Equipment grounding conductor sizing is done with NEC Table 250.122, and it depends on one number: the rating of the breaker or fuse protecting the circuit. Find that rating in the left column, round up to the next row if it falls between rows, and read the minimum copper or aluminum size. A 20 A circuit needs a 12 AWG copper EGC, a 60 A circuit needs 10 AWG copper, and a 200 A feeder needs 6 AWG copper.

That is the easy 80% of the topic. The rest is where exam points are lost: the round-up trap, proportional upsizing for voltage drop, parallel raceways, motor circuits and the "not larger than the circuit conductors" cap. This guide covers each one under the 2023 NEC with worked examples you can repeat on exam day.

What the equipment grounding conductor does

The equipment grounding conductor (EGC) is the conductive path that connects normally non-current-carrying metal parts of equipment together and to the system grounded conductor, the grounding electrode conductor, or both (NEC Article 100). It is the bonding half of grounding vs bonding: when a hot conductor faults to a metal box or enclosure, the EGC carries the fault current back to the source so the overcurrent device opens.

That is why it is sized from the overcurrent device. The EGC has one job: carry enough fault current, for long enough, to let the breaker or fuse do its work. A bigger breaker lets through more fault current before it opens, so it needs a bigger EGC.

The EGC is not the same thing as the grounding electrode conductor, which connects the service to the earth and is sized from the service conductors with Table 250.66. If you mix those two tables up on an exam, you will get the question wrong every time.

NEC Table 250.122: the full table

The left column is titled "Rating or Setting of Automatic Overcurrent Device in Circuit Ahead of Equipment, Conduit, etc., Not Exceeding (Amperes)." Those two words, "not exceeding," are the whole round-up rule.

OCPD rating, not exceeding (A)CopperAluminum or copper-clad aluminum
1514 AWG12 AWG
2012 AWG10 AWG
6010 AWG8 AWG
1008 AWG6 AWG
2006 AWG4 AWG
3004 AWG2 AWG
4003 AWG1 AWG
5002 AWG1/0 AWG
6001 AWG2/0 AWG
8001/0 AWG3/0 AWG
10002/0 AWG4/0 AWG
12003/0 AWG250 kcmil
16004/0 AWG350 kcmil
2000250 kcmil400 kcmil
2500350 kcmil600 kcmil
3000400 kcmil600 kcmil
4000500 kcmil800 kcmil
5000700 kcmil1200 kcmil
6000800 kcmil1200 kcmil

A note under the table warns that where necessary to comply with NEC 250.4(A)(5), the EGC must be sized larger than the table shows. The table is a minimum. On very long runs, the impedance of a minimum-size EGC can be too high to trip the breaker quickly, which is exactly the situation the upsizing rule below addresses.

10 AWG Cu

EGC for any OCPD over 20 A up to 60 A

6 AWG Cu

EGC for a 200 A feeder

1/0 Cu

EGC for an 800 A feeder

How to size an EGC in four steps

1. Rating of the breaker or fuseahead of the circuit (not the load)2. Table 250.122"not exceeding": round UP to next row3. Hots upsized beyond minimum?(voltage drop, future load, etc.)NoYesUse the table sizeas read in step 2Multiply EGC cmil bynew hot cmil ÷ minimum cmil4. Parallel raceways?Full-size EGC in each racewayNever required larger than the hots
Decision flow for equipment grounding conductor sizing under NEC 250.122.

Step 1: Use the overcurrent device rating

Read the rating of the breaker or fuse protecting the circuit, feeder, or equipment. Do not use the calculated load, the conductor ampacity or the nameplate current. If a question gives you a 40 A load on a 50 A breaker, the EGC is sized for 50 A.

Step 2: Read Table 250.122, rounding up

Find the first row that is equal to or greater than the OCPD rating. Copper and aluminum (or copper-clad aluminum) have separate columns.

Step 3: Check for upsized conductors

If the ungrounded conductors are larger than the minimum needed for the load, the EGC may have to grow with them under NEC 250.122(B). More on this below, because it is the calculation the exam likes most.

Step 4: Check the special cases

Parallel runs (NEC 250.122(F)), multiple circuits in one raceway (NEC 250.122(C)), motor circuits (NEC 250.122(D)) and feeder taps (NEC 250.122(G)) each have their own wording. Then apply the cap in NEC 250.122(A): the EGC is not required to be larger than the circuit conductors supplying the equipment.

Proportional upsizing under 250.122(B)

The logic: if you upsized the hots because the run is long (voltage drop), the EGC on that same long run has more impedance too. Upsizing it by the same ratio keeps the fault path as effective as it would be on a short run.

Two key details:

  • Derating does not count. Conductors increased because of ambient temperature correction or more than three current-carrying conductors (NEC 310.15(B) and NEC 310.15(C)) do not trigger proportional upsizing.
  • Use circular mils, not AWG numbers. Look up both conductor areas in Chapter 9, Table 8. The ratio of the actual hot to the minimum hot is the multiplier.

250.122(B) proportional increase

Minimum EGC cmil = Table 250.122 EGC cmil × (installed hot cmil ÷ minimum hot cmil)

Circular mil areas you will need (Chapter 9, Table 8):

SizeArea (cmil)SizeArea (cmil)
14 AWG4,1102 AWG66,360
12 AWG6,5301 AWG83,690
10 AWG10,3801/0 AWG105,600
8 AWG16,5102/0 AWG133,100
6 AWG26,2403/0 AWG167,800
4 AWG41,7404/0 AWG211,600
3 AWG52,620250 kcmil250,000
Worked example

20 A branch circuit upsized for voltage drop

  1. 1

    The question

    A 20 A, 120 V branch circuit to a detached sign would normally use 12 AWG copper. Because of the length, the electrician installs 10 AWG copper ungrounded and grounded conductors. What is the minimum copper EGC?

  2. 2

    Table size

    Table 250.122, 20 A row: 12 AWG copper (6,530 cmil).

  3. 3

    Ratio

    10 AWG ÷ 12 AWG = 10,380 ÷ 6,530 = 1.59.

  4. 4

    Apply the ratio

    6,530 × 1.59 = 10,383 cmil. Using the unrounded ratio, it is exactly 10,380 cmil, the area of 10 AWG.

  5. ✓ Answer: 10 AWG copper EGC. On small circuits the answer is simply "the EGC matches the upsized hots."
Worked example

200 A feeder upsized from 3/0 to 250 kcmil

  1. 1

    The question

    A 200 A feeder would require 3/0 AWG copper ungrounded conductors. For voltage drop, 250 kcmil copper is installed. What is the minimum copper EGC?

  2. 2

    Table size

    Table 250.122, 200 A row: 6 AWG copper = 26,240 cmil.

  3. 3

    Ratio

    250,000 ÷ 167,800 = 1.4899.

  4. 4

    Apply the ratio

    26,240 × 1.4899 = 39,095 cmil.

  5. 5

    Pick a size

    6 AWG (26,240) is too small. The next size with at least 39,095 cmil is 4 AWG (41,740 cmil). Always round up to the next standard size.

  6. ✓ Answer: 4 AWG copper EGC, not the 6 AWG the table alone would give.

For the voltage drop side of this calculation, see the voltage drop formula guide. Exam questions often give you the upsized conductor directly and only ask for the EGC.

Parallel conductors: a full-size EGC in every raceway

NEC 250.122(F) covers circuits with conductors in parallel. When the parallel sets are in separate raceways, a wire-type EGC is installed in each raceway, and each one is sized from Table 250.122 using the rating of the overcurrent device protecting the whole parallel set. You do not divide it by the number of raceways.

Worked example

800 A feeder in three conduits

  1. 1

    The question

    An 800 A feeder consists of three parallel sets of copper conductors, each set in its own PVC conduit. What copper EGC is required in each conduit?

  2. 2

    Table 250.122

    800 A row: 1/0 AWG copper.

  3. 3

    Apply 250.122(F)

    Each conduit gets its own EGC sized for the 800 A device. Do not divide 1/0 by three.

  4. ✓ Answer: One 1/0 AWG copper EGC in each of the three conduits (three total).

If the parallel sets are all in a single raceway, auxiliary gutter or cable tray, one wire-type EGC sized for the OCPD is enough. For multiconductor cables in parallel, each cable's EGC is sized from the OCPD rating as well (NEC 250.122(F)(2)). Parallel installations show up often in 400 amp service and larger feeder questions.

Multiple circuits, motors and taps

Several circuits in one raceway: 250.122(C)

When a single EGC is run with multiple circuits in the same raceway, cable, trench or cable tray, it is sized for the largest overcurrent device protecting conductors in that raceway. A conduit carrying 20 A, 30 A, 50 A and 60 A circuits can use one 10 AWG copper EGC, because 60 A is the largest OCPD.

Motor circuits: 250.122(D)

For a motor branch circuit, the EGC is sized from Table 250.122 using the rating of the motor branch-circuit short-circuit and ground-fault protective device (the breaker or fuse sized under NEC 430.52), not the overload rating. Motor breakers are often sized well above the motor current, and this is where the cap in 250.122(A) earns its keep.

Worked example

Motor circuit: the cap applies

  1. 1

    The question

    A motor circuit uses 10 AWG copper conductors and is protected by a 70 A inverse time breaker selected under 430.52. What size copper EGC is required?

  2. 2

    Table 250.122

    70 A is over 60 A, so use the 100 A row: 8 AWG copper.

  3. 3

    Apply the cap

    NEC 250.122(A) and NEC 250.122(D)(1): the EGC is not required to be larger than the circuit conductors. The circuit conductors are 10 AWG.

  4. ✓ Answer: 10 AWG copper. The table says 8 AWG, but the EGC never needs to exceed the 10 AWG circuit conductors.

Motor breaker sizing is covered in motor calculations under Article 430.

Feeder taps: 250.122(G)

For feeder taps, the EGC is sized from the rating of the overcurrent device ahead of the feeder on the supply side of the tap, but it is not required to be larger than the tap conductors. See the tap rules in 240.21.

→Where tap conductors get their limitsFeeder Tap Rules: The 10-Foot and 25-Foot Taps (NEC 240.21)

When the raceway is the EGC

A wire is not the only kind of EGC. NEC 250.118 lists the types, including rigid metal conduit, intermediate metal conduit, electrical metallic tubing, and, with conditions, flexible metal conduit, liquidtight flexible metal conduit and the armor of certain cables. Table 250.122 and the proportional rule in 250.122(B) apply to wire-type EGCs.

The conditions on flexible conduit are where exams set traps. Listed flexible metal conduit qualifies as an EGC only when, among other conditions, it is terminated in listed fittings, the circuit is protected at 20 A or less, the combined length of flexible metal conduit, flexible metallic tubing and liquidtight flexible metal conduit in the same ground-fault return path does not exceed 6 ft, and the conduit is not installed for flexibility after installation (NEC 250.118(A)(5)). The 2023 NEC also added a condition for stainless steel FMC and LFMC: they need a wire-type EGC or a bonding jumper rather than serving as the EGC on their own. Outside those limits, you pull a wire-type EGC sized from Table 250.122.

Exam questions on EGC sizing

Exam-style question

What is the minimum size copper equipment grounding conductor for a circuit protected by a 40 A circuit breaker?

Pick an answer to see the explanation.

Exam-style question

A 225 A feeder is protected by a 225 A breaker. What is the minimum aluminum equipment grounding conductor?

Pick an answer to see the explanation.

Exam-style question

The ungrounded conductors of a 100 A feeder are increased from 3 AWG to 1/0 AWG copper to limit voltage drop. Table 250.122 requires an 8 AWG copper EGC. What is the minimum copper EGC after the increase?

Pick an answer to see the explanation.

Exam-style question

A 400 A feeder is run as two parallel sets in two separate rigid metal conduits, and a wire-type EGC is installed. What is the minimum copper EGC in each conduit?

Pick an answer to see the explanation.

Common EGC sizing mistakes

Rounding down between rows. "Not exceeding" means round up. 30 A uses the 60 A row.

Sizing from the load or the wire. The EGC is sized from the OCPD rating.

Using Table 250.66. That is for the GEC, sized from service conductors. The EGC uses Table 250.122.

Upsizing for derating. Conductors increased because of temperature correction or bundling (310.15(B) and (C)) do not trigger 250.122(B).

Dividing the EGC in parallel runs. Each raceway gets a full-size EGC.

Forgetting the cap. A motor circuit with a large breaker does not need an EGC bigger than its circuit conductors.

Finding it fast in the code book

Table 250.122 sits in Part VI of Article 250, right after 250.119 (identification of EGCs), 250.120 (installation) and 250.121 (use of EGCs). Tab the table itself, and write "round UP" and "upsize: cmil ratio" next to it in the margin if your testing rules allow notes. Keep Chapter 9, Table 8 tabbed too, because every 250.122(B) question needs it.

EGC sizing is one part of the bigger grounding and bonding picture. Go next to grounding electrode conductor size so the two tables never blur together, and review grounded vs grounding conductor terminology. Then put it under the clock with the free journeyman practice test.