This free journeyman electrician practice test gives you 17 multiple-choice questions written the way licensing exams write them, covering every major topic on the test. Pick an answer to reveal whether you got it right, the full explanation and the NEC section to look up.

Use it two ways: as a diagnostic before you start studying, to see which topics need the most work, and as a timed drill later, to build the code-book speed the real exam demands. The questions cite the 2023 NEC; if your state tests on another edition, confirm each section number in that book. Texas candidates take note: Texas exams have been referenced to the 2026 NEC since September 1, 2026, and question 14 below shows one value that changed.

How to use this practice test

You get the most out of a practice test when you take it under exam conditions. Score it honestly and it tells you exactly where to spend your study time.

  1. Set a timer for 30 minutes. That is a little under two minutes per question, a realistic pace for a mixed code and calculation exam.
  2. Use only what you can use on test day: your code book (if your exam is open book), a basic non-programmable calculator and scratch paper.
  3. Answer every question before you check any explanation. Write your answers down first, then click through.
  4. Mark each miss by cause: did not know the rule, could not find it in time, or made a math or reading error. Each cause needs a different fix.
  5. Look up every reference, even for questions you got right. Finding the section fast is the skill being tested.

How this test compares with the real exam

Real journeyman exams are longer and weighted by a published content outline. Texas, for example, splits its exam into an NEC knowledge portion and a calculations portion, each with its own time limit, and requires 70% on each, according to the Texas PSI candidate bulletin. Other states use one combined test with a different number of questions and a different clock.

This page samples every major area in proportion to how often it tends to appear: more branch circuit, wiring method and grounding questions, fewer on special topics. The mix of question types is also realistic:

Question typeShare of this testWhat it trains
Code or table lookup10 of 17Finding a section or table value fast
Calculation7 of 17Picking the right formula, table and rounding
"NOT" wording (within the above)2 of 17Reading the whole question before answering

For what the real exam covers and how it is weighted, start with what is on the journeyman electrician exam. For the whole licensing road, see the pillar guide on how to become a journeyman electrician.

Electrical theory and calculations

Theory questions are free points if your formulas are automatic. The NEC tells you to use nominal voltages (120, 208, 240, 480 and so on) for load calculations unless other voltages are specified.

Question 1 of 17 · Theory

A 4,800-watt, 240-volt water heater element is connected to a 240-volt circuit. How much current does it draw?

Pick an answer to see the explanation.

Question 2 of 17 · Three-phase

A 45-kVA balanced three-phase load is supplied at 208 volts. What is the line current, to the nearest ampere?

Pick an answer to see the explanation.

Question 3 of 17 · Voltage drop

A 120-volt, 2-wire circuit supplies a 16-ampere load 100 feet from the panel using 12 AWG copper (6,530 circular mils, K = 12.9). What is the approximate voltage drop?

Pick an answer to see the explanation.

More practice on these: Ohm's law, single-phase vs three-phase and the voltage drop formula.

Conductors, ampacity and overcurrent protection

Know which column of Table 310.16 to use, when correction and adjustment factors apply, and the list of standard OCPD sizes.

Question 4 of 17 · Ampacity

What is the ampacity of a 3 AWG THWN copper conductor (75°C) under the conditions of Table 310.16, with no more than three current-carrying conductors and a 30°C ambient?

Pick an answer to see the explanation.

Question 5 of 17 · Adjustment factors

Six current-carrying conductors are installed in the same raceway longer than 24 inches. What adjustment factor applies to their ampacity?

Pick an answer to see the explanation.

Question 6 of 17 · Overcurrent protection

Which of the following is NOT a standard ampere rating for fuses and inverse time circuit breakers?

Pick an answer to see the explanation.

Go deeper with the wire ampacity chart, correction and adjustment factors and standard breaker sizes.

Branch circuits, GFCI and receptacles

Question 7 of 17 · GFCI

In a dwelling unit, which of these locations is NOT on the 210.8(A) list of areas where receptacles require GFCI protection for personnel?

Pick an answer to see the explanation.

Question 8 of 17 · Required circuits

What is the minimum number of 20-ampere small-appliance branch circuits required to serve the kitchen countertop receptacles in a dwelling unit?

Pick an answer to see the explanation.

Related reading: GFCI requirements and branch circuits under Article 210.

Grounding and bonding

Article 250 sizing questions come down to one decision: are you sizing from the service conductors (Table 250.66) or from the overcurrent device (Table 250.122)?

Question 9 of 17 · GEC

A service is supplied by 3/0 AWG copper service-entrance conductors. What is the minimum size copper grounding electrode conductor to a metal underground water pipe electrode?

Pick an answer to see the explanation.

Question 10 of 17 · EGC

What is the minimum size copper equipment grounding conductor for a feeder protected by a 100-ampere circuit breaker?

Pick an answer to see the explanation.

See GEC sizing with Table 250.66 and EGC sizing with Table 250.122.

Wiring methods, boxes and raceways

Question 11 of 17 · Box fill

A box has a marked volume of 18.0 cubic inches and contains no clamps, devices, fittings or grounding conductors. What is the maximum number of 14 AWG conductors permitted?

Pick an answer to see the explanation.

Question 12 of 17 · Burial depth

What is the minimum cover required for UF cable directly buried in a location not subject to vehicular traffic and not covered by any other special condition in the table?

Pick an answer to see the explanation.

Question 13 of 17 · Raceway support

EMT must be securely fastened within what distance of each outlet box, junction box or other conduit termination?

Pick an answer to see the explanation.

Worked examples for these are in the box fill calculation and conduit fill calculation guides.

Load calculations

Question 14 of 17 · General lighting load

Using the 2023 NEC standard method, what is the general lighting and general-use receptacle load for a 2,400-square-foot dwelling, before demand factors?

Pick an answer to see the explanation.

Question 15 of 17 · Small-appliance and laundry

A dwelling has two small-appliance branch circuits and one laundry branch circuit. What load is added for these circuits in a standard load calculation?

Pick an answer to see the explanation.

Full walk-throughs: dwelling load calculation, standard method.

Motors and working space

Question 16 of 17 · Motor overloads

A continuous-duty motor has a nameplate full-load current of 20 A and a service factor of 1.15. Under 430.32(A)(1), what is the maximum rating of a separate overload device?

Pick an answer to see the explanation.

Question 17 of 17 · Working space

What is the minimum width of the working space in front of a 120/240-volt panelboard?

Pick an answer to see the explanation.

More on these topics: motor calculations and working clearance under 110.26.

How to work a calculation question without mistakes

Most points lost on calculation questions are not lost on arithmetic. They are lost on picking the wrong column, forgetting a factor or rounding the wrong way. Use the same five steps on every calculation, and write them down.

Worked example

Ampacity with correction and adjustment

  1. 1

    The question

    Six current-carrying 8 AWG THHN copper conductors run in one EMT raceway, more than 24 inches long, through a space where the ambient temperature is 30°C. What is the adjusted ampacity of each conductor?

  2. 2

    Pick the column

    THHN is rated 90°C, and the NEC lets you start derating from the 90°C column: 8 AWG copper = 55 A in Table 310.16.

  3. 3

    Apply correction

    The ambient is 30°C, the table's base temperature, so the correction factor is 1.00.

  4. 4

    Apply adjustment

    Six current-carrying conductors: 80% from Table 310.15(C)(1). 55 × 0.80 = 44 A.

  5. 5

    Check the termination limit

    Under NEC 110.14(C), the circuit also cannot exceed the termination rating. With 75°C terminals, 8 AWG copper is limited to 50 A from the 75°C column; 44 A is below that, so 44 A stands.

  6. ✓ Answer: 44 A per conductor. The trap answers are 55 A (no adjustment), 40 A (adjusting the 75°C value: 50 × 0.80) and 50 A (the 75°C column value).

The same habit works for box fill, conduit fill, voltage drop and motors: write what is asked, name the table, apply each factor on its own line, then check the result against any limit the code puts on it.

How exam questions try to trip you

Licensing exams rarely trick you with obscure rules. They use ordinary rules with wording that punishes skimming. Watch for these patterns:

  • NOT and EXCEPT questions. Question 7 above asks where GFCI is NOT required. If you skim, you pick the first location that needs GFCI.
  • Minimum vs maximum. A minimum cover depth and a maximum support spacing look alike on a fast read.
  • The wrong column. Ampacity answers from the 60°C, 75°C and 90°C columns are always among the choices.
  • The missing multiplier. Motor and continuous-load questions offer the answer without the 125% factor as a distractor.
  • Nameplate vs table. Motor conductors and short-circuit protection come from the NEC tables; overloads come from the nameplate.
  • Assuming exceptions apply. The Texas bulletin, for example, tells candidates not to consider exceptions or optional methods unless the question says to. Answer the question as written.

Score yourself

Count your correct answers and use this table. Many state exams require 70%, which is 12 of 17 here.

Correct answersScoreWhat it means
15 to 1788% to 100%Strong. Keep doing timed, full-length tests to build stamina.
12 to 1471% to 82%Passing range, but thin. One bad section on exam day can sink you.
9 to 1153% to 65%Below a 70% line. Target your weakest two topics first.
0 to 8under 50%Start with the fundamentals and a structured study plan.

What to do with your results

Missed a rule you did not know? Read the matching guide linked under each section, then answer 10 more questions on that topic.

Knew it but could not find it in time? Learn the layout of the NEC and tab your book. How to tab your NEC code book shows which articles and tables to mark.

Made math or reading errors? Slow down on words like NOT, minimum and maximum, write every step on scratch paper and re-check the column or row you used.

→Turn your results into a planHow to Study for the Journeyman Exam: A 60-Day Plan

If your score surprised you, read how hard is the journeyman exam to understand where points are usually lost, then follow the 60-day study plan. When you are ready for full-length, timed exams that match your state's format, go to the practice tests.