle on purpose. A smaller conductor is connected to a larger feeder with no breaker at the splice, and the code makes it safe by keeping the tap short, sizing it against the upstream breaker, and ending it in a device that protects it from overload.

This guide covers each of the five feeder tap rules, the transformer secondary rules that follow the same logic, and the exam calculations built on them. You will be able to pick the right rule from the length in the question, apply its ratio, and size the conductor and the terminating breaker correctly.

What counts as a tap (and what does not)

Article 100 defines tap conductors as conductors, other than service conductors, that have overcurrent protection ahead of their point of supply that exceeds the value permitted for similar conductors protected as described elsewhere in 240.4. In plain words: a tap is a conductor too small for the breaker feeding it.

NEC 240.21 requires overcurrent protection at the point where conductors receive their supply, then lists exceptions in (A) through (H):

SubsectionCovers
240.21(A)Branch-circuit taps (as permitted in 210.19)
240.21(B)Feeder taps, the subject of most exam questions
240.21(C)Transformer secondary conductors
240.21(D)Service conductors
240.21(E)Busway taps
240.21(F)Motor circuit taps
240.21(G)Conductors from generator terminals
240.21(H)Battery conductors

Feeder taps may be made at any point on the load side of the feeder overcurrent device. And the most important sentence in 240.21(B): the provisions of 240.4(B) are not permitted for tap conductors. You never round up on a tap. The next-size-up rule is explained in NEC 240.4 conductor overcurrent protection.

400 AFeeder OCPDFeederPanel100 A main150 A10 ft max≥ load and ≥ 100 A≥ 1/10 × 400 A25 ft max≥ 1/3 × 400 A= 133.3 A minimum1/0 Cu = 150 ASingle breaker≤ tap ampacity
The two feeder tap rules you will see most: a 10-ft tap to a panelboard and a 25-ft tap ending in a single breaker.

The 10-foot tap rule: 240.21(B)(1)

Tap conductors not over 10 ft long are permitted if all of these are true:

  1. The tap ampacity is not less than the combined calculated loads on the circuits it supplies, and not less than the rating of the equipment containing an overcurrent device supplied by the tap, or the rating of the overcurrent device at the termination of the tap.
  2. The tap does not extend beyond the switchboard, switchgear, panelboard, disconnecting means or control devices it supplies.
  3. Except at the point of connection to the feeder, the tap is enclosed in a raceway extending from the tap to the enclosure of the device it supplies (or to the back of an open switchboard).
  4. For field installations where the tap leaves the enclosure or vault in which the tap is made, the feeder overcurrent device may not exceed 10 times the tap ampacity. Put the other way: the tap ampacity must be at least 1/10 of the feeder OCPD rating.
Worked example

10-foot tap to a panelboard

  1. 1

    The question

    A 400 A feeder breaker protects a feeder. A tap, 8 ft long, leaves the gutter and runs in conduit to a panelboard with a 100 A main breaker. The calculated load is 72 A. What is the minimum size copper tap conductor with 75°C terminations?

  2. 2

    Three minimums

    Load: 72 A. Downstream OCPD: 100 A. One-tenth of feeder OCPD: 400 ÷ 10 = 40 A.

  3. 3

    Take the largest

    The governing minimum is 100 A.

  4. 4

    Pick the conductor

    Table 310.16, 75°C: 3 AWG copper = 100 A.

  5. ✓ Answer: 3 AWG copper. 4 AWG (85 A) would fail the 100 A requirement even though it exceeds the load.

The 1/10 condition catches small taps from big feeders. A 30 A disconnect tapped from that same 400 A feeder with conductors leaving the enclosure needs a tap ampacity of at least 40 A, so 10 AWG copper (35 A at 75°C) is too small and 8 AWG (50 A) is the minimum, even though the disconnect is only 30 A.

The 25-foot tap rule: 240.21(B)(2)

Tap conductors over 10 ft but not over 25 ft are permitted if all of these are true:

  1. The tap ampacity is not less than one-third of the rating of the overcurrent device protecting the feeder.
  2. The tap terminates in a single circuit breaker or a single set of fuses that limits the load to the ampacity of the tap conductors. That device may supply any number of additional overcurrent devices on its load side.
  3. The tap conductors are protected from physical damage by an approved raceway or other approved means.
Worked example

25-foot tap from a 400 A feeder

  1. 1

    The question

    A 20 ft tap is made from a feeder protected at 400 A. What is the minimum copper tap conductor (75°C), and what is the largest breaker allowed at its end?

  2. 2

    One-third rule

    400 ÷ 3 = 133.3 A minimum ampacity.

  3. 3

    Pick the conductor

    Table 310.16, 75°C: 1 AWG = 130 A (too small). 1/0 AWG = 150 A.

  4. 4

    Terminating device

    The single breaker or set of fuses must limit the load to the tap ampacity: 150 A maximum. No rounding up to 175 A, because 240.4(B) does not apply to taps.

  5. ✓ Answer: 1/0 copper, ending in a breaker or fuses rated no more than 150 A.

Taps supplying a transformer: 240.21(B)(3)

This rule covers a tap that feeds a transformer primary, with the secondary continuing to a breaker. Conditions:

  1. Primary tap conductors: ampacity at least 1/3 of the feeder OCPD rating.
  2. Secondary conductors: their ampacity, multiplied by the secondary-to-primary voltage ratio, must be at least 1/3 of the feeder OCPD rating.
  3. The total length of one primary plus one secondary conductor, excluding any portion of the primary that is protected at its own ampacity, may not exceed 25 ft.
  4. Primary and secondary conductors are protected from physical damage by an approved raceway or other approved means.
  5. The secondary conductors terminate in a single circuit breaker or set of fuses that limits the load current to the ampacity of the conductors permitted by 310.14.
Worked example

Feeder tap to a 480-208Y/120 V transformer

  1. 1

    The question

    A 480 V feeder is protected at 300 A. A tap feeds a 480 V to 208Y/120 V transformer, and the combined primary and secondary length is 22 ft. Find the minimum primary and secondary copper conductor ampacities.

  2. 2

    Primary

    300 ÷ 3 = 100 A minimum. 3 AWG copper (100 A at 75°C) works.

  3. 3

    Secondary

    Voltage ratio, secondary to primary: 208 ÷ 480 = 0.4333. Secondary ampacity × 0.4333 ≥ 100 A, so secondary ampacity ≥ 100 ÷ 0.4333 = 230.8 A.

  4. 4

    Pick the secondary conductor

    4/0 copper = 230 A at 75°C, just short. 250 kcmil = 255 A.

  5. ✓ Answer: Primary at least 100 A (3 AWG Cu). Secondary at least 230.8 A (250 kcmil Cu), ending in a single breaker or set of fuses no larger than 255 A, which in practice means a 250 A device (no rounding up to 300 A). The transformer itself must still be protected under 450.3.

Transformer protection is a separate check, covered in transformer calculations and NEC 450.3.

Taps over 25 feet in high-bay buildings: 240.21(B)(4)

This one is narrow and shows up as a "which conditions apply" question. It is only for manufacturing buildings with walls more than 35 ft high, where conditions of maintenance and supervision ensure only qualified persons service the system. Conditions:

  • Horizontal length not over 25 ft; total length not over 100 ft.
  • Ampacity at least 1/3 of the feeder OCPD rating.
  • Terminates in a single breaker or set of fuses that limits the load to the tap ampacity.
  • Protected from physical damage by an approved raceway or other approved means.
  • Continuous from end to end with no splices.
  • At least 6 AWG copper or 4 AWG aluminum.
  • Does not penetrate walls, floors or ceilings.
  • The tap is made at least 30 ft above the floor.

Outside taps of unlimited length: 240.21(B)(5)

Outside feeder taps have no length limit and no ratio, if:

  1. The conductors are outside a building or structure, except at the point of load termination.
  2. They are protected from physical damage in an approved manner.
  3. They terminate in a single circuit breaker or single set of fuses that limits the load to their ampacity.
  4. That overcurrent device is part of, or immediately adjacent to, a disconnecting means.
  5. The disconnecting means is readily accessible: outside the building, inside nearest the point of entrance of the conductors, or where installed in accordance with 230.6.

If that list sounds like a service entrance, it should. Outside taps are treated much like service conductors, which is why the protection sits at the building. Compare with service-entrance conductors under Article 230.

Transformer secondary conductors: 240.21(C)

Transformer secondaries follow the same pattern as feeder taps, with the ratios applied through the transformer's primary-to-secondary voltage ratio. The ones to know:

  • (C)(1) Secondary protected by the primary OCPD: only for the 2-wire to 2-wire single-phase and 3-wire delta-delta cases in 240.4(F).
  • (C)(2) Secondary conductors not over 10 ft, with conditions similar to the 10-foot feeder tap.
  • (C)(3) Industrial installations, not over 25 ft, where maintenance and supervision ensure only qualified persons service the system.
  • (C)(4) Outside secondary conductors, unlimited length, conditions similar to outside taps.
  • (C)(5) Secondary conductors from a transformer fed by a 240.21(B)(3) feeder tap.
  • (C)(6) Secondary conductors not over 25 ft: ampacity at least the primary-to-secondary voltage ratio multiplied by 1/3 of the primary OCPD rating, ending in a single breaker or set of fuses.

The secondary side has no 240.4(B) rounding either. The bonding and grounding of these conductors is in supply-side bonding jumper sizing.

→Transformer currents and 450.3 protectionTransformer Calculations and Overcurrent Protection (NEC 450.3)

Grounding with taps

A wire-type equipment grounding conductor run with feeder tap conductors is sized from Table 250.122 under NEC 250.122(G) using the rating of the feeder overcurrent device ahead of the tap, not the breaker at the end of the tap. It never needs to be larger than the tap's ungrounded conductors. For the table itself, see equipment grounding conductor sizing.

Exam-style questions on the tap rules

Exam-style question

A 15-ft feeder tap is made from a feeder protected by a 600 A overcurrent device. What is the minimum ampacity of the tap conductors?

Pick an answer to see the explanation.

Exam-style question

A 25-ft tap has an ampacity of 165 A. Which terminating overcurrent device is permitted?

Pick an answer to see the explanation.

Exam-style question

Which of the following is a condition of the 10-foot tap rule when the tap conductors leave the enclosure in which the tap is made?

Pick an answer to see the explanation.

Mistakes that cost points on tap questions

Using the wrong rule for the length. Up to 10 ft: (B)(1). Over 10 ft to 25 ft: (B)(2). Over 25 ft: only (B)(4) in high-bay manufacturing, or (B)(5) outside.

Forgetting the downstream device in the 10-foot rule. The tap must be at least as large as the breaker or equipment rating it feeds, not just the load.

Rounding the terminating breaker up. 240.4(B) is not permitted for taps.

Using the primary-to-secondary ratio backwards. For (B)(3), multiply the secondary ampacity by the secondary-to-primary ratio. A smaller ratio means a larger secondary conductor.

How to find the tap rules fast

240.21 is in Part II of Article 240, "Location." Tab it. Inside, highlight the length in each heading of 240.21(B)(1) through (B)(5), and the fraction in each rule. On exam day you will read the length in the question, jump to the matching heading, and apply its fraction.

→Category hub: branch circuits and protectionBranch Circuits Explained: NEC Article 210 for the Exam

Tap rules sit next to the rest of the overcurrent material in this category. Start with the branch circuits guide for the big picture, then standard breaker sizes for the ratings every tap calculation ends on. When the fractions feel automatic, try them on a timed journeyman practice test. For an independent explanation of the same rules, Electrical Construction & Maintenance has a good overview of NEC rules for tapping feeders.