The 200 amp service wire size for a house is 2/0 AWG copper or 4/0 AWG aluminum, as long as the conductors supply the entire dwelling load on a 120/240-volt single-phase system. NEC 310.12 lets those conductors have just 83% of the service rating, which is 166 A. That is why the familiar 4/0 aluminum SER works on a 200 A residential service even though Table 310.16 lists it at 180 A.

This guide shows exactly where the 83% rule comes from, when you lose it, what size to use instead, and how to size the neutral, the grounding electrode conductor and the equipment ground. It ends with exam questions built on the mistakes most candidates make.

200 amp service wire size: the answer by situation

All values assume conductors rated 75°C or higher (THHN/THWN-2, XHHW-2, SER, USE-2) and terminals rated 75°C, which is standard for 200 A meter sockets, panelboards and main breakers.

SituationRuleMinimum ampacityCopperAluminum
Dwelling service, entire load, 120/240 V 1ØNEC 310.12(A)166 A2/0 (175 A)4/0 (180 A)
Dwelling main feeder, entire loadNEC 310.12(B)166 A2/0 (175 A)4/0 (180 A)
Subpanel feeder, full 200 ATable 310.16, 75°C200 A3/0 (200 A)250 kcmil (205 A)
Subpanel feeder, load ≤ 180 ANEC 240.4(B)load3/04/0 (180 A)
Commercial or three-phase 200 ATable 310.16, 75°C200 A3/0 (200 A)250 kcmil (205 A)

Ampacities are from the 75°C column of NEC Table 310.16. If any of those columns feel unfamiliar, start with the wire ampacity chart guide for Table 310.16.

Where the 83% rule comes from: NEC 310.12

The 83% rule is in NEC 310.12, "Single-Phase Dwelling Services and Feeders." It was moved there in the 2020 NEC from the old 310.15(B)(7), and the 2023 NEC keeps the same 83% approach for services and feeders rated 100 through 400 A.

Five conditions, all required:

  1. Dwelling: a one-family dwelling or an individual dwelling unit.
  2. Single-phase, 120/240 V supply. (2023 also allows a single-phase dwelling feeder of two hots and a neutral from a 208Y/120 V system; see below.)
  3. Entire load: the conductors supply the whole dwelling unit, not one panel out of two.
  4. Rating 100 through 400 A.
  5. Service conductors, or the feeder that carries the entire load (for example, from a meter-main to the only panelboard).

310.12 also includes a table of conductor sizes for when no correction or adjustment factors apply: Table 310.12(A) in the 2023 NEC (it was Table 310.12 in 2020). Every size in it is simply the 83% value read from the 75°C column, so if you can do the math you never need to memorize the table.

RatingCopperAluminum
100 A4 AWG2 AWG
125 A2 AWG1/0
150 A1 AWG2/0
200 A2/04/0
225 A3/0250 kcmil
300 A250 kcmil350 kcmil
400 A400 kcmil600 kcmil

These rows come from Table 310.12(A); the table also lists 110, 175, 250 and 350 A.

Dwelling service or main feeder

0.83 × 200 A = 166 A → 2/0 Cu (175 A) or 4/0 Al (180 A)

75°C ampacity (Table 310.16)1501/0 Cu1752/0 Cu2003/0 Cu1553/0 Al1804/0 Al205250 Al166 A200 A
How 166 A lands in the 75°C column of Table 310.16: 2/0 copper and 4/0 aluminum are the first sizes at or above it.

When you cannot use 2/0 copper or 4/0 aluminum

These are the situations that put you back on Table 310.16 at the full rating.

A subpanel or second panel. A 200 A feeder from the house panel to a shop or garage supplies only part of the load. Likewise, a 400 A dwelling service split into two 200 A panels: each 200 A feeder carries only half the house, so 310.12(B) does not apply to it as written. Size each at 200 A: 3/0 Cu or 250 kcmil Al, or 4/0 Al through 240.4(B) if the calculated load is 180 A or less. The 400 amp service wire size guide covers that layout.

A non-dwelling building. A 200 A service to a store or office is sized from the load calculation and Table 310.16. If the load has continuous loads, NEC 230.42(A) requires the service conductors to have an ampacity of at least the noncontinuous load plus 125% of the continuous load.

Three-phase systems. 310.12 never applies to a three-phase service or feeder. The one 208Y/120-V case it covers in the 2023 NEC is a single-phase dwelling feeder (two ungrounded conductors and the neutral), common in apartment buildings, and that feeder gets 310.12(A) through (C) only, not the reduced-neutral provision in (D).

A calculated load above 166 A. 310.12 sets the conductor ampacity from the service rating, but NEC 230.42(A) still requires service conductors to carry the calculated load. If your Article 220 calculation comes out at, say, 185 A on a 200 A service, 2/0 copper (175 A) fails that check: use 3/0 copper or 250 kcmil aluminum. Most houses calculate well under 166 A, which is why the shortcut usually works.

Derating with the 83% rule

When a correction or adjustment factor applies, Table 310.12(A) is off the table, but the 83% target is not. Derate the conductor the normal way, starting from its own temperature column (the 2023 text of NEC 310.12(D) says so expressly for the neutral, and the 2026 NEC moves that sentence up to cover every 310.12 conductor), then cap the result at the 75°C termination value. That helps 90°C conductors like XHHW-2.

Worked example

200 A dwelling service through a hot space

  1. 1

    The question

    A 200 A one-family dwelling service uses three 4/0 aluminum XHHW-2 conductors in a raceway that passes through an area with a 40°C (104°F) ambient. Terminals are 75°C. Is 4/0 Al still adequate?

  2. 2

    Target

    310.12: 0.83 × 200 = 166 A.

  3. 3

    Correct at 90°C

    4/0 Al at 90°C = 205 A. Ambient correction for a 90°C conductor at 36 to 40°C = 0.91. 205 × 0.91 = 186.55 A.

  4. 4

    Apply the termination limit

    At 75°C terminals, 4/0 Al is limited to 180 A. Usable ampacity = the lower of 186.55 and 180 = 180 A.

  5. ✓ Answer: Yes. 180 A ≥ 166 A, so 4/0 aluminum XHHW-2 still works.

The ampacity correction and adjustment factors guide covers ambient and bundling factors in detail.

Neutral size for a 200 amp service

The neutral (grounded conductor) can be smaller than the ungrounded conductors. NEC 310.12 allows it when the neutral load calculation of NEC 220.61 and the service rules of NEC 230.42 are met. That is why 4/0-4/0-2/0 aluminum SER is common on 200 A services.

There is a floor, though. NEC 250.24(D)(1) requires the neutral brought to the service to be no smaller than the size in NEC Table 250.102(C)(1), based on the ungrounded conductor size:

Ungrounded conductorsMinimum neutral at the service
2/0 Cu4 AWG Cu or 2 AWG Al
4/0 Al4 AWG Cu or 2 AWG Al
3/0 Cu4 AWG Cu or 2 AWG Al
250 kcmil Al4 AWG Cu or 2 AWG Al

So a 2/0 Al neutral with 4/0 Al lines meets the floor; whether it meets the calculated neutral load is a separate check. The distinction between neutral and ground is explained in grounded vs grounding conductor.

Ground wire size for a 200 amp service

Two different grounding conductors, two different tables.

Grounding electrode conductor (GEC), NEC Table 250.66: sized from the largest ungrounded service conductor. 2/0 or 3/0 Cu, or 4/0 or 250 kcmil Al, needs a 4 AWG copper or 2 AWG aluminum GEC. Limits apply by electrode: a GEC that goes only to rod, pipe or plate electrodes need not be larger than 6 AWG copper (NEC 250.66(A)), and only to a concrete-encased electrode need not be larger than 4 AWG copper (NEC 250.66(B)). Rod spacing and the 25-ohm rule are in ground rod requirements.

Equipment grounding conductor (EGC), NEC Table 250.122: only for a feeder, sized from the overcurrent device. 200 A OCPD: 6 AWG copper or 4 AWG aluminum. Services do not normally have an EGC; the neutral does that job back to the main bonding jumper.

ConductorTable200 A answer
GEC (2/0 Cu or 4/0 Al service)250.664 AWG Cu / 2 AWG Al
GEC to rods only250.66(A)6 AWG Cu max
EGC for a 200 A feeder250.1226 AWG Cu / 4 AWG Al

Exam-style practice

Exam-style question

A one-family dwelling has a 200 A, 120/240-volt single-phase service. The service conductors supply the entire load and no correction or adjustment factors apply. What is the minimum size aluminum service-entrance conductor?

Pick an answer to see the explanation.

Exam-style question

A 200 A breaker in a dwelling's main panel feeds a 200 A subpanel in a detached shop. The calculated load is 195 A and terminals are rated 75°C. What is the minimum size copper feeder conductor?

Pick an answer to see the explanation.

Exam-style question

What is the minimum size copper grounding electrode conductor for a service with 4/0 AWG aluminum service-entrance conductors, connected to a metal underground water pipe electrode?

Pick an answer to see the explanation.

Mistakes that cost points

Applying 83% to a subpanel. The rule needs the entire dwelling load.

Mixing up 2/0 Cu and 2/0 Al. 2/0 Al is only 135 A at 75°C. The 200 A dwelling sizes are 2/0 copper and 4/0 aluminum.

Sizing the GEC from the breaker. Table 250.66 uses the service conductor size; Table 250.122 uses the breaker.

Reading the 90°C column as the final answer. 90°C ampacity is only the starting point for derating.

Forgetting the utility. The utility may dictate the meter socket, the lateral or drop, and its own minimum conductor sizes. Local amendments can also change 310.12. Always check both.

How to find this fast in the code book

310.12 sits right before the ampacity tables in Article 310, so one tab covers both. Tab NEC Table 250.66 and NEC Table 250.122 separately: they look alike and that is exactly why people grab the wrong one. The code text is free to read on the NFPA free access page.

→Article 230 from end to endService-Entrance Conductors: NEC Article 230 Explained

For smaller and larger services, see the 100 amp service wire size guide and aluminum vs copper wire. Then put the 83% rule under the clock with the free journeyman electrician practice test.