GFCI requirements are set by NEC 210.8. In a dwelling, the 2023 NEC requires GFCI protection for every 125- through 250-volt receptacle in bathrooms, garages, outdoors, crawl spaces, basements, kitchens, food and beverage prep areas with a sink, within 6 ft of a sink or tub, boathouses, laundry areas and damp or wet locations. Separate rules cover commercial buildings, specific appliances and outdoor outlets.

This guide walks through 210.8 one subsection at a time, (A) through (F), with what changed in the 2020 and 2023 editions. By the end you will know exactly which receptacles and outlets need protection, which exceptions exist, and how exam questions try to trip you up.

The general rule: listed Class A, readily accessible

The opening paragraph of NEC 210.8 in the 2023 NEC sets three conditions before you even get to the locations:

  1. A listed Class A GFCI provides the protection. Class A means it trips when ground-fault current is 6 mA or higher and does not trip below 4 mA, which is the personnel-protection level (more on that in GFI vs GFCI).
  2. The GFCI must be installed in a readily accessible location. That rules out a GFCI receptacle behind a refrigerator, washer or dishwasher.
  3. Distances from sinks, tubs and similar items are measured as the shortest path the power supply cord connected to the receptacle would follow without piercing a floor, wall, ceiling or fixed barrier.

210.8(A): the 12 dwelling unit locations

NEC 210.8(A) covers all 125-volt through 250-volt receptacles in the listed locations that are supplied by single-phase branch circuits rated 150 volts or less to ground. That voltage range has been in place since the 2020 NEC, and it is why a 240-volt dryer receptacle in a laundry area needs GFCI protection.

#Location (2023 NEC)Notes
(1)BathroomsEvery receptacle in the bathroom
(2)Garages, and accessory buildings with a floor at or below grade not intended as habitable roomsStorage, work and similar areas
(3)OutdoorsSee also 210.8(F) for outlets
(4)Crawl spacesAt or below grade level
(5)BasementsFinished or unfinished since 2020
(6)KitchensAll receptacles since 2023, not just countertop
(7)Areas with a sink and permanent provisions for food or beverage prep or cookingNew in 2023: wet bars, beverage stations
(8)SinksReceptacles within 6 ft of the top inside edge of the bowl
(9)Boathouses
(10)Bathtubs or shower stallsReceptacles within 6 ft of the outside edge
(11)Laundry areasIncludes 240 V dryer receptacles
(12)Indoor damp and wet locations
Outdoors (A)(3)Kitchen (A)(6)all receptaclesBath (A)(1)BedroomAFCI, not GFCILaundry(A)(11)Living roomWet bar(A)(7)Garage(A)(2)Basement (A)(5) and crawl space (A)(4)finished or unfinished
Where 2023 NEC 210.8(A) requires GFCI protection for dwelling receptacles (yellow). Bedrooms and living areas only need it within 6 ft of a sink or tub, or in damp or wet spots.

The 2023 kitchen change in plain words

Before 2023, only receptacles serving the countertop in a dwelling kitchen needed GFCI protection. Now NEC 210.8(A)(6) says kitchens, full stop. The refrigerator receptacle, a receptacle behind the range, a receptacle on the island cabinet, a wall receptacle at the breakfast table: if it is in the kitchen and rated 125 to 250 volts, it needs GFCI protection. In practice that means both small-appliance circuits are usually protected at the breaker, and the countertop layout from NEC 210.52 receptacle spacing is entirely GFCI.

New item NEC 210.8(A)(7) catches the spaces that are kitchens in all but name: a basement wet bar, a coffee station with a sink, a butler's pantry. If the area has a sink and permanent provisions for food prep, beverage prep or cooking, every receptacle there needs GFCI protection, regardless of distance from the sink.

Dwelling exceptions to know

The 2023 NEC collected the 210.8(A) exceptions after the list. The ones you are most likely to see:

  • Exception No. 1: receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment, where ground-fault protection of equipment is provided per 426.28 or 427.22.
  • Exception No. 2: a receptacle supplying only a permanently installed premises security system may omit GFCI protection.
  • Exception No. 3: listed weight-supporting ceiling receptacles (WSCR) used with a compatible weight-supporting attachment fitting to support a ceiling luminaire or ceiling fan may omit GFCI protection. If the luminaire or fan has an integral general-purpose convenience receptacle, that receptacle needs GFCI protection.
  • Exception No. 4 (new in 2023): factory-installed receptacles that are not readily accessible and are mounted inside bathroom exhaust fan assemblies do not require GFCI protection unless the listing or instructions require it.

210.8(B): other than dwelling units

NEC 210.8(B) covers commercial, industrial and other non-dwelling buildings. In the 2023 NEC it applies to 125- through 250-volt receptacles on single-phase branch circuits rated 150 volts or less to ground, 50 amperes or less, and to receptacles on three-phase branch circuits rated 150 volts or less to ground, 100 amperes or less, in these 15 locations:

#Location (2023 NEC 210.8(B))
(1)Bathrooms
(2)Kitchens
(3)Areas with sinks and permanent provisions for food prep, beverage prep or cooking
(4)Buffet serving areas with permanent provisions for food serving, beverage serving or cooking (new in 2023)
(5)Rooftops
(6)Outdoors
(7)Sinks: receptacles within 6 ft of the top inside edge of the bowl
(8)Indoor damp and wet locations
(9)Locker rooms with associated showering facilities
(10)Garages, accessory buildings, service bays and similar areas (not vehicle exhibition halls and showrooms)
(11)Crawl spaces at or below grade level
(12)Unfinished areas of basements
(13)Aquariums, bait wells and similar open aquatic vessels: receptacles within 6 ft (new in 2023)
(14)Laundry areas
(15)Bathtubs and shower stalls: receptacles within 6 ft of the outside edge

Notice three differences from dwellings: the non-dwelling rule covers three-phase receptacles up to 100 A, it adds rooftops, locker rooms, buffets and aquariums, and it still says unfinished areas of basements.

210.8(C), (D) and (E): lighting, appliances and service receptacles

210.8(C) Crawl space lighting outlets. GFCI protection is required for lighting outlets not exceeding 120 volts installed in crawl spaces. This is one of the few rules that covers lighting outlets rather than receptacles.

210.8(D) Specific appliances. The branch circuit or outlet supplying these appliances, rated 150 volts or less to ground and 60 amperes or less, single- or three-phase, must be GFCI-protected, whether hardwired or cord-and-plug connected:

Appliances in 2023 NEC 210.8(D)
1. Automotive vacuum machines7. Dishwashers
2. Drinking water coolers and bottle fill stations8. Electric ranges
3. High-pressure spray washing machines9. Wall-mounted ovens
4. Tire inflation machines10. Counter-mounted cooking units
5. Vending machines11. Clothes dryers
6. Sump pumps12. Microwave ovens

Items 8 through 12 are the 2023 additions. A hardwired 40-ampere, 240-volt cooktop now needs a two-pole GFCI breaker.

210.8(E) Equipment requiring servicing. The service receptacles required by NEC 210.63 (the receptacle within 25 ft of HVAC and similar equipment) need GFCI protection.

210.8(F): outdoor outlets, and the HVAC exception

NEC 210.8(F), added in the 2020 NEC, goes beyond receptacles. For dwellings, all outdoor outlets supplied by single-phase branch circuits rated 150 volts or less to ground, 50 amperes or less, need GFCI protection, including outlets in garages with floors at or below grade, accessory buildings and boathouses. Outlets covered by 210.8(A) Exception No. 1 are excluded, and so are lighting outlets other than those covered by 210.8(C) (Exception No. 1). If equipment supplied by one of these outlets is replaced, the outlet must be given GFCI protection.

That rule swept in outdoor air conditioners and heat pumps, and some of them nuisance-tripped GFCI breakers. NFPA responded with Tentative Interim Amendment 23-3, which added Exception No. 2: GFCI protection is not required for listed HVAC equipment, and "this exception shall expire September 1, 2026."

Where that stands now (late 2026):

  • The exception has expired in the 2023 text as published. On paper, a 2023-code outdoor condenser outlet needs GFCI protection again.
  • An extension was proposed and stalled. HVAC manufacturers asked for an extension to September 1, 2028 (proposed TIA Log No. 1924, covered by EC&M). Code-Making Panel 2 did not approve it, and ACCA and AHRI appealed to the NFPA Standards Council. Until NFPA issues a decision, treat the exception as expired unless your jurisdiction says otherwise.
  • The 2026 NEC takes a different route: it raises the 210.8(F) limit to 60 A and adds an exception that permits Class C special-purpose GFCI (SPGFCI) protection for listed HVAC equipment. That only helps where the 2026 edition is adopted.

What changed in 2020 and 2023 (and why it matters on the exam)

EditionChange
2020Dwelling 210.8(A) expanded to 125–250 V receptacles
2020Basements (finished or not) replace "unfinished basements" for dwellings
2020New 210.8(F) outdoor outlets for dwellings
2023Listed Class A GFCI stated in the 210.8 parent text
2023Kitchens: all receptacles, not just countertop
2023New (A)(7): areas with a sink and food/beverage prep provisions
2023210.8(D) appliance list grows to 12 (ranges, ovens, cooktops, dryers, microwaves)
2023Distance measurement no longer excludes paths through windows, and applies to any cord
2023210.8(B) adds buffet serving areas and aquariums and bait wells (15 locations)
2023 (TIA 23-3)210.8(F) Exception No. 2 for listed HVAC, expired September 1, 2026

Your exam is written on a specific edition. If your state is still on the 2020 NEC, the kitchen answer is "countertop receptacles only". Confirm with which NEC edition your state uses before you memorize.

Replacing receptacles: 406.4(D)(3)

When you replace a receptacle at an outlet that the current code requires to be GFCI-protected, NEC 406.4(D)(3) requires the replacement to have GFCI protection. Swapping a worn-out kitchen receptacle in a 1985 house under the 2023 NEC means the new one needs GFCI protection, even though the original installation was legal when built.

How the exam tests 210.8

Worked example

The 6-ft sink measurement

  1. 1

    The question

    A bedroom receptacle sits on the other side of a wall from a bathroom sink, 2 ft from the bowl in a straight line. The shortest path a cord could take, out the bathroom door and back into the bedroom, is 9 ft. Does 210.8(A)(8) require GFCI protection?

  2. 2

    How to measure

    The distance is the shortest path the cord would follow without piercing a wall. You cannot measure straight through the wall.

  3. 3

    Compare

    9 ft is more than 6 ft.

  4. ✓ Answer: No GFCI is required by the sink rule. The bedroom receptacle does need AFCI protection under 210.12.

Exam-style question

Under the 2023 NEC, which receptacles in a dwelling unit kitchen require GFCI protection?

Pick an answer to see the explanation.

Exam-style question

Which of the following appliances requires GFCI protection under 210.8(D), whether it is hardwired or cord-and-plug connected?

Pick an answer to see the explanation.

Exam-style question

A 30-ampere, 125/250-volt dryer receptacle is installed in the laundry area of a single-family dwelling. GFCI protection is:

Pick an answer to see the explanation.

Exam-style question

A GFCI receptacle installed behind a dwelling refrigerator to protect the refrigerator outlet violates which requirement?

Pick an answer to see the explanation.

Find it fast in the code book

Tab 210.8 and highlight the six subsection headings: (A) dwellings, (B) other than dwellings, (C) crawl space lighting, (D) appliances, (E) service receptacles, (F) outdoor outlets. Then box the voltage limits in (A), (B), (D) and (F), because they are all different and exam writers mix them up: 150 V to ground for all four, with 50 A for (B) single-phase and (F), 100 A for (B) three-phase and 60 A for (D).

How you provide the protection is a separate decision: see GFCI breaker vs GFCI outlet. Arc-fault protection overlaps in kitchens and laundry areas, so read AFCI requirements under 210.12 next. All of this sits inside the bigger picture in branch circuits under NEC Article 210. When you can name all twelve dwelling locations without looking, test yourself on a free journeyman practice test.