Dedicated circuits in a house come in two kinds. The first kind is the set of 20-ampere circuits that NEC 210.11(C) requires in every dwelling unit: at least two small-appliance circuits for the kitchen and dining areas, a laundry circuit, a bathroom receptacle circuit and, since the 2020 NEC, a garage receptacle circuit. The second kind is the individual branch circuit that a single appliance needs, such as an EV charger, a furnace or a water heater.

This guide covers both, rule by rule, with the exceptions that exam writers like to test. By the end you will be able to list the minimum required circuits for any dwelling, spot an illegal load on a small-appliance circuit, and find every one of these rules in your code book in seconds.

What "dedicated circuit" means in the NEC

The NEC never uses the phrase "dedicated circuit". It uses two different ideas, and mixing them up is a classic exam trap.

  • An individual branch circuit (Article 100) supplies only one piece of utilization equipment. A 240-volt circuit feeding one water heater is an individual branch circuit.
  • A required branch circuit under NEC 210.11(C) is limited by area and purpose, not by the number of outlets. The two kitchen small-appliance circuits can each feed several countertop receptacles. What they cannot feed is anything else.

So when a homeowner says "the kitchen needs dedicated circuits", the code answer is: the kitchen needs at least two 20-ampere small-appliance branch circuits that serve only receptacles in the kitchen and dining areas, plus whatever individual circuits the appliances need.

The four required circuits in every dwelling (210.11(C))

Panelboard20 A20 A20 A20 A20 ASmall-appliance #1Kitchen, dining, pantry receptaclesSmall-appliance #2Countertop needs both (210.52(B)(3))LaundryLaundry receptacles onlyBathroom (120 V)Bathroom receptaclesGarage (120 V)Garage receptacles (since 2020)Each: 12 AWG Cu minimum
Minimum branch circuits required by NEC 210.11(C) in a dwelling unit with a garage. General lighting circuits and individual appliance circuits come on top of these.

1. Small-appliance branch circuits: at least two, 20 A

NEC 210.11(C)(1) requires two or more 20-ampere small-appliance branch circuits to supply the receptacle outlets covered by NEC 210.52(B). Those are the receptacles in the kitchen, pantry, breakfast room, dining room and similar areas: wall receptacles, countertop receptacles and the refrigerator receptacle.

Three details matter on the exam:

  • No other outlets. Under NEC 210.52(B)(2), these circuits cannot supply lighting outlets or receptacles in other rooms. The exceptions are a receptacle installed solely for an electric clock and receptacles for the supplemental equipment and lighting on gas-fired ranges, ovens and counter-mounted cooking units.
  • The countertop needs both. NEC 210.52(B)(3) says the kitchen countertop receptacles must be supplied by not fewer than two small-appliance circuits. Putting every countertop receptacle on one circuit and the dining room on the other is a violation.
  • One kitchen per circuit. No small-appliance branch circuit may serve more than one kitchen. A house with a second kitchen needs its own pair.

The refrigerator has a choice. It can sit on a small-appliance circuit, or, under the exception to NEC 210.52(B)(1), it can be supplied by an individual branch circuit rated 15 amperes or greater.

2. Laundry branch circuit: at least one, 20 A

NEC 210.11(C)(2) requires at least one 20-ampere branch circuit for the laundry receptacle outlets required by NEC 210.52(F). This circuit shall have no other outlets. A light in the laundry room cannot be on it, and neither can a bedroom receptacle on the other side of the wall.

An electric dryer is not served by this circuit. It is a 240-volt appliance on its own individual branch circuit. The 20-ampere laundry circuit is for the washer, a gas dryer's 120-volt controls, an iron and similar loads.

3. Bathroom branch circuit: at least one 120 V, 20 A

NEC 210.11(C)(3) requires at least one 120-volt, 20-ampere branch circuit to supply the bathroom receptacle outlets required by NEC 210.52(D). This circuit has no other outlets.

There are two legal ways to wire it, and the exam likes both:

LayoutWhat the 20 A circuit may supply
One circuit for several bathroomsReceptacles only, in any number of bathrooms
One circuit for a single bathroomReceptacles plus other equipment in that same bathroom (lights, exhaust fan), within the 210.23(B)(1) and (B)(2) load limits

4. Garage branch circuit: at least one 120 V, 20 A

This is the newest of the four. The 2020 NEC added NEC 210.11(C)(4), and the 2023 NEC reworded it. In the 2023 text, at least one 120-volt, 20-ampere branch circuit must supply receptacle outlets, including those required by 210.52(G)(1), in attached garages and in detached garages with electric power. This circuit shall have no other outlets.

The 2023 edition also clarified that:

  • The 20-ampere circuit may serve other receptacles in the garage, not only the required one per vehicle bay.
  • Additional circuits rated 15 amperes or more may serve garage receptacles other than the required ones.
  • Exception No. 1: the garage circuit may also supply outdoor receptacle outlets.
  • Exception No. 2: in a single vehicle bay garage, the 20-ampere circuit may also supply other equipment outlets in that garage (lighting, a door opener) within the 210.23 load limits.

The receptacles it supplies are set by NEC 210.52(G)(1): at least one receptacle outlet in each vehicle bay, not more than 5½ ft above the floor.

→Where the receptacles on these circuits must goReceptacle Spacing and Placement: NEC 210.52 for Dwellings

Quick reference: required circuits at a glance

CircuitSectionRatingMay also supply
Small-appliance (2 min.)210.11(C)(1), 210.52(B)20 AKitchen, pantry, breakfast, dining receptacles only (clock and gas-range exceptions)
Laundry (1 min.)210.11(C)(2), 210.52(F)20 ANothing else
Bathroom (1 min.)210.11(C)(3), 210.52(D)120 V, 20 AOther equipment in the same bathroom, if it serves only one bathroom
Garage (1 min.)210.11(C)(4), 210.52(G)(1)120 V, 20 AOutdoor receptacles; other equipment in a single-bay garage

Every one of these is a 20-ampere circuit, which means 12 AWG copper minimum under the small-conductor rule in NEC 240.4(D). If you want the full story on why, see 12 vs 14 gauge wire and the small-conductor rule.

2

minimum small-appliance circuits (20 A)

1,500 VA

load per small-appliance or laundry circuit (220.52)

5½ ft

max height of the garage bay receptacle

How these circuits show up in the load calculation

The required circuits are also line items in the dwelling load calculation. Under NEC 220.52(A), each 2-wire small-appliance branch circuit is figured at 1,500 VA, and under NEC 220.52(B) the laundry circuit adds another 1,500 VA. Those loads are added to the general lighting load before the demand factors are applied.

The bathroom and garage circuits do not get their own 1,500 VA line. Their receptacles are part of the general lighting and receptacle load figured per square foot.

Worked example

Minimum circuits for a 2,000 ft² house

  1. 1

    The question

    A 2,000 ft² single-family dwelling has one kitchen, a dining room, two bathrooms, a laundry area and an attached two-car garage. What is the minimum number of 120-volt branch circuits for general lighting and the required 210.11(C) circuits, using 15-ampere general lighting circuits?

  2. 2

    General lighting load

    NEC 220.41 sets the dwelling unit load at 3 VA per ft². 2,000 × 3 = 6,000 VA. 6,000 VA ÷ 120 V = 50 A.

  3. 3

    Number of 15 A lighting circuits

    50 A ÷ 15 A = 3.33. You cannot install a third of a circuit, so round up to 4 general lighting circuits.

  4. 4

    Required 210.11(C) circuits

    Small-appliance: 2. Laundry: 1. Bathroom: 1 (one 20 A circuit may serve the receptacles in both bathrooms). Garage: 1. Total = 5.

  5. ✓ Answer: 4 general lighting circuits + 5 required 20 A circuits = 9 circuits minimum. Real houses get more, but that is the code floor.

Appliances that need an individual (dedicated) circuit

Beyond 210.11(C), several appliances need their own circuit because a specific code section or the manufacturer says so. NEC 110.3(B) makes listed equipment's installation instructions enforceable, and that is where most "dedicated circuit" requirements actually come from.

EquipmentWhy it gets its own circuit
Central heating equipment (furnace, boiler)NEC 422.12 requires an individual branch circuit; auxiliary equipment like a pump or humidifier may share it
EV charging outletNEC 625.40: each outlet for EV charging gets an individual branch circuit
Storage water heaterSized under NEC 422.13; typically its own 240 V circuit per the nameplate
Air conditioner, heat pumpSized from the nameplate MCA and MOCP under Article 440
Electric range, oven, cooktop, dryer240 V individual circuits sized from the nameplate and Article 220
Dishwasher, disposal, built-in microwaveUsually per the manufacturer's instructions (110.3(B)); cannot be on small-appliance circuits
RefrigeratorOptional: small-appliance circuit or individual 15 A or larger circuit

For the HVAC side of that table, our guide to MCA vs MOCP on HVAC nameplates walks through the sizing. For ranges, see Table 220.55 cooking appliance demand.

Common mistakes on the job and on the exam

Lighting on a small-appliance circuit. The pendant over the island, the under-cabinet lights, the range hood light: none of them may be on the 20-ampere small-appliance circuits.

One small-appliance circuit for the whole countertop. NEC 210.52(B)(3) requires at least two circuits at the countertop. Alternate them along the counter.

A bathroom circuit that wanders. A shared bathroom receptacle circuit that also picks up the hallway receptacle is a violation.

Garage lights on the garage receptacle circuit. Unless the garage has a single vehicle bay, the 20-ampere garage circuit has no other outlets.

Forgetting the 15 A option for the fridge. "The refrigerator must be on a 20-ampere circuit" is false. An individual 15-ampere circuit is allowed.

Calling 210.11(C) circuits individual branch circuits. They are not. That matters for receptacle ratings: on a circuit with two or more receptacles, 15-ampere receptacles are allowed on a 20-ampere circuit. Read why in can you put a 15 amp receptacle on a 20 amp circuit.

GFCI and AFCI on the required circuits

The required circuits carry protection requirements too. Under the 2023 NEC, NEC 210.8(A) requires GFCI protection for all 125- through 250-volt receptacles in kitchens (no longer just the countertop), bathrooms, garages and laundry areas. NEC 210.12(B) requires AFCI protection for the 120-volt circuits supplying kitchens, dining rooms and laundry areas, among others.

So a typical 2023-compliant kitchen small-appliance circuit needs both GFCI and AFCI protection, which is why dual-function breakers are common there. The full location lists are in our guides to GFCI requirements under 210.8 and AFCI requirements under 210.12.

→Choosing how to protect these circuitsGFCI Breaker vs GFCI Outlet: Which One to Use

Exam-style questions

Exam-style question

What is the minimum number of 20-ampere small-appliance branch circuits required for the kitchen and dining room of a dwelling unit?

Pick an answer to see the explanation.

Exam-style question

A 120-volt, 20-ampere branch circuit supplies the receptacle outlets in two bathrooms of a dwelling. Which of the following may also be connected to this circuit?

Pick an answer to see the explanation.

Exam-style question

In a dwelling with an attached two-car garage, the required 120-volt, 20-ampere garage branch circuit may also supply:

Pick an answer to see the explanation.

How to find these rules fast in the code book

All four required circuits are in one place: 210.11(C)(1) through (C)(4). Each one points to a receptacle rule in 210.52: (B) for small-appliance, (F) for laundry, (D) for bathrooms and (G)(1) for garages. Tab 210.11 and 210.52 next to each other, and write those four pairings in the margin.

The 1,500 VA values are in 220.52(A) and (B), which you will use in every dwelling service calculation. Our tabbing guide shows how to mark Article 210 so these jump out.

Required circuits are one piece of Article 210. For the full picture of ratings, loading limits and receptacle rules, read the pillar guide to branch circuits under NEC Article 210, then see how the 1,500 VA circuits feed into a dwelling load calculation. When you are ready to test yourself under time pressure, take a free journeyman practice test.