To convert horsepower to amps for wire and breaker sizing, use the NEC full-load current tables, not a formula. Table 430.248 gives single-phase motor currents and Table 430.250 gives three-phase currents: a 10 hp, 460 V three-phase motor is 14 A, and a 5 hp, 230 V single-phase motor is 28 A. Those table values are what the code, the inspector and the exam all expect.

This guide gives you the two tables in usable form, explains which voltage column to use, shows the horsepower-to-amps formula with worked numbers so you can see why it gives the wrong exam answer, and lists the exceptions where the nameplate wins.

Why the NEC tables beat the formula

Motor current depends on efficiency, power factor, speed, design and load. Two 10 hp motors from different manufacturers can have different nameplate currents. The NEC removes that uncertainty by giving one conservative value per horsepower and voltage.

There are four FLC tables in Article 430:

TableMotor type
430.247Direct-current motors
430.248Single-phase AC motors
430.249Two-phase AC motors (rare)
430.250Three-phase AC motors (induction and synchronous)

On the journeyman exam you will mostly use 430.248 and 430.250.

Single-phase horsepower to amps (Table 430.248)

hp115 V208 V230 V
¼5.83.22.9
⅓7.24.03.6
½9.85.44.9
¾13.87.66.9
1168.88
1½201110
22413.212
33418.717
55630.828
7½804440
101005550

The table also has a 200 V column. Notice that the 230 V value is exactly half the 115 V value: double the voltage, half the current.

Three-phase horsepower to amps (Table 430.250)

These are the induction-type squirrel-cage and wound-rotor values, which cover almost every exam question:

hp208 V230 V460 V575 V
½2.42.21.10.9
¾3.53.21.61.3
14.64.22.11.7
1½6.66.03.02.4
27.56.83.42.7
310.69.64.83.9
516.715.27.66.1
7½24.222119
1030.8281411
1546.2422117
2059.4542722
2574.8683427
3088804032
401141045241
501431306552
601691547762
752111929677
10027324812499

Table 430.250 also has 115 V, 200 V and 2300 V columns and a separate group of values for synchronous motors at unity power factor.

10 hp, 3-phase: full-load current (A)32.2200 V30.8208 V28230 V14460 V11575 VUse 460 V for a 480 V system, 230 V for 240 V
Same 10 hp three-phase motor, different voltage: the table current drops as voltage rises (Table 430.250).

Which voltage column? (480 V, 240 V and 208 V)

The column headings are rated motor voltages, which are a little lower than system voltages. The notes to both tables say the listed currents are permitted for system voltage ranges:

System voltageUse the column for
110–120 V115 V
220–240 V230 V
440–480 V460 V
550–600 V575 V
208 V208 V (its own column)

So a 20 hp motor on a 480 V system is 27 A (the 460 V column). A 20 hp motor on a 208 V system is 59.4 A, not the 230 V value of 54 A.

If the difference between system and rated voltage is new to you, see 110 vs 120 volts and nominal voltage.

The horsepower to amps formula (and why it gives the wrong exam answer)

One horsepower equals 746 watts of mechanical output. To get input current, you divide by voltage and by everything that makes a real motor draw more than its output: efficiency and power factor.

Single-phase

I = (hp × 746) ÷ (V × eff × PF)

Three-phase

I = (hp × 746) ÷ (V × 1.732 × eff × PF)

Worked example

10 hp, 460 V, three-phase: formula vs table

  1. 1

    Ideal motor (100% efficient, unity power factor)

    10 × 746 = 7,460 W. 460 × 1.732 = 796.72. 7,460 ÷ 796.72 = 9.36 A

  2. 2

    Typical motor (assume 90% efficiency, 0.85 power factor)

    eff × PF = 0.90 × 0.85 = 0.765. 796.72 × 0.765 = 609.49. 7,460 ÷ 609.49 = 12.24 A

  3. 3

    NEC table

    Table 430.250, 10 hp at 460 V = 14 A

  4. ✓ Answer: Use 14 A for any NEC sizing. The formula answers (9.36 A and 12.24 A) are estimates that would undersize the circuit.
Worked example

5 hp, 230 V, single-phase: formula vs table

  1. 1

    Formula (assume 85% efficiency, 0.80 power factor)

    5 × 746 = 3,730 W. 230 × 0.85 × 0.80 = 156.4. 3,730 ÷ 156.4 = 23.85 A

  2. 2

    NEC table

    Table 430.248, 5 hp at 230 V = 28 A

  3. ✓ Answer: 28 A is the value for conductors and protection.

The power factor and efficiency in those examples are assumptions; real motors vary, which is exactly why the code uses tables. For more on what power factor does to current, read power factor, kW and kVA, and for the three-phase √3 see single-phase vs three-phase.

Where the table current goes next

Once you have the FLC, every other motor number is a multiplier. Using a 25 hp, 460 V motor (34 A from the table, 32 A on the nameplate):

What you are sizingRuleUsesResult
Branch conductors125% (430.22)Table FLC42.5 A
Inverse-time breaker250%, next size up (Table 430.52(C)(1))Table FLC85 → 90 A
Overload, SF 1.15125% (430.32)Nameplate40 A
Disconnect rating115% (430.110)Table FLC39.1 A

The full sequence with three worked examples is in motor calculations under Article 430.

→Next step: wire, overloads and breakersMotor Calculations: FLC, Conductors, Overloads and Breakers (Article 430)

When the nameplate wins over the table

NEC 430.6(A)(1) has a short list of cases where you use the marked current instead of the horsepower table:

  • Multispeed motors, whose current varies with speed.
  • Low-speed motors (less than 1200 rpm) and high-torque motors, which can draw more than the table.
  • Shaded-pole and permanent split-capacitor (PSC) fan or blower motors in equipment marked with the motor type: use the current marked on the equipment nameplate.
  • Listed motor-operated appliances marked with both horsepower and current: use the appliance nameplate current.
  • A motor marked in amperes but not horsepower: the horsepower is assumed to be the one that corresponds to that current in the tables.

And hermetic refrigerant motor-compressors (A/C and refrigeration) are not sized from horsepower at all. They use the rated-load current on the nameplate under Article 440. See MCA vs MOCP.

Going backward: amps to horsepower

Sometimes the question runs the other way: "A three-phase, 460 V motor circuit has a full-load current of 52 A. What horsepower motor is it?" Go to the 460 V column of Table 430.250, find 52 A, and read across: 40 hp.

If the current falls between two rows, it doesn't match a table rating: 30 A at 460 V sits between 20 hp (27 A) and 25 hp (34 A). On the exam, reverse lookups almost always land exactly on a table value, so if yours doesn't, re-check the voltage column and the phase before you pick an answer.

The same reverse logic answers "what is the largest motor this circuit can serve" questions: compute the FLC the circuit can carry (conductor ampacity ÷ 1.25), then find the largest horsepower in the correct column whose FLC does not exceed it. A 10 AWG copper circuit at 60°C (30 A) can carry an FLC of 30 ÷ 1.25 = 24 A, which covers a 2 hp, 115 V single-phase motor (24 A) but not a 3 hp (34 A).

Quick sanity check: amps per horsepower

You don't use this for sizing, but it catches typos. In the 10 to 100 hp range of Table 430.250, three-phase motors at 460 V run about 1.2 to 1.4 A per hp (10 hp = 14 A, 50 hp = 65 A, 100 hp = 124 A). At 230 V the current is double that. If you read 140 A for a 10 hp, 460 V motor, you are in the wrong row or the wrong table.

Exam-style questions

Exam-style question

What full-load current is used to size the branch-circuit conductors for a 7½ hp, 230 V, three-phase motor?

Pick an answer to see the explanation.

Exam-style question

A 1 hp, 115 V, single-phase motor is installed. What current is used for conductor sizing?

Pick an answer to see the explanation.

Exam-style question

A 20 hp, three-phase induction motor is connected to a 480 V system. What table full-load current applies?

Pick an answer to see the explanation.

Keep these tables one flip away

Tab Tables 430.248 and 430.250 together; they are on facing or adjacent pages near the end of Article 430. Highlight the 115/230 V columns in one color and the 208/460 V columns in another so you never read across the wrong row under time pressure. Our code book tabbing guide has a full layout.

Motor FLC feeds the 25% largest-motor line in the standard dwelling load calculation and every motor feeder you will ever size. The tables themselves are in NFPA 70, available through the NFPA 70 page. When you can find any value in under 20 seconds, move on to a free journeyman practice test.