110V vs 120V describes the same thing: the ordinary US household circuit. The official nominal voltage is 120 volts, and "110", "115" and "117" are older names or equipment ratings that stuck around. The same goes for 220 vs 240: the voltage between the two hot legs of a residential service is nominally 240 volts. The real voltage at any outlet floats a few volts above or below nominal, normally within about 114 to 126 volts.

This guide explains where the different numbers come from, what "nominal" means in the NEC, how much the actual voltage is allowed to vary, why motor and appliance nameplates use different numbers, and exactly which voltage to plug into exam calculations.

110V vs 120V: same circuit, different names

US utility voltages crept upward during the early decades of electrification, and the names people used followed at different speeds. That is why you hear 110, 115, 117 and 120 for the same receptacle, and 220, 230 and 240 for the same range circuit. Today the standard is settled:

What people sayStandard nominal system voltageTypical equipment rating
110, 115, 117 V120 V115 V (motors), 120 V or 125 V (devices)
220, 230 V240 V230 V (motors), 240 V or 250 V (devices)
440, 460 V480 V460 V (motors)
550, 575 V600 V575 V (motors)

Receptacles are rated a little above nominal: a standard NEMA 5-15 or 5-20 receptacle is rated 125 volts, and a 6-20 is rated 250 volts. That is why GFCI rules talk about "125-volt through 250-volt receptacles". A device rated 125 V is meant for a 120-volt circuit.

What "nominal voltage" means in the NEC

The NEC defines voltage, nominal as a value assigned to a circuit or system for the purpose of conveniently designating its voltage class, such as 120/240 volts, 480Y/277 volts or 600 volts. The actual voltage at which a circuit operates can vary from the nominal within a range that permits satisfactory operation of equipment.

In other words, "120 volts" is a label for the system, not a promise about what your meter will read. A healthy 120-volt circuit can measure 118 one minute and 123 the next.

How much can the real voltage vary? ANSI C84.1

ANSI C84.1 is the national standard utilities and manufacturers use for system voltages. It sets two ranges around each nominal voltage:

  • Range A: the normal operating range. For service voltage (at the meter), it is ±5% of nominal: 114 to 126 V on a 120-volt base. Equipment must perform fully throughout Range A.
  • Range B: a wider range (110 to 127 V service voltage on a 120-volt base) that is acceptable occasionally and for limited periods. Sustained operation in Range B should be corrected.

The minimum utilization voltage, at the equipment, is set lower than the minimum service voltage. That gap is the allowance for voltage drop in the building wiring. Pacific Gas and Electric publishes a clear one-page summary of these ranges in its ANSI C84.1 voltage tolerance explainer.

105110115120125130Range B: 110 to 127 VRange A: 114 to 126 Vnominal 120 VService voltage, 120-V base
ANSI C84.1 service voltage ranges on a 120-volt base.

120 V

US nominal (not 110)

114–126 V

ANSI Range A service voltage

±5%

Range A around nominal

Why nameplates say 115 V, 230 V and 460 V

Motors and many appliances are rated at utilization voltage: what is left at the equipment after voltage drop in the feeders and branch circuits. That is why the standard pairs are:

System nominalMotor nameplate
120 V115 V
208 V200 V
240 V230 V
480 V460 V
600 V575 V

The NEC motor tables follow the same convention. NEC 430.248 (single-phase) lists columns for 115, 200, 208 and 230 volts, and NEC 430.250 (3-phase) lists 115, 200, 208, 230, 460, 575 and 2300 volts. Their notes say the listed currents may be used for system voltage ranges such as 110 to 120 volts and 220 to 240 volts (and, for 3-phase, 440 to 480 and 550 to 600 volts). So on a 240-volt system you read the 230-volt column. The full method is in horsepower to amps.

Which voltage to use in exam calculations

The rule is simple, and it is where 110 vs 120 actually costs points:

  1. Branch-circuit and feeder loads: use the nominal voltages of NEC 220.5(A): 120, 240, 208, 277, 480 and so on. Never 110 or 220 unless the question specifies them.
  2. Motors: use the full-load current from Tables 430.248 or 430.250 in the column for the motor's rated voltage (230 V column for a 240-volt system), not a calculated current.
  3. Rounding: NEC 220.5(B) permits calculations to be rounded to the nearest whole ampere, dropping decimal fractions smaller than 0.5.
Worked example

The 110 vs 120 trap

  1. 1

    The question

    What is the current drawn by a 1500-watt space heater on a 120-volt circuit?

  2. 2

    Use nominal voltage

    I = P ÷ E = 1500 ÷ 120 = 12.5 A.

  3. 3

    What happens if you use 110

    1500 ÷ 110 = 13.6 A, which appears as a distractor on many exams.

  4. ✓ Answer: 12.5 A. Use 120 V unless the question gives another voltage.
Worked example

Motor current from the table

  1. 1

    The question

    What is the full-load current of a 2 hp, single-phase motor on a 240-volt system?

  2. 2

    Pick the column

    A 240-volt system uses the 230-volt column of Table 430.248.

  3. 3

    Read the table

    2 hp at 230 V = 12 A. (At 115 V the same motor is 24 A.)

  4. ✓ Answer: 12 A, from the table, not from a formula and not from the nameplate.

220 vs 240, and why 208 is different

On a residential 120/240-volt single-phase service, "220" and "240" are the same thing: 240 volts nominal between the two hot legs. A dryer, range or water heater rated 240 V runs at its rating.

A 208Y/120-volt system, used in apartments and commercial buildings, is different: two hot legs give 208 volts, not 240, because the phases are 120 degrees apart (120 × 1.732 = 208). The delta vs wye guide explains why.

A resistive load rated for 240 V does not fail on 208 V, but it puts out less heat, because power varies with the square of the voltage:

Resistive load at a different voltage

P new = P rated × (E new ÷ E rated)²

Worked example

Water heater element on 208 V

  1. 1

    The question

    A 4500-watt, 240-volt water heater element is connected to 208 volts. What is its output?

  2. 2

    Ratio

    (208 ÷ 240)² = 0.751.

  3. 3

    Output

    4500 × 0.751 = 3380 W, about 75% of the rating.

  4. ✓ Answer: About 3380 W. That is why many commercial appliances are rated "208–240 V" or come in a separate 208-volt version.

Can you plug a 110V appliance into a 120V outlet?

Yes. A product labeled 110 V, 115 V or 120 V is built for the standard US receptacle, and the label difference is the same naming history described above. Devices are designed to work across the whole normal range, so 110-volt and 120-volt products are interchangeable on a US outlet.

The same is true for 220 V and 240 V equipment on a residential 120/240-volt service. What you cannot mix is a 120-volt device on a 240-volt receptacle, or the reverse; NEMA receptacle configurations (5-15 and 5-20 for 125 V, 6-15 and 6-20 for 250 V) are shaped differently precisely to prevent that.

What about 220 V and 230 V outside the US?

Much of the world uses 230 V at 50 Hz for ordinary outlets, which is where "220 V" is still common in conversation. That is a different system from US 240 V: it is one hot conductor and a neutral at 230 V, while a US 240-volt circuit is two 120-volt hot legs with no neutral needed for the 240-volt load. Phone and laptop chargers marked 100–240 V, 50/60 Hz work on either system; a plain US hair dryer or a 120-volt motor does not.

The NEC nominal voltages, and where you meet them

The 220.5(A) list is not random. Each value is a real US distribution system:

220.5(A) voltageSystemTypical use
120, 120/240, 240Single-phase, 3-wireHouses, small shops
208Y/1203-phase, 4-wire wyeApartments, offices, retail
480Y/277, 4803-phase wye or deltaCommercial lighting at 277 V, motors and HVAC at 480 V
600Y/347, 347, 6003-phase wye or deltaMostly Canada and some industrial sites

If a question gives you a "240-volt, 3-phase" load, that is usually a 240-volt delta system, and the high-leg delta guide explains the odd 208 V you will measure to ground on one leg of it.

Low voltage at the outlet: when to worry

Readings of 116 to 124 volts at a receptacle are normal. Readings below about 114 volts at the service, or a large drop between the panel and the outlet under load, point to a problem: utility regulation, an undersized or long circuit, or a loose connection.

The NEC treats voltage drop mostly through informational notes, with a few mandatory exceptions; see NEC voltage drop: where the 3% and 5% come from and the voltage drop formula to size conductors so the outlet stays in range.

Practice: nominal voltage exam questions

Exam-style question

Unless other voltages are specified, which voltage is used to calculate the load of a 120-volt branch circuit under NEC 220.5(A)?

Pick an answer to see the explanation.

Exam-style question

A motor nameplate reads 460 volts. What is the nominal system voltage it is designed for?

Pick an answer to see the explanation.

Exam-style question

Under ANSI C84.1 Range A, what is the normal service voltage range on a 120-volt nominal system?

Pick an answer to see the explanation.

The mistakes that cost points

Using 110 or 220 in calculations. The NEC uses 120 and 240.

Calculating motor current with I = P ÷ E. Exam answers come from Tables 430.248 and 430.250.

Treating 208 as 240. Two legs of a 208Y/120 system give 208 V; a 240-volt resistive load loses about 25% of its output there.

Reading the 240-volt column for a motor. The table column is 230 V; it applies to 220–240 V systems.

Where to go next

Nominal voltage is part of the foundation in basic electrical theory. For the voltage classes above 120 and 240 volts, read what is considered high voltage, then put the 120-volt rule to work on the free journeyman practice test.

→Reading the motor tablesHorsepower to Amps: Using NEC Tables 430.248 and 430.250