A dwelling load calculation tells you the minimum service or feeder size a house needs. Under the NEC standard method, you calculate general lighting at 3 VA per square foot, add 1,500 VA for each small-appliance and laundry circuit, apply the Article 220 demand factors, then add appliances, the dryer, the range, the larger of heating or cooling and any EV charger. Divide the total volt-amperes by 240 volts and you have the calculated load in amperes.

This guide takes you through every line of the standard method exactly as the 2023 NEC lays it out, then runs one complete service calculation for a sample house, from square footage to conductor size and neutral. Work through it once with a pencil and you will be able to do the exam version in under ten minutes.

What the standard method is (and when you use it)

Article 220 gives you two ways to calculate a dwelling service or feeder. The standard method is Part III (220.40 through 220.61). The optional method is Part IV (220.82 and 220.83), a shortcut allowed only for single dwelling units. Exam questions tell you which one to use, and if they don't, the standard method is the default.

→The faster method, comparedDwelling Load Calculation: The Optional Method (NEC 220.82)

The standard method is longer, but it works for every dwelling: one-family houses, each unit of a duplex, and multifamily buildings (with the Table 220.84 shortcut also available for those). It is also the method that teaches you why each load counts the way it does, so learn it first.

Two housekeeping rules from NEC 220.5 apply to every line:

  • Use nominal voltages: 120, 120/240, 208Y/120 and so on NEC 220.5(A). A dwelling on 120/240 V is divided by 240, never by 230 or 220.
  • Rounding: you may round to the nearest whole ampere, dropping decimal fractions smaller than 0.5 NEC 220.5(B). So 192.75 A becomes 193 A, and 192.4 A becomes 192 A. Round only the final amperes, never the VA lines along the way.

2023 NEC section numbers: what moved

Article 220 was reorganized in recent editions, and a lot of study material still uses the old numbers. If your state exam is on the 2023 NEC, these are the sections to tab:

What you are looking up2020 NEC2023 NEC
Dwelling unit load, 3 VA/ft²220.14(J)220.41
Lighting demand factors (100/35/25%)Table 220.42Table 220.45
Floor area from outside dimensions220.11220.5(C)
EV charger (EVSE) loadno specific rule220.57
Small-appliance, laundry, appliances, dryer, range220.52 to 220.55220.52 to 220.55 (same)
Noncoincident loads, neutral220.60, 220.61220.60, 220.61 (same)
Service neutral minimum size250.24(C)250.24(D)

Older books (2017 and before) put the dwelling row in Table 220.12. That row is gone from Table 220.12 now, which is why so many candidates search the table and come up empty. The value itself has not changed: still 3 VA per square foot.

Step 1: General lighting load at 3 VA per square foot

Start with the floor area. NEC 220.5(C) says to calculate it from the outside dimensions of the building or dwelling unit. For dwelling units, the 2023 text excludes open porches and unfinished areas not adaptable for future use as habitable or occupiable space.

Multiply the area by the unit load in NEC 220.41:

General lighting load

Floor area (ft²) × 3 VA = general lighting VA

That 3 VA already covers general lighting outlets and the general-use receptacles rated 20 A or less, including the bathroom and garage receptacle circuits. You do not add anything extra for those outlets, no matter how many there are. That surprises people, and it is exactly what the exam tests.

A 2,400 ft² house: 2,400 × 3 = 7,200 VA.

Step 2: Small-appliance and laundry circuits at 1,500 VA each

NEC 220.52(A) adds 1,500 VA for each 2-wire small-appliance branch circuit required by NEC 210.11(C)(1). Every dwelling has at least two. If the question says the kitchen has three, use three.

NEC 220.52(B) adds 1,500 VA for each laundry branch circuit required by NEC 210.11(C)(2). Every dwelling has at least one.

Both sections let you add these loads to the general lighting load and apply the lighting demand factors to the combined total. Everyone does, because it lowers the result. For where these circuits come from and what they may serve, see required and dedicated circuits under 210.11.

Step 3: Apply the Table 220.45 demand factors

People don't turn on every light and plug in every appliance at once. Table 220.45 (Table 220.42 in older editions) reflects that for dwelling units:

Portion of the lighting + small-appliance + laundry loadDemand factor
First 3,000 VA or less100%
From 3,001 to 120,000 VA35%
Remainder over 120,000 VA25%

The 25% tier only matters on large multifamily feeders. For a single house you will use the first two lines.

Typical house

3,000 VA + (total − 3,000) × 0.35

3 VA/ft²

general lighting, 220.41

1,500 VA

per small-appliance or laundry circuit

100% / 35%

first 3,000 VA / next to 120,000 VA

Step 4: Fixed appliances at 75% when there are four or more

NEC 220.53 lets you apply a 75% demand factor to the nameplate ratings of four or more appliances fastened in place and served by the same feeder or service. Only appliances rated ¼ hp or greater, or 500 W or greater count toward the four (a 300 VA range hood fan does not).

Typical members of this group: water heater, dishwasher, garbage disposal, trash compactor, built-in microwave, attic fan, well pump, water softener.

The 75% factor does not apply to:

  • Electric ranges, ovens and cooktops (they have Table 220.55)
  • Clothes dryers (they have 220.54)
  • Space heating and air conditioning (they go through 220.60)
  • Electric vehicle supply equipment (EVSE)

With three or fewer qualifying appliances, add them at 100%.

Step 5: Dryer, range and EV charger

Electric clothes dryer: 5,000 VA minimum

NEC 220.54: each electric dryer counts at 5,000 W (VA) or its nameplate rating, whichever is larger. A 4,500 W dryer counts as 5,000. A 5,600 W dryer counts as 5,600. For one to four dryers the Table 220.54 demand factor is 100%, so in a house you use the full value.

Ranges and cooking equipment: Table 220.55

A household range over 1¾ kW goes through NEC 220.55. For one range rated 12 kW or less, Column C gives a demand of 8 kW. For ratings above 12 kW, Note 1 adds 5% for each kW (or major fraction) above 12 kW. A 14 kW range becomes 8 × 1.10 = 8.8 kW.

Separate wall ovens and cooktops, several ranges and the Column A/B alternative all have their own rules. The Table 220.55 guide walks through every note with examples.

EV charger: 7,200 VA or nameplate (new in 2023)

NEC 220.57 requires the EVSE load to be calculated at 7,200 W (VA) or the nameplate rating, whichever is larger. A 32 A charger at 240 V (7,680 VA) counts at 7,680 VA. A 48 A charger counts at 48 × 240 = 11,520 VA. EVSE is excluded from the 220.53 demand factor, so it goes in at 100%.

Step 6: Heating vs air conditioning (220.60) and the largest motor

Noncoincident loads

NEC 220.60: where it is unlikely that two or more loads will be used at the same time, you only include the largest of them. Heating and cooling are the classic pair. Calculate each side:

  • Heating side: fixed electric space heating at 100% of nameplate NEC 220.51, plus any blower that runs with it.
  • Cooling side: the A/C compressor and condenser fan at nameplate, plus the indoor blower.

Keep the larger side. Drop the other one entirely.

One more sentence in 220.60 catches people: if a motor or A/C load is part of the noncoincident pair but is not the larger load, you compare using 125% of that motor or A/C load. In practice, check that the heat still wins against 1.25 × the A/C before you drop the A/C.

25% of the largest motor

Motor loads are calculated under NEC 220.50, which sends you to NEC 430.24 (and NEC 440.33 for hermetic compressors). Those sections size conductors at 125% of the largest motor plus the other loads. In a dwelling calculation, you add the extra 25% of the largest motor as one separate line. In most houses the largest motor is the A/C compressor; if you dropped the A/C under 220.60, use the largest motor that remains in the calculation.

→The 125% rule, explainedMotor Calculations: FLC, Conductors, Overloads and Breakers (Article 430)

Complete worked example: a 200 A service for a sample house

Here is a full standard-method calculation, the same shape as a long-form exam problem. Each line is a separate step so you can check your own work.

The house (120/240 V, single-phase, 2023 NEC):

  • 2,400 ft² measured from outside dimensions; no garage; an open porch (not counted)
  • 2 small-appliance circuits and 1 laundry circuit
  • Electric range, 12 kW
  • Electric dryer, 5.5 kW
  • Water heater 4,500 W; dishwasher 1,200 VA; disposal 900 VA; over-the-range microwave 1,500 VA (all fastened in place)
  • Electric baseboard heat: 6 kW total, in four separately controlled rooms
  • Central A/C: compressor 26 A, condenser fan 1.5 A, air handler blower 4 A, all at 240 V
  • EV charger rated 48 A at 240 V
Worked example

Standard method, 2,400 ft² house with EV charger

  1. 1

    General lighting (220.41)

    2,400 ft² × 3 VA = 7,200 VA

  2. 2

    Small-appliance and laundry (220.52)

    2 × 1,500 = 3,000 VA small-appliance. 1 × 1,500 = 1,500 VA laundry. Subtotal with lighting: 7,200 + 3,000 + 1,500 = 11,700 VA

  3. 3

    Demand factors (Table 220.45)

    First 3,000 VA at 100% = 3,000 VA. Remainder: 11,700 − 3,000 = 8,700 VA × 0.35 = 3,045 VA. Demand load: 3,000 + 3,045 = 6,045 VA

  4. 4

    Heating vs cooling (220.60)

    Heating: 6,000 VA (baseboards have no blower). Cooling: compressor 26 × 240 = 6,240 VA; condenser fan 1.5 × 240 = 360 VA; blower 4 × 240 = 960 VA. Total 6,240 + 360 + 960 = 7,560 VA. Keep the larger: 7,560 VA (A/C)

  5. 5

    Fixed appliances (220.53)

    4,500 + 1,200 + 900 + 1,500 = 8,100 VA. Four appliances, each 500 VA or more, so apply 75%: 8,100 × 0.75 = 6,075 VA

  6. 6

    Dryer (220.54)

    Nameplate 5,500 W is larger than 5,000 W: 5,500 VA

  7. 7

    Range (Table 220.55, Column C)

    One range, 12 kW (not over 12 kW): 8,000 VA

  8. 8

    EV charger (220.57)

    48 A × 240 V = 11,520 VA, larger than 7,200: 11,520 VA

  9. 9

    Largest motor, extra 25% (220.50, 430.24, 440.33)

    Largest motor is the compressor, 6,240 VA × 0.25 = 1,560 VA

  10. 10

    Total and amperes

    6,045 + 7,560 + 6,075 + 5,500 + 8,000 + 11,520 + 1,560 = 46,260 VA. 46,260 ÷ 240 = 192.75 A, rounded to 193 A (220.5(B)).

  11. ✓ Answer: 193 A calculated load. The minimum standard service that covers it is 200 A.

Check the addition a second way, by grouping: lighting group 6,045; HVAC and motor 7,560 + 1,560 = 9,120; appliances 6,075 + 5,500 + 8,000 = 19,575; EVSE 11,520. Then 6,045 + 9,120 + 19,575 + 11,520 = 46,260 VA. Same answer.

Demand load by line (VA)Lighting, SA, laundry6,045A/C (larger than heat)7,560Fixed appliances 75%6,075Dryer5,500Range (Column C)8,000EV charger11,52025% largest motor1,56046,260 VA ÷ 240 V = 193 A
Where the 46,260 VA comes from in the sample house. The EV charger alone is a quarter of the service load.

Sizing the service-entrance conductors

The minimum service is 200 A. For a one-family dwelling service rated 100 through 400 A supplying the entire load, NEC 310.12 lets the ungrounded conductors have an ampacity of 83% of the service rating:

200 A × 0.83 = 166 A. From the 75°C column of Table 310.16: 2/0 copper (175 A) or 4/0 aluminum (180 A). 1/0 copper (150 A) and 3/0 aluminum (155 A) are too small.

The 200 amp service wire size guide covers when the 83% rule can and cannot be used, and service-entrance conductors covers the rest of Article 230.

Calculating the neutral (220.61)

The neutral only carries the maximum unbalanced load: the 120-volt loads and the 120-volt parts of 120/240-volt appliances. Straight 240-volt loads (water heater, A/C, baseboards, EV charger) put nothing on the neutral. NEC 220.61(B)(1) also lets you take ranges and dryers at 70% of their calculated load.

Neutral loadCalculationVA
Lighting, SA, laundry (after demand)same as line load6,045
120-V appliances: dishwasher, disposal, microwave(1,200 + 900 + 1,500) × 0.752,700
Range8,000 × 0.705,600
Dryer5,500 × 0.703,850
Water heater, A/C, heat, EVSE (240 V only)no neutral load0
Total18,195

18,195 ÷ 240 = 75.8 A, rounded to 76 A. A 4 AWG copper neutral (85 A at 75°C) carries it. The grounded conductor also can't be smaller than the minimum in NEC 250.24(D)(1) (250.24(C) in the 2020 NEC), which for 2/0 copper service conductors is 4 AWG copper per Table 250.102(C)(1). Both checks give 4 AWG copper.

On the exam, the neutral question almost always hinges on two things: leaving out the 240-volt-only loads, and taking 70% of the range and dryer. If your neutral comes out bigger than the line load, you forgot one of them.

What the same house would look like without the EV charger

Delete the 11,520 VA charger and the total drops to 46,260 − 11,520 = 34,740 VA. 34,740 ÷ 240 = 144.75 A, rounded to 145 A. A 150 A service would have been enough.

That is the practical lesson behind 220.57: a single 48 A charger can move a house up a full service size. It is also why exam writers like to ask "what is the minimum service" on two versions of the same house.

The optional method runs this exact house again and gets a noticeably smaller number. Read it next if you want to see why many contractors prefer it for single-family homes.

Standard method checklist (copy this to your scratch paper)

#LineRuleSection
1General lightingft² × 3 VA220.41, 220.5(C)
2Small-appliance circuits1,500 VA each (min. 2)220.52(A)
3Laundry circuit1,500 VA each (min. 1)220.52(B)
4Demand on 1 + 2 + 33,000 at 100%, rest at 35% (25% over 120,000)Table 220.45
5Heat or A/Clarger only220.51, 220.60
6Fixed appliances75% if four or more220.53
7Dryer5,000 VA or nameplate, larger220.54
8CookingTable 220.55220.55
9EVSE7,200 VA or nameplate, larger220.57
10Largest motor+ 25%220.50, 430.24
11Amperestotal ÷ 240, round per 220.5(B)220.5

Exam-style questions

Exam-style question

A 2,000 ft² dwelling has the two required small-appliance circuits and one laundry circuit. Using the standard method, what is the demand load for general lighting, small-appliance and laundry?

Pick an answer to see the explanation.

Exam-style question

A dwelling has a 4,500 W water heater, a 1,200 W dishwasher, a 1,000 VA disposal, an 800 VA trash compactor and a 5,000 W dryer, all fastened in place. What is the demand load for the fixed appliances under 220.53?

Pick an answer to see the explanation.

Exam-style question

A house has 10 kW of electric heat in its air handler (with a 1,000 VA blower) and a 4,800 VA air conditioner that uses the same blower. What heating/cooling load goes into the standard calculation?

Pick an answer to see the explanation.

Exam-style question

A one-family dwelling has a calculated load of 41,500 VA at 120/240 V and a 200 A service supplying the entire load. What is the minimum size copper service-entrance conductor permitted using 310.12?

Pick an answer to see the explanation.

The mistakes that cost points on load calculation questions

Adding a 1,500 VA circuit for the bathroom. The bathroom circuit in 210.11(C)(3) is part of the 3 VA/ft² unit load. Only small-appliance and laundry circuits get 1,500 VA.

Taking 35% of the whole lighting total. The first 3,000 VA is always at 100%.

Putting the dryer or range in the 75% appliance group. They have their own sections. Same for A/C, heat and EV chargers.

Adding heating and cooling together. Keep the larger one.

Using the range nameplate instead of Column C. A 12 kW range is 8 kW, not 12 kW.

Dividing by 230 V or 220 V. NEC 220.5(A) requires nominal voltage: 240 V for a 120/240 V dwelling.

Rounding up to the next ampere by habit. 220.5(B) drops fractions below 0.5. 192.4 A is 192 A.

The rest of the load calculation toolkit

The standard method touches almost every other calculation topic on the exam. Once you are comfortable with it, work through the rest of this series:

For the conductor side of the problem, keep the wire ampacity chart (Table 310.16) and the list of standard breaker sizes close. The code text itself is available from NFPA's NFPA 70 page, including free read-only access.

Load calculations reward speed and a fixed routine. Copy the checklist above onto a blank sheet, do this house again from memory, then test yourself under the clock with a free journeyman practice test.