Single phase vs three phase comes down to how many alternating voltages the system delivers. Single-phase power has one voltage waveform and is what most US homes receive, as 120/240 volts. Three-phase power has three waveforms spaced 120 degrees apart, which delivers steady power, runs motors more efficiently and carries more power per conductor, so it is the standard for commercial and industrial buildings.
This guide explains how each system works, which voltages you will find in the field, where the factor 1.732 comes from, and how to calculate current, power and neutral current for each, with worked examples built the way the journeyman exam asks.
Single-phase vs three-phase at a glance
| Single-phase | Three-phase | |
|---|---|---|
| Voltage waveforms | One | Three, 120° apart |
| Typical US systems | 120/240 V, 3-wire | 208Y/120 V, 480Y/277 V, 240 V delta |
| Conductors | 2 or 3 (plus EGC) | 3 or 4 (plus EGC) |
| Power delivery | Pulses to zero twice per cycle | Nearly constant |
| Motors | Need start windings or capacitors | Self-starting rotating field |
| Current formula | I = VA ÷ E | I = VA ÷ (E × 1.732) |
| Typical use | Homes, small shops, light loads | Commercial, industrial, large HVAC and motors |
How single-phase power works
A single-phase system has one sinusoidal voltage. In US homes, the utility transformer's secondary winding is center-tapped: the center tap becomes the grounded neutral, and the two ends become the ungrounded conductors (often called L1 and L2).
That gives you:
- 240 V between L1 and L2, for ranges, dryers, water heaters and air conditioners;
- 120 V from either leg to the neutral, for receptacles and lighting.
This is still single-phase. L1 and L2 are the two ends of one winding, not two separate phases. Calling it "two-phase" is a common mistake; true two-phase systems are a historical rarity.
Because the two legs are opposite each other relative to the neutral, balanced 120 V loads on L1 and L2 cancel in the neutral. That is why the neutral on a 120/240 V system carries only the difference between the two legs' 120-volt loads, and why a multiwire branch circuit can share one neutral.
How three-phase power works
A three-phase system has three voltages of the same magnitude and frequency, each shifted 120 degrees from the next. When one phase is passing through zero, the other two are delivering power, so the total power delivered to a balanced load never drops to zero.
Three-phase systems come in two basic transformer connections:
- Wye (Y): the three windings share a common point, which becomes the neutral. You get two voltages: line-to-neutral and line-to-line (for example, 120 V and 208 V).
- Delta (Δ): the windings are connected end to end in a triangle. Line-to-line voltage equals the winding voltage, and there is no neutral unless one winding is center-tapped.
The details, including line and phase currents, are in delta vs wye. A center-tapped delta creates one phase with about 208 V to ground, the high-leg delta, which has its own marking and placement rules.
Common US system voltages
NEC 220.5(A) lists the nominal voltages used for calculations: 120, 120/240, 208Y/120, 240, 347, 480Y/277, 480, 600Y/347 and 600 volts.
| System | Phase | Line-to-line | Line-to-neutral | Where you find it |
|---|---|---|---|---|
| 120/240 V, 3-wire | Single | 240 V | 120 V | Homes, small commercial |
| 208Y/120 V, 4-wire | Three | 208 V | 120 V | Offices, retail, apartments |
| 480Y/277 V, 4-wire | Three | 480 V | 277 V | Large commercial, industrial |
| 240 V delta, 3-wire | Three | 240 V | — | Older industrial, motor loads |
| 240/120 V high-leg delta, 4-wire | Three | 240 V | 120 V (two phases), about 208 V (high leg) | Older shops with mixed loads |
Why 120/240 and 208, not 110/220? The NEC uses nominal values for calculations; see 110 vs 120 volts. And for how voltages are grouped into low, medium and high, see what is considered high voltage.
Where the 1.732 comes from
In a wye system, the line-to-line voltage is the difference between two phase voltages that are 120 degrees apart. Draw the two phase voltages as arrows (phasors) and the line voltage is the third side of the triangle they form. Geometry gives:
Wye line-to-line voltage
E_line = 2 × E_phase × cos 30° = √3 × E_phase ≈ 1.732 × E_phase
- 120 V × 1.732 = 207.8 V, called 208 V
- 277 V × 1.732 = 479.8 V, called 480 V
- 347 V × 1.732 = 601.0 V, called 600 V
The same √3 shows up in total three-phase power. Each phase delivers E_phase × I × PF, and three phases deliver three times that. Rewritten in line-to-line voltage (E_phase = E_line ÷ √3): P = 3 × (E_line ÷ √3) × I × PF = √3 × E_line × I × PF.
Power and current formulas
| Single-phase | Three-phase | |
|---|---|---|
| Apparent power (VA) | E × I | E × I × 1.732 |
| True power (W) | E × I × PF | E × I × 1.732 × PF |
| Current from VA | VA ÷ E | VA ÷ (E × 1.732) |
| Current from W | W ÷ (E × PF) | W ÷ (E × 1.732 × PF) |
In three-phase formulas, E is the line-to-line voltage and I is the line current. All of these, with voltage drop and transformer formulas, are collected in the electrical formulas cheat sheet.
Same 20 kW load: single-phase vs three-phase
- 1
The question
A 20 kW resistive heating load (PF = 1) can be supplied at 240 V single-phase, 208 V three-phase or 480 V three-phase. What is the current in each case?
- 2
240 V single-phase
I = 20,000 ÷ 240 = 83.3 A.
- 3
208 V three-phase
I = 20,000 ÷ (208 × 1.732) = 20,000 ÷ 360.3 = 55.5 A.
- 4
480 V three-phase
I = 20,000 ÷ (480 × 1.732) = 20,000 ÷ 831.4 = 24.1 A.
Three-phase power from a measured current
- 1
The question
A 480 V three-phase motor load draws 50 A per phase at a power factor of 0.9. What are the apparent power and true power?
- 2
Apparent power
VA = 480 × 50 × 1.732 = 41,568 VA, about 41.6 kVA.
- 3
True power
W = 41,568 × 0.9 = 37,411 W, about 37.4 kW.
For code questions on motors, do not calculate full-load current from horsepower with these formulas; the NEC requires the values in NEC Table 430.248 and NEC Table 430.250 per NEC 430.6(A)(1). See horsepower to amps.
Single-phase loads on a three-phase system
Most buildings with three-phase service also feed plenty of single-phase loads:
- Line-to-neutral loads (120 V on 208Y/120, 277 V on 480Y/277): lighting and receptacles, spread across the three phases.
- Line-to-line single-phase loads (208 V or 480 V, using two of the three phases): water heaters, small HVAC units, ranges in apartments.
A single-phase load connected line-to-line on a three-phase system is still calculated with the single-phase formula, using the line-to-line voltage. A 5,000 W, 208 V water heater draws 5,000 ÷ 208 = 24.0 A, with no 1.732.
Watch for equipment rated 240 V installed on a 208 V system. A resistive load rated 240 V produces only about 75% of its rated wattage at 208 V, because power varies with the square of the voltage; the Ohm's law guide works that example in full.
Neutral current: balanced and unbalanced
In a balanced three-phase wye system with linear loads, the three phase currents are equal and 120 degrees apart, so they add to zero in the neutral. When the line-to-neutral loads are unbalanced, the neutral carries the difference. For a 4-wire wye with resistive loads:
Neutral current, 4-wire wye (resistive loads)
I_N = √(A² + B² + C² − AB − BC − CA)
Unbalanced neutral current
- 1
The question
A 208Y/120 V panel has line-to-neutral resistive loads of 50 A on phase A, 40 A on phase B and 30 A on phase C. What is the neutral current?
- 2
Squares
50² + 40² + 30² = 2,500 + 1,600 + 900 = 5,000.
- 3
Products
(50 × 40) + (40 × 30) + (30 × 50) = 2,000 + 1,200 + 1,500 = 4,700.
- 4
Neutral
I_N = √(5,000 − 4,700) = √300 = 17.3 A.
Two code rules follow from this. When a 3-wire circuit uses two phase conductors and the neutral of a 4-wire, three-phase wye system, the neutral carries about the same current as the phase conductors and is counted as a current-carrying conductor (NEC 310.15(E)(2)). And when the major portion of the load on a 4-wire wye circuit is nonlinear (electronic power supplies, LED drivers), harmonic currents add in the neutral, so it is also counted as current-carrying (NEC 310.15(E)(3)). Both rules affect ampacity adjustment factors.
Why three-phase is used for larger loads
- Less conductor per kilowatt. A three-phase, 3-wire circuit carries 1.732 times the power of a single-phase, 2-wire circuit with conductors of the same size and the same line voltage, while using only 1.5 times as many conductors. That is about 15% more power per conductor.
- Self-starting motors. Three-phase currents create a rotating magnetic field, so three-phase induction motors start and run without start windings or capacitors.
- Smoother power. Constant power delivery means less vibration in large motors and steadier operation.
- Flexible voltages. A 208Y/120 or 480Y/277 system serves both three-phase equipment and single-phase lighting and receptacles from one service.
Single-phase remains the standard for homes because residential loads are smaller, and distribution lines in residential areas are often single-phase. Where three-phase is not available, phase converters or variable frequency drives can run three-phase motors from a single-phase supply.
Practice questions
Exam-style question
What is the current drawn by a balanced 30 kVA three-phase load at 208 volts?
Pick an answer to see the explanation.
Exam-style question
A 480Y/277-volt system has a line-to-neutral voltage of 277 V. What is the line-to-line voltage?
Pick an answer to see the explanation.
Exam-style question
A 4-wire 208Y/120 V panel has line-to-neutral resistive loads of 30 A, 30 A and 30 A. What is the neutral current?
Pick an answer to see the explanation.
Exam-style question
A 6,000-watt, 208-volt single-phase water heater is installed on a 208Y/120 V three-phase system. What current does it draw?
Pick an answer to see the explanation.
Where to go next
This topic connects directly to delta vs wye, the high-leg delta and power factor and kVA. For the foundations, see basic electrical theory; for the code side, transformer calculations and motor calculations both rely on the three-phase formulas above. Then test yourself under the clock with a free journeyman electrician practice test.