The electrical formulas every journeyman needs fit on one page: Ohm's law (E = I × R), the power formula (P = E × I), single- and three-phase current (I = VA ÷ E and I = VA ÷ (E × 1.732)), voltage drop (VD = 2KIL ÷ CM, or 1.732KIL ÷ CM for three-phase), transformer ratios, and the motor and AC relationships built on them. This cheat sheet lists each one with its units, when to use it and a worked example.

Use it as a study sheet, then as a self-test: cover the right-hand column and try to write each formula from memory. On exam day, you should know the core formulas cold, because many testing providers do not hand you a formula sheet. Check your candidate bulletin for your exam's rules.

Ohm's law and power formulas

FindFormulaNotes
Voltage (E)E = I × RVolts = amps × ohms
Current (I)I = E ÷ RAlso I = P ÷ E
Resistance (R)R = E ÷ IAlso R = E² ÷ P
Power (P)P = E × IWatts, for DC or resistive AC
Power from currentP = I² × RHeat in a conductor
Power from voltageP = E² ÷ RResistive load at a new voltage
EnergykWh = kW × hours1.5 kW for 4 h = 6 kWh

The full set of 12 combinations, with the classic exam traps, is in Ohm's law and the power formula wheel.

Single-phase formulas

FindFormula
Apparent powerVA = E × I
True powerW = E × I × PF
Current from VAI = VA ÷ E
Current from wattsI = W ÷ (E × PF)
kVAkVA = E × I ÷ 1,000

For a resistive load (heaters, incandescent lamps), PF = 1 and watts equal volt-amperes.

Worked example

Single-phase current with power factor

  1. 1

    The question

    A 5 kW single-phase load operates at 240 V with a power factor of 0.85. What current does it draw?

  2. 2

    Apply the formula

    I = W ÷ (E × PF) = 5,000 ÷ (240 × 0.85) = 5,000 ÷ 204 = 24.5 A.

  3. ✓ Answer: About 24.5 amperes. At unity power factor it would draw only 5,000 ÷ 240 = 20.8 A.

Three-phase formulas

In three-phase systems, E is the line-to-line voltage unless a question says otherwise, and the constant 1.732 (√3) appears in every power and current formula.

FindFormula
Apparent powerVA = E × I × 1.732
True powerW = E × I × 1.732 × PF
Current from VAI = VA ÷ (E × 1.732)
Current from wattsI = W ÷ (E × 1.732 × PF)
kVAkVA = E × I × 1.732 ÷ 1,000
Wye line voltageE_line = E_phase × 1.732
Delta line currentI_line = I_phase × 1.732

Common products worth memorizing: 208 × 1.732 = 360, 240 × 1.732 = 416, 480 × 1.732 = 831. Dividing by those numbers saves time on every three-phase question.

Find current (I)Single-phaseThree-phaseGiven VA: I = VA ÷ EGiven VA: I = VA ÷ (E × 1.732)Given W: I = W ÷ (E × PF)Given W: I = W ÷ (E × 1.732 × PF)
Pick the current formula in two questions: single- or three-phase, and are you given VA or watts?
Worked example

Transformer full-load current, two voltages

  1. 1

    The question

    What is the full-load current of a 45 kVA three-phase transformer on its 480 V primary and its 208 V secondary?

  2. 2

    Primary

    I = 45,000 ÷ (480 × 1.732) = 45,000 ÷ 831.36 = 54.1 A.

  3. 3

    Secondary

    I = 45,000 ÷ (208 × 1.732) = 45,000 ÷ 360.26 = 124.9 A.

  4. ✓ Answer: About 54 A on the 480 V side and 125 A on the 208 V side. Lower voltage, higher current, same kVA.

Where the 1.732 comes from, and how single- and three-phase systems compare, is explained in single-phase vs three-phase power. Line and phase relationships in delta and wye connections are covered in delta vs wye.

Voltage drop formulas

The K-factor method is the standard exam approach. K is the approximate resistance of a one-circular-mil, one-foot conductor: about 12.9 Ω for copper and 21.2 Ω for aluminum. Conductor area in circular mils (CM) comes from NEC Chapter 9, Table 8.

FindSingle-phaseThree-phase
Voltage dropVD = 2 × K × I × L ÷ CMVD = 1.732 × K × I × L ÷ CM
Minimum conductor sizeCM = 2 × K × I × L ÷ VDCM = 1.732 × K × I × L ÷ VD
Maximum lengthL = CM × VD ÷ (2 × K × I)L = CM × VD ÷ (1.732 × K × I)
Percent drop% = VD ÷ E × 100% = VD ÷ E × 100

L is the one-way length in feet. The 2 in the single-phase formula accounts for current going out and back.

Circular mil areas you will use most (Chapter 9, Table 8): 14 AWG = 4,110, 12 AWG = 6,530, 10 AWG = 10,380, 8 AWG = 16,510, 6 AWG = 26,240, 4 AWG = 41,740.

Worked example

Single-phase voltage drop

  1. 1

    The question

    A 240 V single-phase load draws 24 A through 10 AWG copper conductors. The load is 120 ft from the panel. What is the voltage drop, as volts and as a percentage?

  2. 2

    Plug in

    VD = 2 × 12.9 × 24 × 120 ÷ 10,380 = 74,304 ÷ 10,380 = 7.16 V.

  3. 3

    Percent

    7.16 ÷ 240 × 100 = 2.98%.

  4. ✓ Answer: About 7.2 volts, just under 3%.
Worked example

Size the conductor for a 3% limit

  1. 1

    The question

    A 240 V single-phase, 40 A load is 150 ft from the panel. What is the smallest copper conductor that keeps voltage drop at or below 3%?

  2. 2

    Allowed drop

    3% of 240 V = 0.03 × 240 = 7.2 V.

  3. 3

    Required area

    CM = 2 × 12.9 × 40 × 150 ÷ 7.2 = 154,800 ÷ 7.2 = 21,500 CM.

  4. 4

    Pick the size

    8 AWG has only 16,510 CM, too small. The next size, 6 AWG, has 26,240 CM.

  5. ✓ Answer: 6 AWG copper. Always round up to the next conductor with at least the required area, then confirm ampacity separately.

Three-phase example: a 480 V three-phase load draws 50 A on 8 AWG copper, 200 ft away. VD = 1.732 × 12.9 × 50 × 200 ÷ 16,510 = 223,428 ÷ 16,510 = 13.5 V, which is 13.5 ÷ 480 = 2.8%.

The 3% and 5% figures come from informational notes, not mandatory rules, in most cases; see NEC voltage drop rules. The full method, including the Chapter 9 Table 9 approach, is in the voltage drop formula guide.

Transformer formulas

FindFormula
Turns ratioa = N_p ÷ N_s = E_p ÷ E_s
Current ratioI_s ÷ I_p = E_p ÷ E_s
Single-phase full-load currentI = kVA × 1,000 ÷ E
Three-phase full-load currentI = kVA × 1,000 ÷ (E × 1.732)
kVA ratingkVA = E × I ÷ 1,000 (× 1.732 for three-phase)

Example: a single-phase 480 V to 120 V transformer has a ratio of 4:1. If the secondary delivers 40 A, the primary carries 40 ÷ 4 = 10 A (ignoring losses): 480 × 10 = 4,800 VA = 120 × 40.

Sizing overcurrent protection for transformers uses the percentages in NEC 450.3; see transformer calculations.

Motor formulas

FindFormula
Output wattsW = HP × 746
EfficiencyEff = output ÷ input
Input wattsW_in = HP × 746 ÷ Eff
Single-phase current (estimate)I = HP × 746 ÷ (E × Eff × PF)
Three-phase current (estimate)I = HP × 746 ÷ (E × 1.732 × Eff × PF)

Example: a 10 HP motor with 88% efficiency needs 10 × 746 ÷ 0.88 = 7,460 ÷ 0.88 = 8,477 W of electrical input.

Series, parallel and AC formulas

TopicFormula
Series resistanceR_T = R₁ + R₂ + R₃ …
Parallel resistanceR_T = 1 ÷ (1/R₁ + 1/R₂ + 1/R₃ …)
Two in parallelR_T = (R₁ × R₂) ÷ (R₁ + R₂)
Equal resistors in parallelR_T = R ÷ number of resistors
Inductive reactanceX_L = 2 × π × f × L
Capacitive reactanceX_C = 1 ÷ (2 × π × f × C)
ImpedanceZ = √(R² + X²)
Power factorPF = W ÷ VA = R ÷ Z
Peak and RMSPeak = RMS × 1.414; RMS = Peak × 0.707

The rules behind those first four rows, with combination circuits, are in series vs parallel circuits. The AC rows are explained in basic electrical theory and power factor and kVA.

A few multipliers are not physics, but you will use them in almost every calculation question:

RuleMultiplierWhere
Continuous loads: OCPD sizing125% of continuous load (+100% of noncontinuous)NEC 210.20(A), NEC 215.3
Continuous load on an OCPD80% of the rating (the inverse of 125%)Same rule, other direction
Single motor branch-circuit conductors125% of table FLCNEC 430.22

A continuous load is one expected to run at maximum current for 3 hours or more. Example: a 32 A continuous load needs an overcurrent device of at least 32 × 1.25 = 40 A. Standard OCPD ratings are listed in NEC 240.6(A); see standard breaker sizes.

Practice questions

Exam-style question

What is the full-load current of a 75 kVA, 480-volt, three-phase transformer?

Pick an answer to see the explanation.

Exam-style question

A 120-volt single-phase circuit supplies 16 amperes over 12 AWG copper (6,530 CM). The load is 100 feet away. Using K = 12.9, what is the approximate voltage drop?

Pick an answer to see the explanation.

Exam-style question

A 5 HP motor operates at 85% efficiency. Approximately how many watts of electrical input does it require at full load?

Pick an answer to see the explanation.

Next steps

Formulas only stick when you use them. Work the deeper guides in order: basic electrical theory, Ohm's law, series vs parallel circuits and single-phase vs three-phase. Then put the whole sheet to work under time with a free journeyman electrician practice test.