Motor calculations under NEC Article 430 always follow the same order: look up the full-load current (FLC) in the NEC tables, size the conductors at 125% of that FLC, size the overloads from the nameplate current at 115% or 125%, and size the breaker or fuses from a percentage of the table FLC in Table 430.52(C)(1). Feeders that serve several motors add 125% of the largest motor to 100% of the others.
The motor calculations NEC-based exams ask for are some of the most predictable questions on the journeyman test, but each step uses a different current and a different percentage. This guide puts every step in order, shows exactly which number each one uses, and works three full examples: a three-phase motor, a single-phase motor and a motor feeder.
Step zero: which current do you use? (430.6)
Every motor circuit has two currents in play, and using the wrong one is the number-one way to miss motor questions.
Table FLC (430.248 / 430.250)
- Conductor ampacity (430.22, 430.24)
- Short-circuit and ground-fault protection (430.52)
- Feeder protection (430.62)
- Disconnect ampere rating (430.110)
Nameplate FLA
- Overload protection only (430.32)
- Read from the motor itself
- Usually a little lower than the table
- Service factor and temperature rise also from the nameplate
If you need help reading the FLC tables (voltage columns, single-phase vs three-phase, what to do with 208 V), see horsepower to amps. The examples below use these table values:
| Motor | Table | Table FLC |
|---|---|---|
| 3 hp, 230 V, single-phase | 430.248 | 17 A |
| 5 hp, 460 V, three-phase | 430.250 | 7.6 A |
| 10 hp, 460 V, three-phase | 430.250 | 14 A |
| 15 hp, 460 V, three-phase | 430.250 | 21 A |
| 25 hp, 460 V, three-phase | 430.250 | 34 A |
The motor branch circuit, piece by piece
Conductors: 125% of table FLC (430.22)
NEC 430.22: conductors supplying a single motor used in a continuous-duty application must have an ampacity of not less than 125% of the motor's full-load current rating as determined by 430.6(A)(1).
430.22
Conductor ampacity ≥ table FLC × 1.25
Then choose the conductor from Table 310.16 in the right temperature column. For circuits of 100 A or less, 110.14(C)(1)(a) normally limits you to the 60°C column, but it allows the 75°C ampacity for motors marked with design letter B, C or D when 75°C-rated conductors are used. Our 110.14(C) termination guide covers the details.
Overloads: 115% or 125% of nameplate (430.32)
NEC 430.32(A)(1) sizes a separate overload device (the heater or electronic relay in the motor starter) from the nameplate full-load current:
| Motor nameplate says | Maximum overload setting |
|---|---|
| Service factor 1.15 or greater | 125% |
| Temperature rise 40°C or less | 125% |
| All other motors | 115% |
If the overload sized this way won't let the motor start or carry its load, NEC 430.32(C) allows the next higher size or setting, up to 140% (service factor 1.15 or more, or temperature rise 40°C or less) or 130% (all others).
Short-circuit and ground-fault protection (Table 430.52(C)(1))
The breaker or fuses ahead of a motor protect against short circuits and ground faults only. They have to be big enough to ride through starting inrush, which is why the percentages are so high. NEC 430.52(C)(1) sends you to the table:
| Motor type | Non-time-delay fuse | Dual-element (time-delay) fuse | Instantaneous-trip breaker | Inverse-time breaker |
|---|---|---|---|---|
| Single-phase motors | 300% | 175% | 800% | 250% |
| AC polyphase squirrel cage, other than Design B energy-efficient / premium efficiency | 300% | 175% | 800% | 250% |
| Design B energy-efficient and Design B premium efficiency | 300% | 175% | 1100% | 250% |
| Synchronous | 300% | 175% | 800% | 250% |
| Wound rotor | 150% | 150% | 800% | 150% |
| DC (constant voltage) | 150% | 150% | 250% | 150% |
All percentages are of the table FLC. A table footnote applies the non-time-delay fuse column to time-delay Class CC fuses too. Two rules let you go above the calculated value (in the 2020 and earlier editions they were Exceptions No. 1 and No. 2; the 2023 NEC renumbered them as list items):
- 430.52(C)(1)(a), next size up: where the calculated value doesn't match a standard rating in NEC 240.6(A), you may use the next higher standard size.
- 430.52(C)(1)(b), starting problems: if that size still won't carry the starting current, you may go up to 400% for an inverse-time breaker on a motor with FLC of 100 A or less (300% above 100 A), 225% for a time-delay fuse, 400% for a non-time-delay fuse rated 600 A or less (or a time-delay Class CC fuse), and 300% for fuses rated 601 to 6000 A.
Worked example 1: a 25 hp, 460 V three-phase motor
25 hp, 460 V, 3-phase, Design B, SF 1.15, nameplate 32 A
- 1
Table FLC
Table 430.250, 25 hp at 460 V = 34 A (the 32 A nameplate is not used here)
- 2
Conductors (430.22)
34 × 1.25 = 42.5 A. Design B motor with 75°C terminations: 8 AWG copper THWN-2 is 50 A in the 75°C column. 10 AWG (35 A) is too small. 8 AWG copper
- 3
Overload (430.32)
Nameplate 32 A, service factor 1.15 → 125%. 32 × 1.25 = 40 A
- 4
Inverse-time breaker (Table 430.52(C)(1))
34 × 2.50 = 85 A. 85 A is not a standard size; next higher standard size is 90 A (430.52(C)(1)(a))
- 5
Or time-delay fuses
34 × 1.75 = 59.5 A → next standard size 60 A
Worked example 2: a 3 hp, 230 V single-phase motor
3 hp, 230 V, 1-phase, nameplate 16 A, no service factor, 50°C rise
- 1
Table FLC
Table 430.248, 3 hp at 230 V = 17 A
- 2
Conductors
17 × 1.25 = 21.25 A. No design letter, so use the 60°C column: 12 AWG copper is 20 A (too small), 10 AWG is 30 A. 10 AWG copper
- 3
Overload
No service factor and a 50°C temperature rise → "all other motors" → 115%. 16 × 1.15 = 18.4 A
- 4
Inverse-time breaker
17 × 2.50 = 42.5 A → next standard size 45 A
A 45 A breaker on 10 AWG looks wrong if you are thinking of general branch circuits, but it is correct. NEC 240.4(G) sends motor circuit conductors to Article 430, so the small-conductor limits in NEC 240.4(D) don't apply. The overload relay protects the conductors from overload; the breaker only has to clear faults. The 240.4 guide explains the logic.
Worked example 3: a feeder for several motors
Three motors on one 460 V, three-phase feeder: 25 hp (34 A), 10 hp (14 A) and 5 hp (7.6 A). Each motor has an inverse-time breaker sized at 250% with next size up.
Motor feeder: conductors and protection
- 1
Branch breakers first
25 hp: 34 × 2.5 = 85 → 90 A. 10 hp: 14 × 2.5 = 35 → 35 A. 5 hp: 7.6 × 2.5 = 19 → 20 A
- 2
Feeder conductors (430.24)
125% of largest + 100% of others: (34 × 1.25) + 14 + 7.6 = 42.5 + 21.6 = 64.1 A. 6 AWG copper at 75°C (65 A)
- 3
Feeder protection (430.62(A))
Largest branch device + FLC of the other motors: 90 + 14 + 7.6 = 111.6 A
- 4
Round down
430.62(A) sets a maximum and has no next-size-up allowance. Next standard size below 111.6 A is 110 A
Motor disconnects and other numbers worth knowing
- Disconnect ampere rating: at least 115% of the table FLC NEC 430.110(A).
- Disconnect location: the disconnect must be in sight from the controller, and generally in sight from the motor too, unless an exception applies NEC 430.102.
- Several motors on a feeder with other loads: 430.24 adds 100% of noncontinuous non-motor loads and 125% of continuous non-motor loads to the motor total.
- Hermetic A/C compressors are not sized from Article 430 tables. They use the nameplate rated-load current and Article 440. See MCA vs MOCP.
Mistakes that cost points on motor questions
Using the nameplate current for conductors or breakers. Table FLC for those; nameplate only for overloads.
Using the table FLC for overloads. The reverse error. Overloads come from the nameplate.
Taking 125% for every overload. 125% only when the service factor is 1.15 or more or the temperature rise is 40°C or less. Otherwise 115%.
Rounding the feeder device up. Branch circuits may round up (430.52(C)(1)(a)); feeders may not (430.62(A)).
Applying 240.4(D) to motor circuits. The 10 AWG / 30 A limit doesn't apply to motor branch circuits.
Using the three-phase table for a single-phase motor (or the other way around). Check the phase before you read a number.
Exam-style questions
Exam-style question
What is the minimum branch-circuit conductor ampacity for a 10 hp, 208 V, three-phase, continuous-duty motor?
Pick an answer to see the explanation.
Exam-style question
A motor has a nameplate full-load current of 50 A, no service factor marked, and a marked temperature rise of 50°C. What is the maximum rating of a separate overload device (without the 430.32(C) increase)?
Pick an answer to see the explanation.
Exam-style question
What is the maximum standard inverse-time circuit breaker for a 15 hp, 460 V, three-phase squirrel-cage motor (not Design B energy-efficient premium), assuming normal starting?
Pick an answer to see the explanation.
How motor calculations fit into the rest of the exam
Motor rules feed directly into service and feeder sizing. The extra 25% of the largest motor in the standard dwelling load calculation comes straight from 430.24. The breaker sizes all come from the list in standard breaker sizes, and the conductor sizes from the Table 310.16 ampacity chart. If three-phase current still feels shaky, review single-phase vs three-phase power before you drill these.
The full text of Article 430 is in NFPA 70, available through the NFPA 70 page. Then practice the whole sequence under time pressure with a free journeyman practice test.