Power factor is the ratio of true power (kilowatts, the power that does work) to apparent power (kilovolt-amperes, volts times amps). A heater has a power factor of 1.0: every amp does useful work. A motor might run at 0.8: the circuit carries 25% more current than the work alone would require, because part of the current only builds and collapses magnetic fields. Since wires, breakers and transformers are sized for current, power factor directly affects what you install.

This guide explains the power triangle, gives every formula you need for single- and three-phase circuits, and works through the calculations the journeyman exam asks for, including power factor correction with capacitors and the NEC rules that depend on power factor.

Power factor in one picture: the power triangle

θTrue power: kW (does the work)Reactivepower: kVARApparent power:kVA (E × I)PF = kW ÷ kVA
The power triangle: true power (kW), reactive power (kVAR) and apparent power (kVA). Shown at a power factor of 0.8.

The three kinds of power form a right triangle:

  • True power (P), in watts or kW: turns into heat, light or mechanical work. This is what an energy meter mostly bills.
  • Reactive power (Q), in VAR or kVAR: current that flows back and forth to build magnetic fields in motors and transformers (or electric fields in capacitors). It does no net work, but it still flows in the wires.
  • Apparent power (S), in VA or kVA: voltage times current, the total the system must carry.

Power factor is the cosine of the angle θ between kW and kVA. When current and voltage are in phase (resistive load), θ is 0 and PF = 1.0. The more the current lags or leads the voltage, the lower the power factor.

The formulas you need

QuantitySingle-phaseThree-phase
Apparent power (VA)E × I1.732 × E × I
True power (W)E × I × PF1.732 × E × I × PF
Current from wattsW ÷ (E × PF)W ÷ (1.732 × E × PF)
Power factorW ÷ VAW ÷ VA
Reactive power (VAR)√(VA² − W²)√(VA² − W²)

The two you will use most

kW = kVA × PF · kVA = kW ÷ PF

For 3-phase, E is always the line-to-line voltage and I the line current, whether the load is connected in delta or wye; see delta vs wye. All of these come from Ohm's law and the power formula; review Ohm's law and the power wheel if any of them look unfamiliar.

Why power factor matters: current

For a fixed amount of real work, current goes up as power factor goes down. That current heats conductors, trips breakers and fills up transformer capacity.

Worked example

Same 100 kW, two power factors

  1. 1

    The question

    A 480-volt, 3-phase plant load uses 100 kW. What is the line current at a power factor of 0.70, and at 0.95?

  2. 2

    At PF 0.70

    kVA = 100 ÷ 0.70 = 142.9 kVA. I = 142,857 ÷ (1.732 × 480) = 171.8 A.

  3. 3

    At PF 0.95

    kVA = 100 ÷ 0.95 = 105.3 kVA. I = 105,263 ÷ (1.732 × 480) = 126.6 A.

  4. ✓ Answer: About 172 A at 0.70 versus about 127 A at 0.95: roughly 45 A less current for exactly the same work.

1.0

PF of a resistive heater

0.8

Common rating basis for generators

135%

Capacitor conductor ampacity, 460.8(A)

Quick table: 100 kW at different power factors

The same 100 kW of real work, at 480 V three-phase:

Power factorkVAkVARLine current
1.00100.00120.3 A
0.95105.332.9126.6 A
0.90111.148.4133.6 A
0.85117.662.0141.5 A
0.80125.075.0150.4 A
0.70142.9102.0171.8 A
0.60166.7133.3200.5 A

Two patterns to remember. Current scales with 1 ÷ PF, so dropping from 1.0 to 0.8 adds 25% current. And the penalty grows fast at the bottom of the table: going from 0.7 to 0.6 costs more current than going from 1.0 to 0.85.

Lagging, leading and what causes each

  • Lagging power factor: current lags voltage. Caused by inductive loads: induction motors, transformers, magnetic ballasts, welders. Most facilities run lagging.
  • Leading power factor: current leads voltage. Caused by capacitive loads: power factor correction capacitors, long lightly loaded cables, some electronic power supplies.
  • Unity (1.0): resistive loads such as heaters and incandescent lamps.

Induction motors have their worst power factor at light load, because they draw nearly the same magnetizing current whether loaded or not. An oversized motor running at a fraction of its rating is a common cause of low plant power factor.

Electronic loads add a second issue: harmonic distortion. Their current is not a clean sine wave, so the true power factor can be low even when voltage and current peaks line up. The fix for that is filtering, not capacitors.

Worked examples, built like exam questions

Worked example

Find power factor from a meter reading

  1. 1

    The question

    A 240-volt, single-phase load draws 20 A and a wattmeter reads 3840 W. What is the power factor?

  2. 2

    Apparent power

    VA = 240 × 20 = 4800 VA.

  3. 3

    Power factor

    PF = W ÷ VA = 3840 ÷ 4800 = 0.80.

  4. ✓ Answer: 0.80 (80%), lagging if the load is a motor.
Worked example

All three sides of the triangle

  1. 1

    The question

    A 3-phase, 480-volt motor draws 50 A at a power factor of 0.85. Find kVA, kW and kVAR.

  2. 2

    kVA

    1.732 × 480 × 50 ÷ 1000 = 41.57, about 41.6 kVA.

  3. 3

    kW

    41.57 × 0.85 = 35.33, about 35.3 kW.

  4. 4

    kVAR

    √(41.57² − 35.33²) = √(1728.0 − 1248.2) = √479.8 = 21.9 kVAR. Carry the unrounded values: squaring numbers already rounded to 41.6 and 35.3 gives 22.0, a small error that can push you toward the wrong choice.

  5. ✓ Answer: 41.6 kVA, 35.3 kW, 21.9 kVAR.
Worked example

Current from kW and power factor

  1. 1

    The question

    A 10 kW, 3-phase load operates at 208 volts with a power factor of 0.80. What is the line current?

  2. 2

    Formula

    I = W ÷ (1.732 × E × PF) = 10,000 ÷ (1.732 × 208 × 0.80).

  3. 3

    Calculate

    1.732 × 208 × 0.80 = 288.2. 10,000 ÷ 288.2 = 34.7 A.

  4. ✓ Answer: 34.7 A. Forgetting the power factor gives 27.8 A, a classic wrong answer choice.

Power factor correction with capacitors

Capacitors draw leading reactive current that cancels part of the lagging reactive current of motors. The utility and the upstream wiring then carry less total current.

Capacitor kVAR needed

kVAR = kW × (tan θ₁ − tan θ₂)

where θ₁ is the angle at the existing power factor and θ₂ at the target (θ = arccos PF).

Worked example

Correct 100 kW from 0.70 to 0.95

  1. 1

    Angles

    At PF 0.70, tan θ₁ = 1.020. At PF 0.95, tan θ₂ = 0.329.

  2. 2

    kVAR before and after

    Before: 100 × 1.020 = 102.0 kVAR. After: 100 × 0.329 = 32.9 kVAR.

  3. 3

    Capacitor size

    102.0 − 32.9 = 69.1 kVAR.

  4. ✓ Answer: About 69 kVAR of capacitors. As shown earlier, line current at 480 V drops from about 172 A to about 127 A.

Article 460 covers the installation:

  • Conductor ampacity: capacitor circuit conductors must have an ampacity of not less than 135% of the capacitor's rated current (NEC 460.8(A)). A 50 kVAR, 480-volt, 3-phase capacitor draws 50,000 ÷ (1.732 × 480) = 60.1 A, so its conductors need at least 60.14 × 1.35 = 81.2 A. Where the capacitor connects to the motor terminals or motor circuit conductors, its conductors must also be at least one-third of the ampacity of the motor circuit conductors, whichever gives the larger result.
  • Motor overloads: when a capacitor is connected on the load side of a motor overload device, the overload rating or setting is based on the improved power factor of the motor circuit, and the capacitor's effect is disregarded when sizing the motor circuit conductors (NEC 460.9).
  • Discharge: capacitors must have a means to drain the stored charge after they are disconnected (NEC 460.6).

Where power factor shows up in the NEC

Lighting loads with ballasts or drivers. NEC 220.18(B): for circuits supplying lighting units with ballasts, transformers, autotransformers or LED drivers, the calculated load is based on the total ampere ratings of those units, not the total watts of the lamps. A fixture with 100 W of LEDs may draw more than 100 ÷ 120 amps if its driver's power factor is below 1.0.

Motors. You do not calculate motor current with watts and power factor on the exam. NEC 430.6(A)(1) sends you to Tables 430.247 through 430.250, whose full-load currents already reflect typical motor power factor and efficiency. See horsepower to amps and motor calculations under Article 430.

Transformers and generators are rated in kVA (generators often also in kW at a stated power factor, commonly 0.8). Sizing a transformer from kW without dividing by power factor undersizes it. The sizing method is in transformer calculations.

Power factor, the utility bill and the meter

Residential customers are billed for kWh, so power factor rarely shows up on a home bill. Many commercial and industrial rate schedules are different: they include a demand charge measured in kW or kVA, a power factor adjustment when the monthly power factor falls below a threshold set in the tariff, or a charge for reactive energy (kVARh). The threshold and the penalty vary by utility, so read the customer's tariff before promising savings.

That is also why correction capacitors are usually installed by the owner's choice, not by code. The NEC does not require any minimum power factor. It only regulates how capacitors are installed and protected (Article 460).

To measure power factor on the job, use a power quality analyzer or a clamp meter with a power function. It reads volts, amps, kW, kVA and PF at once. A plain multimeter and a separate clamp give you volts and amps (kVA) but not kW, so they cannot tell you power factor.

Practice: power factor exam questions

Exam-style question

A single-phase load draws 15 A at 240 V and consumes 2880 W. What is its power factor?

Pick an answer to see the explanation.

Exam-style question

A 75 kVA transformer supplies a load with a power factor of 0.8. What is the maximum true power it can deliver at full rating?

Pick an answer to see the explanation.

Exam-style question

The ampacity of conductors supplying a power factor correction capacitor shall not be less than what percentage of the capacitor's rated current?

Pick an answer to see the explanation.

Exam-style question

A 50 kW, 480-volt, 3-phase load operates at a power factor of 0.80. What is the line current?

Pick an answer to see the explanation.

The mistakes that cost points

Dividing when you should multiply. kW = kVA × PF. kW is always the smaller number.

Leaving out power factor when finding current from watts. I = W ÷ (E × PF), with 1.732 for 3-phase.

Calculating motor current from horsepower and power factor. Use the NEC tables.

Treating harmonics like displacement power factor. Capacitors fix lagging displacement power factor; they do not fix harmonic distortion and can make resonance problems worse.

Where to go next

Power factor ties together basic electrical theory, the electrical formulas cheat sheet and single-phase vs three-phase power. Next, apply it to real equipment in transformer calculations, then test your speed with the free journeyman practice test.

→Where table currents replace PF mathMotor Calculations: FLC, Conductors, Overloads and Breakers (Article 430)