NEC voltage drop limits for ordinary branch circuits and feeders are not requirements. The familiar numbers, 3% for a branch circuit or feeder and 5% total from the service to the farthest outlet, come from informational notes in sections 210.19 and 215.2, and the NEC itself says informational notes are explanatory material, not enforceable rules.

That surprises a lot of electricians, and exam writers know it. This guide shows where the 3% and 5% come from, why the NEC treats them as advice, the handful of places where voltage drop is mandatory, and how to budget the 5% between a feeder and a branch circuit with real numbers.

Is voltage drop required by the NEC?

For general wiring, no. The National Electrical Code's purpose, stated in NEC 90.1, is the practical safeguarding of people and property from electrical hazards. Excessive voltage drop is mostly an efficiency and performance problem: dim lights, hot motors, wasted energy. It is not, by itself, a fire or shock hazard, so the NEC addresses it with recommendations.

The recommendations sit in informational notes. NEC 90.5(C) explains that informational notes, like other explanatory material in the Code, are for information only and are not enforceable as requirements.

So a branch circuit with a 4% drop does not violate the NEC. It may still be bad practice, it may violate a project specification, and it may violate a local amendment or energy code. But the NEC alone does not prohibit it.

Where the 3% and 5% numbers come from

Two informational notes carry the numbers:

LocationWhat it recommends
Informational note in NEC 210.19 (branch circuits)Branch-circuit conductors sized to prevent a voltage drop over 3% at the farthest outlet, and a combined feeder + branch circuit drop not over 5%
Informational note in NEC 215.2 (feeders)Feeder conductors sized to prevent a voltage drop over 3% at the farthest outlet, and a combined feeder + branch circuit drop not over 5%

The note numbers inside 210.19 and 215.2 have shifted between editions as those sections were reorganized, so search the section for the words "voltage drop" rather than memorizing a note number. If your exam asks for a location, "an informational note to 210.19" (branch circuits) or "to 215.2" (feeders) is the answer that survives every edition.

The notes say these limits provide "reasonable efficiency of operation." That phrase is the tell: it is an engineering recommendation, not a safety rule.

ServicepanelSubpanelOutletFeederBranch circuit≤ 3% (e.g. 2%)≤ 3%Total to farthest outlet ≤ 5%
The 5% recommended budget from the service to the farthest outlet. A common split is 2% feeder + 3% branch circuit.

How many volts is 3% and 5%?

Percent voltage drop is always calculated against the nominal system voltage at the source. Memorize the common ones:

System voltage3%5%
120 V3.6 V6.0 V
208 V6.24 V10.4 V
240 V7.2 V12.0 V
277 V8.31 V13.85 V
480 V14.4 V24.0 V

3%

recommended max, branch circuit or feeder

5%

recommended max, feeder + branch combined

3.6 V

3% of a 120 V circuit

How to budget the 5% between feeder and branch circuit

The notes give you two caps that must both be respected: each part at 3% or less, and the total at 5% or less. That leaves room for several splits:

  • 2% feeder + 3% branch. The most common design split. It lets every branch circuit use its full 3%.
  • 3% feeder + 2% branch. Works when the feeder is long and the branch circuits are short.
  • 1% feeder + 3% branch. Typical when a panel sits right next to the service.

What the notes do not support is something like 1% feeder + 4% branch, even though the total is still 5%: the branch circuit exceeds its own 3%.

Worked example

Checking a feeder and branch circuit against 3% and 5%

  1. 1

    The question

    A 240-volt single-phase feeder to a detached shop drops 5.0 V. A 120-volt branch circuit in the shop drops 3.1 V to its farthest outlet. Do they meet the informational note recommendations?

  2. 2

    Feeder percent

    5.0 ÷ 240 × 100 = 2.08%. At or under 3%.

  3. 3

    Branch circuit percent

    3.1 ÷ 120 × 100 = 2.58%. At or under 3%.

  4. 4

    Combined

    2.08% + 2.58% = 4.66%. At or under 5%.

  5. ✓ Answer: Yes. Each part is under 3% and the total is under 5%. Adding percentages is the practical way to combine drops when the feeder and branch circuit run at different voltages.
Worked example

How much is left for the branch circuits?

  1. 1

    The question

    A 208Y/120-volt feeder to a panel is calculated at a 2.6% voltage drop. What is the maximum drop, in volts, that a 120-volt branch circuit from that panel should have to stay within 5% total?

  2. 2

    Remaining percent

    5% − 2.6% = 2.4%. That is below the 3% branch cap, so 2.4% controls.

  3. 3

    Convert to volts

    120 × 0.024 = 2.88 V

  4. ✓ Answer: 2.88 V. A long feeder eats into every branch circuit's budget, which is why designers often keep feeders at 2% or less.

The formula that turns these percentages into wire sizes is covered step by step in the voltage drop formula guide, including the K-factor and Chapter 9, Table 8 methods.

Where voltage drop IS mandatory in the NEC

A few articles turn voltage drop into an enforceable requirement because performance there is a safety issue.

Sensitive electronic equipment, 647.4(D)

Article 647 covers separately derived 120-volt systems with 60 volts to ground, used for sensitive electronic equipment such as audio and video production. NEC 647.4(D) sets mandatory limits: for fixed equipment, the branch circuit may not drop more than 1.5% and the combined feeder and branch circuit not more than 2.5%. Branch circuits supplying receptacles for cord-and-plug-connected equipment are held even tighter: 1% on the branch circuit, calculated with the receptacle load taken as 50% of the branch-circuit rating, plus a combined feeder and branch-circuit limit given in the same section.

Fire pumps, 695.7

A fire pump must start and run when the building is burning, so NEC 695.7 makes voltage drop a requirement:

  • Starting: the voltage at the fire pump controller line terminals must not drop more than 15% below the controller's rated voltage while the motor starts.
  • Running: the voltage at the controller load terminals must not drop more than 5% below the motor's rated voltage while the motor runs at 115% of its full-load current rating.

Local amendments and energy codes

Many jurisdictions adopt the NEC with amendments, and many adopt energy codes that include their own voltage drop limits for feeders and branch circuits. Those become enforceable where adopted. On a commercial project, the engineer's specifications often set limits too. Always check the local rules and the project documents.

Why voltage drop still matters if it isn't required

Even when it is not enforceable, excessive voltage drop causes real problems:

  • Motors draw more current at lower voltage to produce the same horsepower, run hotter and can trip overloads. Motor starting causes a momentary dip on top of the running drop.
  • Lighting dims and some drivers misbehave at low voltage.
  • Electronics and controls reset or fault.
  • Energy is wasted as heat in the conductors, every hour the load runs.

Upsizing for voltage drop: the grounding rule you must not miss

When you increase conductor size to control voltage drop, NEC 250.122(B) kicks in. If the ungrounded conductors are increased in size from the minimum size that has sufficient ampacity for the load, wire-type equipment grounding conductors must be increased proportionally according to circular mil area.

Worked example

Proportional EGC upsizing

  1. 1

    The question

    A 60-ampere circuit would normally use 6 AWG copper (26,240 cmil) with a 10 AWG copper EGC from Table 250.122. For voltage drop, the ungrounded conductors are increased to 3 AWG (52,620 cmil). What is the minimum EGC size?

  2. 2

    Ratio

    52,620 ÷ 26,240 = 2.005

  3. 3

    Apply to the EGC

    10 AWG = 10,380 cmil. 10,380 × 2.005 = 20,815 cmil (carrying the unrounded ratio)

  4. 4

    Pick from Chapter 9, Table 8

    8 AWG = 16,510 cmil, too small. 6 AWG = 26,240 cmil, large enough.

  5. ✓ Answer: 6 AWG copper EGC. Keep a few decimals in the ratio: AWG sizes step up geometrically, so rounding early can push a borderline answer into the wrong size.

The full method, with tables, is in equipment grounding conductor sizing.

Voltage drop vs ampacity: two different checks

Students often blur these together. They answer different questions:

Ampacity (mandatory)

  • Prevents conductor overheating
  • Table 310.16 plus correction and adjustment factors
  • Limited by 110.14(C) terminations
  • Enforceable everywhere the NEC is adopted

Voltage drop (usually recommended)

  • Keeps voltage at the load usable
  • Chapter 9, Table 8 or K-factor formula
  • Depends on length, current and conductor area
  • Mandatory only in 647, 695 or where locally adopted

Size for ampacity first using the wire ampacity chart (Table 310.16), then check voltage drop and upsize if needed. Never go the other way and pick a smaller conductor because the run is short: ampacity still controls.

Practice: NEC voltage drop questions

Exam-style question

According to the NEC, what is the maximum voltage drop permitted on a general-purpose 120-volt branch circuit in a dwelling?

Pick an answer to see the explanation.

Exam-style question

A feeder has a 2.5% voltage drop. To stay within the recommended total, what is the maximum voltage drop for a 240-volt branch circuit supplied by it?

Pick an answer to see the explanation.

Exam-style question

Which of the following installations has a mandatory voltage drop limit in the NEC?

Pick an answer to see the explanation.

How to find it fast in the code book

Highlight the words "voltage drop" in the informational notes at 210.19 and 215.2, and tab 647.4(D) and 695.7 if your exam covers commercial or industrial work. The calculation tables are in Chapter 9, Table 8 (DC resistance) and Table 9 (AC impedance). Exam rules on tabs and highlighting vary, so read your candidate bulletin and see how to tab your NEC code book.

→Do the mathVoltage Drop Formula and Calculation, Step by Step

Next steps

The recommendations only become useful when you can turn them into a wire size. Work through the voltage drop formula with worked examples, then see how long runs affect real circuits in 10 gauge wire amps and what size wire for a 60 amp subpanel. For motors, where voltage drop matters most, see motor calculations under Article 430.

When you are ready to check yourself under exam conditions, take a free journeyman practice test or go to the timed practice tests.