Grounding electrode conductor size is found in NEC Table 250.66, using the size of the largest ungrounded service-entrance conductor. Read across to the copper or aluminum GEC column: a service with 3/0 copper conductors needs a 4 AWG copper GEC, and nothing is ever required to be larger than 3/0 copper. Then check the three electrode-specific limits in 250.66(A), (B) and (C), which often let you use a smaller conductor to rods, a Ufer, or a ground ring.

By the end of this guide you will be able to size a GEC for a single or parallel service, size each bonding jumper in a multi-electrode system, and avoid the table mix-ups that make GEC questions some of the most missed on the journeyman exam.

What the grounding electrode conductor does

The grounding electrode conductor (GEC) connects the system grounded conductor (the neutral), the equipment, or both, to a grounding electrode or to a point on the grounding electrode system (NEC Article 100). At a service, it runs from the neutral bus or the equipment grounding terminal in the service equipment to the electrodes (NEC 250.24(E)).

It is the grounding half of grounding vs bonding. The GEC carries lightning and surge current into the earth and holds the system at a stable voltage to ground. It does not carry ordinary ground-fault current back to the source; that is the equipment grounding conductor's job.

That is why the GEC is sized from the service conductors and has a ceiling. Because it is not the path that clears ground faults, a bigger GEC past a certain point adds little; the NEC caps it at 3/0 copper (250 kcmil aluminum). The same table sizes the GEC for a separately derived system (NEC 250.30(A)(5)) and for a building supplied by a feeder (NEC 250.32(E)), using the largest ungrounded supply conductor.

NEC Table 250.66: the full table

Largest ungrounded service conductor: copperLargest ungrounded service conductor: aluminum or copper-clad aluminumGEC: copperGEC: aluminum or copper-clad aluminum
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 or 1/0 AWG2/0 or 3/0 AWG6 AWG4 AWG
2/0 or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
Over 3/0 AWG through 350 kcmilOver 250 kcmil through 500 kcmil2 AWG1/0 AWG
Over 350 kcmil through 600 kcmilOver 500 kcmil through 900 kcmil1/0 AWG3/0 AWG
Over 600 kcmil through 1100 kcmilOver 900 kcmil through 1750 kcmil2/0 AWG4/0 AWG
Over 1100 kcmilOver 1750 kcmil3/0 AWG250 kcmil

The notes to the table matter on exam questions:

  • Parallel sets: where multiple sets of service-entrance conductors connect directly to a service drop or lateral, the "equivalent size" is the sum of the areas of the corresponding conductors of each set.
  • No service-entrance conductors: where there are none (for example, the service disconnect is fed directly from the utility's conductors), size the GEC from the equivalent size of the largest service-entrance conductor that would be required for the load.

The electrode limits: 250.66(A), (B) and (C)

Table 250.66 gives the size for the GEC in general, for example to the metal underground water pipe or building steel. But for three electrode types, the NEC sets a maximum that is smaller than the table often requires, because those electrodes cannot use a bigger conductor.

ElectrodeMaximum GEC or bonding jumper requiredRule
Rod, pipe, or plate electrodes6 AWG copper / 4 AWG aluminumNEC 250.66(A)
Concrete-encased electrode4 AWG copperNEC 250.66(B)
Ground ringSize of the ring conductor (2 AWG copper minimum ring)NEC 250.66(C)

The condition in each case: the conductor goes only to that type of electrode and does not continue on to another electrode type that needs a larger conductor. If one GEC runs to a ground rod and then continues to the water pipe, the whole run must meet the water pipe size.

Service350 kcmil CuWater pipeTable 250.662 AWG CuUfer (CEE)250.66(B)4 AWG CuGround rods250.66(A)6 AWG CuGround ring250.66(C)= ring sizeEach limit applies only if that conductor goes to that electrode type alone
One service, four electrodes, four different maximum sizes. Example based on 350 kcmil copper service conductors.

For the electrodes themselves, see the ground rod requirements guide and the Ufer ground guide.

Worked examples: sizing the GEC

Worked example

200 A dwelling service with aluminum conductors

  1. 1

    The question

    A 200 A dwelling service uses 4/0 AWG aluminum service-entrance conductors. The GEC is copper and runs to the metal underground water pipe. What is the minimum size?

  2. 2

    Choose the columns

    Service conductors are aluminum → aluminum service column. GEC is copper → copper GEC column.

  3. 3

    Read the row

    4/0 AWG aluminum falls in the "4/0 AWG or 250 kcmil" row.

  4. ✓ Answer: 4 AWG copper (or 2 AWG aluminum if the GEC were aluminum).

The 4/0 aluminum conductor comes from the dwelling service rule in NEC 310.12; the 200 amp service wire size guide explains where it comes from.

Worked example

Parallel service: add the areas

  1. 1

    The question

    A service has two parallel sets of 250 kcmil copper conductors per phase. What is the minimum copper GEC to the building steel?

  2. 2

    Equivalent area

    2 × 250 kcmil = 500 kcmil copper.

  3. 3

    Read the row

    500 kcmil falls in "Over 350 through 600 kcmil."

  4. ✓ Answer: 1/0 AWG copper. Using one 250 kcmil conductor (2 AWG row) would be the classic mistake.
Worked example

Large service: the 3/0 ceiling

  1. 1

    The question

    A service has three parallel sets of 500 kcmil copper per phase. What is the minimum copper GEC to the water pipe?

  2. 2

    Equivalent area

    3 × 500 = 1500 kcmil, which is over 1100 kcmil.

  3. ✓ Answer: 3/0 AWG copper, the largest GEC Table 250.66 ever requires.
Worked example

One service, several electrodes

  1. 1

    The question

    A commercial building has a 350 kcmil copper service. Present at the building: metal underground water pipe, a concrete-encased electrode in the footing, and two ground rods added to supplement the water pipe. Size each conductor if each electrode has its own conductor from the service.

  2. 2

    Table 250.66

    350 kcmil copper falls in "Over 3/0 through 350 kcmil" → 2 AWG copper.

  3. 3

    Water pipe

    No special limit → 2 AWG copper.

  4. 4

    Concrete-encased electrode

    NEC 250.66(B): not required larger than 4 AWG copper.

  5. 5

    Ground rods

    NEC 250.66(A): not required larger than 6 AWG copper.

  6. ✓ Answer: 2 AWG Cu to the water pipe, 4 AWG Cu to the CEE, 6 AWG Cu to the rods. If one conductor were run from the rods on to the water pipe, it would have to be 2 AWG Cu all the way.

Table 250.66 vs Table 250.102(C)(1) vs Table 250.122

These three tables are where most grounding questions are won or lost.

TableSizesBased onLargest value
250.66Grounding electrode conductorLargest ungrounded service conductor3/0 Cu / 250 kcmil Al
250.102(C)(1)Main, system and supply-side bonding jumpers; grounded conductor minimum at the serviceLargest ungrounded supply conductorNo cap: 12.5% rule above 1100 kcmil Cu
250.122Equipment grounding conductorOCPD rating800 kcmil Cu at 6000 A

Tables 250.66 and 250.102(C)(1) share identical rows up to 1100 kcmil copper. Above that, the GEC stops at 3/0 copper and the bonding jumper keeps growing, because a bonding jumper must carry the full fault current back to the source. The bonding side is covered in the main bonding jumper and supply-side bonding jumper guides, and the load side in equipment grounding conductor sizing.

→The other table people confuseEquipment Grounding Conductor Sizing: NEC Table 250.122

Installing the GEC: 250.64 essentials

Sizing is half the question. NEC 250.64 covers how the GEC is installed, and the exam pulls from it often.

Protection (NEC 250.64(B)). A 6 AWG or larger copper GEC that is not exposed to physical damage can run along the surface of the building without a metal covering. Where it is exposed to physical damage, it must be protected, for example in rigid metal conduit, IMC, Schedule 80 PVC, EMT or cable armor. A GEC smaller than 6 AWG (so 8 AWG copper) must always be protected in one of those enclosures.

Continuous (NEC 250.64(C)). The GEC is installed in one continuous length without a splice or joint, except splices made with irreversible compression-type connectors listed as grounding and bonding equipment, exothermic welding, or connections to busbars.

Ferrous enclosures (NEC 250.64(E)). A steel raceway around a GEC must be bonded at both ends to the GEC or the electrode. Otherwise the steel acts as a choke on surge current. This is why you see a bonding bushing at each end of a short steel nipple around a GEC.

Aluminum (NEC 250.64(A)). Bare or covered aluminum or copper-clad aluminum GECs are not permitted in direct contact with masonry or the earth, or where subject to corrosive conditions, and outside they must terminate at least 18 inches above the earth.

Multiple disconnects (NEC 250.64(D)). Where a service has several disconnecting means in separate enclosures, you can run a common GEC with taps, individual GECs from each enclosure, or a single GEC from a common location such as a wireway.

Exam questions on GEC sizing

Exam-style question

A service has 500 kcmil copper ungrounded service-entrance conductors. What is the minimum size copper grounding electrode conductor to the metal underground water pipe?

Pick an answer to see the explanation.

Exam-style question

A 400 A service uses 600 kcmil copper conductors. The only grounding electrodes are two ground rods. What is the minimum size copper conductor to the rods?

Pick an answer to see the explanation.

Exam-style question

A service consists of three parallel sets of 400 kcmil copper per phase. What is the minimum copper GEC to building structural steel?

Pick an answer to see the explanation.

Common GEC sizing mistakes

Sizing from the main breaker. The GEC is based on conductor size, not the OCPD rating.

Using one conductor of a parallel set. Add the areas of the parallel conductors in one phase.

Running the table size to a ground rod. 6 AWG copper is the most a rod-only conductor ever needs.

Mixing up the material columns. Service conductor material picks the left column; GEC material picks the right column.

Using Table 250.66 for a large bonding jumper. Above 1100 kcmil copper, bonding jumpers use the 12.5% rule, not 3/0.

Leaving 8 AWG unprotected. A GEC smaller than 6 AWG must be in a raceway or cable armor.

Find it fast in the code book

Table 250.66 is in Part III of Article 250, right after NEC 250.64 (installation) and before NEC 250.68 and NEC 250.70 (connections). Write "6 rod / 4 CEE / ring" next to the table if your test allows it. The IAEI article on sizing grounding and bonding conductors is a good second read on how the three tables relate.

For the full grounding and bonding picture, start from the grounding vs bonding hub. Then test your table speed with the free journeyman electrician practice test.