The optional method load calculation is the NEC 220.82 shortcut for sizing the service or feeder of a single dwelling unit. You add up all the general loads at their full rating, take the first 10 kVA at 100% and everything above it at 40%, then add the largest of the heating or air-conditioning selections in 220.82(C). Divide by 240 volts and you have the calculated load.
This guide shows when you are allowed to use it, what goes into each part, and then runs a complete example on the same house used in our standard method guide, so you can see exactly why the two answers differ. You will also get a heat pump example and an existing-house 220.83 example, the two variations exam writers like most.
Who can use the optional method (220.82(A))
Read that as three conditions, all of which must be true:
- One dwelling unit. A house, or one apartment's feeder. A whole apartment building's service uses the multifamily optional method in NEC 220.84, not 220.82.
- One set of 3-wire conductors at 120/240 V or 208Y/120 V.
- Conductor ampacity of 100 A or more. You can't use the optional method to justify a 60 A or 90 A service.
The 220.82 formula in one line
220.82 optional method
10,000 VA + 0.40 × (general loads − 10,000 VA) + heat/A/C
Then divide by 240 V (or by the nominal voltage that applies) and round per NEC 220.5(B): fractions below 0.5 are dropped.
That's it. No Table 220.45, no 75% appliance factor, no Table 220.55 for the range, no 5,000 VA dryer minimum step, no separate 25% for the largest motor. The single 40% factor replaces all of them, which is why the method is fast.
Part B: what goes into "general loads"
NEC 220.82(B) lists four groups. Add them all at full value.
| 220.82(B) item | What to include | Value |
|---|---|---|
| (1) General lighting and general-use receptacles | Floor area from outside dimensions | 3 VA/ft² |
| (2) Small-appliance and laundry circuits | Each 20 A circuit in 210.11(C)(1) and (C)(2) | 1,500 VA each |
| (3) Appliances | Fastened in place, permanently connected or on a specific circuit: ranges, wall ovens, cooktops, dryers not on the laundry circuit, water heaters, and similar | Nameplate |
| (4) Motors | Permanently connected motors not already included in (3) | Nameplate |
Things that do not go in Part B: the air conditioner, heat pump and electric space heating. They are handled only in Part C.
Note that the range goes in at nameplate. A 12 kW range is 12,000 VA here, not the 8,000 VA it would be under Column C. The 40% factor does the reducing.
Part C: the heating and air-conditioning load
NEC 220.82(C) tells you to include the largest of these six selections (only one of them):
| Selection | Load | Percent of nameplate |
|---|---|---|
| (1) | Air conditioning and cooling | 100% |
| (2) | Heat pump used without supplemental electric heat | 100% |
| (3) | Heat pump compressor plus supplemental electric heat (central systems) | 100% compressor + 65% supplemental |
| (4) | Electric space heating, fewer than four separately controlled units | 65% |
| (5) | Electric space heating, four or more separately controlled units | 40% |
| (6) | Electric thermal storage and other heat expected to run continuously at full nameplate | 100% |
Selection (3) has an important condition: if the heat pump compressor is prevented from operating at the same time as the supplemental heat, you don't add the compressor to the supplemental heat for the heating side.
10 kVA
taken at 100% (220.82(B))
40%
of everything above 10 kVA
65% / 40%
space heat: under 4 units / 4 or more
Complete example: the same 2,400 ft² house, optional method
Here is the house from the standard method example, unchanged: 2,400 ft², 2 small-appliance circuits and 1 laundry circuit, 12 kW range, 5.5 kW dryer, 4,500 W water heater, 1,200 VA dishwasher, 900 VA disposal, 1,500 VA microwave, a 48 A EV charger, 6 kW of baseboard heat in four separately controlled rooms, and central A/C totaling 7,560 VA (compressor 6,240 + condenser fan 360 + blower 960). 120/240 V, single-phase.
220.82 optional method, 2,400 ft² house
- 1
General lighting and receptacles (B)(1)
2,400 ft² × 3 VA = 7,200 VA
- 2
Small-appliance and laundry (B)(2)
3 circuits × 1,500 VA = 4,500 VA
- 3
Appliances at nameplate (B)(3)
Range 12,000 + dryer 5,500 + water heater 4,500 + dishwasher 1,200 + disposal 900 + microwave 1,500 + EV charger 11,520 = 37,120 VA
- 4
Total general load
7,200 + 4,500 + 37,120 = 48,820 VA
- 5
Apply 100% / 40%
First 10,000 VA at 100% = 10,000 VA. Remainder: 48,820 − 10,000 = 38,820 × 0.40 = 15,528 VA. General load demand: 10,000 + 15,528 = 25,528 VA
- 6
Heating and A/C (C), largest selection
(1) A/C at 100% = 7,560 VA. (5) Baseboard heat, four separately controlled units at 40% = 6,000 × 0.40 = 2,400 VA. Largest: 7,560 VA
- 7
Total and amperes
25,528 + 7,560 = 33,088 VA. 33,088 ÷ 240 = 137.87 A, rounded to 138 A.
Double-check step 5 a different way: 48,820 × 0.40 = 19,528; plus 60% of the first 10,000 (6,000) = 25,528 VA. Same answer.
For a 150 A one-family service supplying the entire load, NEC 310.12 allows conductors at 83% of the rating: 150 × 0.83 = 124.5 A. From the 75°C column of Table 310.16 that's 1 AWG copper (130 A) or 2/0 aluminum (135 A).
Why the two methods differ so much
| Line | Standard method | Optional method |
|---|---|---|
| Lighting, SA, laundry | 6,045 VA (Table 220.45) | inside the 40% pool |
| Range | 8,000 VA (Column C) | 12,000 VA nameplate, then 40% |
| Fixed appliances | 6,075 VA (75%) | nameplate, then 40% |
| Dryer | 5,500 VA | nameplate, then 40% |
| EV charger | 11,520 VA at 100% | nameplate, then 40% |
| Heat/A/C | 7,560 VA | 7,560 VA |
| 25% largest motor | 1,560 VA | not required |
| Total | 46,260 VA = 193 A | 33,088 VA = 138 A |
The big difference is the EV charger and the appliances: the standard method takes them close to 100%, while the optional method pushes everything past the first 10 kVA into the 40% pool.
Heat pump example: selection (3) in action
1,800 ft² house with a heat pump and 10 kW strips
- 1
The question
A 1,800 ft² house has 2 small-appliance circuits, 1 laundry circuit, a 10 kW range, a 5 kW dryer, a 4,500 W water heater and a 1,200 VA dishwasher. Heating and cooling come from a heat pump rated 4,800 VA with 10 kW of supplemental electric heat that can run with the compressor. Find the calculated load at 120/240 V.
- 2
General loads (B)
Lighting 1,800 × 3 = 5,400 VA. SA and laundry 3 × 1,500 = 4,500 VA. Appliances 10,000 + 5,000 + 4,500 + 1,200 = 20,700 VA. Total 5,400 + 4,500 + 20,700 = 30,600 VA
- 3
100% / 40%
10,000 + (30,600 − 10,000) × 0.40 = 10,000 + 8,240 = 18,240 VA
- 4
Heating and cooling (C)
Cooling (1): heat pump in cooling mode, 4,800 VA. Heating (3): compressor 4,800 + 65% of 10,000 = 4,800 + 6,500 = 11,300 VA. Largest: 11,300 VA
- 5
Total
18,240 + 11,300 = 29,540 VA ÷ 240 = 123.08 A, rounded to 123 A
Existing dwellings: the 220.83 method
NEC 220.83 is for a different question: can the existing service handle the new load? It works on a 120/240 V or 208Y/120 V 3-wire service and has two versions.
220.83(A): no new A/C or electric space heat being added. Add up general lighting (3 VA/ft²), 1,500 VA per small-appliance and laundry circuit, and the nameplate of appliances and motors. Take the first 8 kVA at 100% and the remainder at 40%.
220.83(B): new A/C or electric space heat is being added. Take the larger of the air-conditioning load or the space-heating load (not both) at 100%, then add the first 8 kVA of all other loads at 100% and the remainder at 40%.
Can a 100 A service take a new 5 kVA air conditioner?
- 1
The question
The 1,800 ft² house from the last example has no air conditioning and gas heat. The owner wants to add a 5,000 VA central A/C. The existing service is 100 A at 120/240 V. Use 220.83.
- 2
All other loads
Lighting 5,400 + SA and laundry 4,500 + range 10,000 + dryer 5,000 + water heater 4,500 + dishwasher 1,200 = 30,600 VA
- 3
Apply 220.83(B)
A/C at 100% = 5,000 VA. First 8,000 VA of other loads at 100% = 8,000 VA. Remainder: (30,600 − 8,000) × 0.40 = 22,600 × 0.40 = 9,040 VA.
- 4
Total
5,000 + 8,000 + 9,040 = 22,040 VA ÷ 240 = 91.83 A, rounded to 92 A
Optional method mistakes that cost points
Using it for a whole apartment building. 220.82 is one dwelling unit. Multifamily uses 220.84 or the standard method.
Counting heat or A/C twice. They are only in Part C.
Adding all six Part C selections. You pick the single largest.
Using 65% for four or more heaters. Four or more separately controlled units drop to 40%. A trick question may make the 40% heat smaller than the A/C, so the A/C wins.
Mixing up the 10 kVA and 8 kVA thresholds between 220.82 and 220.83.
Applying the optional method to a service under 100 A. The ampacity condition in 220.82(A) rules it out.
Exam-style questions
Exam-style question
Using the optional method, a dwelling has general loads (lighting, small-appliance, laundry and all appliances at nameplate) totaling 40,000 VA and a 6,000 VA air conditioner. The electric heat is 4 kW in two separately controlled units. What is the calculated load at 120/240 V?
Pick an answer to see the explanation.
Exam-style question
Under 220.82(C), a house has 12 kW of electric baseboard heat in six separately controlled rooms and a 5,000 VA air conditioner. What heating/cooling load is used?
Pick an answer to see the explanation.
Exam-style question
An existing dwelling has 28,000 VA of loads (lighting, small-appliance, laundry and appliances). No heating or A/C is being added. What is the calculated load using 220.83(A)?
Pick an answer to see the explanation.
Where to go next
The optional method rests on the same building blocks as the standard dwelling load calculation, so make sure you can do that one cold first. If the house has an electric range, compare the Part B nameplate treatment with Table 220.55 demand factors. For the A/C nameplate numbers you plug into Part C, see MCA vs MOCP, and once you have a service size, size the conductors with the 200 amp service wire size guide or service-entrance conductors.
The full 220.82 text is in NFPA 70, which you can read free online from the NFPA 70 page. Then put both methods under the clock with a free journeyman practice test.