NEC 210.52 tells you where receptacles must go in a dwelling unit. The core rule is the "6/12 rule": along the floor line of any wall space, no point can be more than 6 feet from a receptacle, so receptacles end up no more than 12 feet apart. Kitchen countertops are tighter, at 24 inches from any point, and the 2023 NEC changed the rules for islands and peninsulas.

This guide goes through 210.52 subsection by subsection, (A) through (I), with diagrams and worked examples. By the end you will be able to lay out the receptacles for any room on a plan, and answer the spacing questions that show up on nearly every journeyman exam.

What 210.52 covers (and what doesn't count)

NEC 210.52 applies to dwelling units. It sets the minimum number and location of 125-volt, 15- and 20-ampere receptacle outlets. You can always install more.

Before you count, know which receptacles do not count toward the requirements. A receptacle does not satisfy 210.52 if it is:

  • part of a luminaire or appliance,
  • located inside cabinets or cupboards,
  • located more than 5½ ft above the floor.

So the receptacle for the garage door opener on the ceiling, or the one inside the microwave cabinet, is extra. It does not cover any wall space.

210.52(A): the 6-foot rule for general wall space

NEC 210.52(A) applies to the kitchen, family room, dining room, living room, parlor, library, den, sunroom, bedroom, recreation room and similar rooms or areas.

The spacing rule: 210.52(A)(1)

Receptacles must be installed so that no point measured horizontally along the floor line of any wall space is more than 6 ft from a receptacle outlet.

Door6 ft max12 ft max6 ft maxDoorMeasured horizontally along the floor line
The 6/12 rule on a wall space between two doors: each receptacle covers 6 ft in both directions along the floor line, so receptacles can be up to 12 ft apart, and the end ones must be within 6 ft of each door. Corners do not end a wall space; doorways do.

The logic is simple: appliance cords are about 6 ft long. If every point on the wall is within 6 ft of a receptacle, a lamp placed anywhere along the wall can reach one without an extension cord.

What counts as wall space: 210.52(A)(2)

A wall space includes:

  1. Any space 2 ft or more in width, including space measured around corners, unbroken along the floor line by doorways and similar openings, fireplaces, stationary appliances (added in the 2023 NEC) and fixed cabinets that do not have countertops or similar work surfaces.
  2. The space occupied by fixed panels in walls, excluding sliding panels.
  3. The space created by fixed room dividers, such as freestanding bar-type counters or railings.

Two consequences come up constantly:

  • Corners don't break the wall. Measure right around them. A receptacle 3 ft from a corner covers 3 ft past it on the next wall.
  • Doorways do. The run starts fresh at each door jamb. A 2-ft piece of wall between two doors is a wall space and needs its own coverage.

Floor and countertop receptacles: (A)(3) and (A)(4)

  • Floor receptacles count toward the wall-space requirement only if they are within 18 in. of the wall (NEC 210.52(A)(3)).
  • Countertop receptacles do not count toward the wall-space requirement (NEC 210.52(A)(4)). The countertop has its own rule in 210.52(C).
Worked example

Minimum receptacles in a bedroom

  1. 1

    The question

    A bedroom is 12 ft × 14 ft. The only opening is a 3-ft door at one corner. There are no fireplaces, closet doors or fixed cabinets on the walls. What is the minimum number of receptacles?

  2. 2

    Find the wall space

    Perimeter = 2 × (12 + 14) = 52 ft. Subtract the door: 52 − 3 = 49 ft. Because the door is at a corner and corners don't break wall space, this is one continuous run from one side of the door to the other.

  3. 3

    Apply the 6/12 rule

    Each receptacle covers up to 12 ft of continuous wall (6 ft each way). 49 ÷ 12 = 4.08.

  4. 4

    Round up

    4 receptacles cover at most 48 ft, which leaves 1 ft uncovered. You need one more.

  5. ✓ Answer: 5 receptacles minimum: the first within 6 ft of one door jamb, then no more than 12 ft apart, the last within 6 ft of the other jamb.

210.52(B): small-appliance receptacles

In the kitchen, pantry, breakfast room, dining room and similar areas, the receptacles covered by 210.52(A), the countertop receptacles and the refrigerator receptacle must be on the 20-ampere small-appliance branch circuits required by NEC 210.11(C)(1). These circuits have no other outlets, and the countertop must be served by at least two of them. The full circuit rules are in our guide to required and dedicated circuits under 210.11.

210.52(C): kitchen countertops, islands and peninsulas

In kitchens, pantries, breakfast rooms, dining rooms and similar areas, every countertop and work surface 12 in. or wider needs receptacle coverage.

Wall countertops: 210.52(C)(1)

Receptacles must be installed so that no point along the wall line is more than 24 in., measured horizontally, from a receptacle outlet in that space.

Sink24 in.48 in. maxCounter space ASpace BReceptacles max 20 in. above the countertop
Wall countertop rule: no point along the wall line more than 24 in. from a receptacle, so receptacles are at most 4 ft apart. A range or sink splits the counter into separate spaces.

So along a wall counter, receptacles can be up to 4 ft apart, and the ones at the ends must be within 24 in. of the end of the counter. Exceptions and details to know:

  • Exception No. 1 to (C)(1): a receptacle is not required directly behind a range, counter-mounted cooking unit or sink in the installation described in Figure 210.52(C)(1).
  • Exception No. 2 (new in 2023): where a required receptacle cannot be installed in the wall areas shown in Figure 210.52(C)(1), it may go as close as practicable to the countertop it serves, but you cannot end up with fewer receptacles than (C)(1) requires.
  • Countertop spaces separated by rangetops, refrigerators or sinks are treated as separate spaces, each with its own coverage.
  • Receptacles made inaccessible by appliances fastened in place, appliance garages, sinks or rangetops do not count as the countertop receptacles.

Islands and peninsulas: the 2023 change, 210.52(C)(2)

This is the biggest 210.52 change in the 2023 NEC. Under the 2020 NEC, an island needed a receptacle based on its area (one for the first 9 ft² and one for each additional 18 ft²). The 2023 NEC removed that requirement:

  • Receptacles are not required to serve an island or peninsula countertop.
  • If you do install one to serve it, it must meet the location rules in (C)(3).
  • If you don't, you must provide provisions at the island or peninsula for future addition of a receptacle outlet.

The reason was safety: receptacles mounted on the side of an island leave cords draped where people walk and where children can grab them and pull an appliance off the counter.

Receptacle location: 210.52(C)(3)

Countertop receptacles (wall, island or peninsula) must be in one or more of these locations:

  1. On or above the countertop or work surface, not more than 20 in. above it.
  2. In the countertop, using receptacle outlet assemblies listed for countertops.
  3. In a work surface, using assemblies listed for work surfaces or listed for countertops.

Gone in 2023: the old permission to mount countertop receptacles up to 12 in. below the counter. A receptacle on the side of the island cabinet no longer serves the countertop.

Worked example

Receptacles on a 10-ft wall counter

  1. 1

    The question

    A straight kitchen wall countertop is 10 ft long with no sink or range in it. How many receptacles are required?

  2. 2

    Coverage per receptacle

    Each receptacle covers 24 in. each way = 48 in. of counter.

  3. 3

    Divide

    10 ft = 120 in. 120 ÷ 48 = 2.5.

  4. 4

    Round up

    2 receptacles cover only 96 in.

  5. ✓ Answer: 3 receptacles, on at least two small-appliance circuits, all GFCI-protected under 210.8(A)(6).

210.52(D): bathrooms

At least one receptacle outlet must be installed within 3 ft of the outside edge of each basin. It goes on a wall or partition adjacent to the basin or basin countertop, on the countertop, or on the side or face of the basin cabinet not more than 12 in. below the top of the basin or countertop. Listed countertop assemblies are permitted.

Two basins can share one receptacle if it falls within 3 ft of each. The receptacle must be on the bathroom circuit required by NEC 210.11(C)(3) and GFCI-protected under NEC 210.8(A)(1).

210.52(E): outdoor receptacles

  • One- and two-family dwellings: at least one receptacle outlet at the front and one at the back of each unit, readily accessible from grade and not more than 6½ ft above grade (NEC 210.52(E)(1)).
  • Multifamily: each unit located at grade level with an individual exterior entrance gets at least one, readily accessible from grade and not more than 6½ ft above grade (NEC 210.52(E)(2)).
  • Balconies, decks and porches within 4 in. horizontally of the dwelling unit need at least one receptacle outlet, not more than 6½ ft above the walking surface (NEC 210.52(E)(3)).

All of them need GFCI protection under 210.8(A)(3).

210.52(F) through (I): laundry, garages, basements, hallways, foyers

LocationSectionRequirement
Laundry210.52(F)At least one receptacle outlet in areas designated for laundry equipment, on the 20 A laundry circuit
Garages210.52(G)(1)At least one receptacle in each vehicle bay, not more than 5½ ft above the floor, in attached garages and detached garages with power
Accessory buildings210.52(G)(2)At least one receptacle in each accessory building with electric power
Basements210.52(G)(3)At least one receptacle in each separate unfinished portion
Hallways210.52(H)Hallways 10 ft or more long (measured along the centerline, not through a doorway): at least one receptacle
Foyers210.52(I)Foyers not part of a hallway, over 60 ft²: a receptacle in each wall space 3 ft or more wide

The 210.52(G) garage, accessory building and basement rules apply to one- and two-family dwellings, and these receptacles are in addition to any receptacle installed for specific equipment (a freezer or a sump pump does not count). Finished basement rooms are habitable rooms, so they follow the 6-ft rule in 210.52(A). The 210.52(G)(3) basement requirement is for the unfinished portions.

6 ft

max distance to a receptacle along a wall

24 in.

max distance along a countertop

6½ ft

max height of required outdoor receptacles

How the exam tests receptacle spacing

Expect three kinds of questions:

  1. Pure numbers. "No point along the floor line shall be more than ___ ft from a receptacle." 6. "Countertop: ___ in." 24. "Hallway: ___ ft or more." 10.
  2. Counting. A room with given dimensions and openings: how many receptacles? Find the continuous runs, divide each by 12, round up.
  3. Edition traps. The island question is the obvious one. If your exam is on the 2023 NEC, "an island receptacle is required" is the wrong answer. If it is on the 2020 NEC, the area-based rule still applies. Check which NEC edition your state uses.

Exam-style question

In a dwelling living room, receptacle outlets shall be installed so that no point measured horizontally along the floor line of any wall space is more than ___ from a receptacle outlet.

Pick an answer to see the explanation.

Exam-style question

Under the 2023 NEC, which statement about a kitchen island countertop in a dwelling is correct?

Pick an answer to see the explanation.

Exam-style question

A dwelling hallway is 12 ft long measured along its centerline. How many receptacle outlets are required in the hallway?

Pick an answer to see the explanation.

Find it fast in the code book

210.52 is long, so tab it and write the subsection letters on the tab: A walls, B small-appliance, C countertops, D bath, E outdoor, F laundry, G garage/basement/accessory, H hallway, I foyer. Mark Figure 210.52(C)(1) as well, because exam writers love the "behind the sink" question. Our code book tabbing guide shows a layout for all of Article 210.

Spacing tells you how many receptacles; it does not tell you how many fit on one circuit. For that, see how many outlets on a 20 amp circuit, and for the protection those receptacles need, read GFCI requirements under 210.8. The pillar guide to branch circuits under NEC Article 210 ties all of Article 210 together. Then put the 6/12 rule to work on a free journeyman practice test.