A wire ampacity chart tells you how many amperes a conductor can carry continuously without overheating its insulation, and in the US the chart everyone uses is NEC Table 310.16. It lists copper and aluminum conductors from 14 AWG through 2000 kcmil in three temperature columns, 60°C, 75°C and 90°C, based on no more than three current-carrying conductors in a raceway or cable at a 30°C (86°F) ambient.

Below you will find the chart itself for the sizes electricians actually use, then the rules that decide which number you are allowed to use. By the end you will be able to size a conductor from Table 310.16 the way the journeyman exam expects, and you will know where to go next for every related topic, from voltage drop to service conductor sizing.

The NEC wire ampacity chart (Table 310.16)

These values are from the 2023 NEC, Table 310.16, for every size from 14 AWG through 2000 kcmil. Amperes, not more than three current-carrying conductors, 30°C (86°F) ambient.

Size (AWG/kcmil)Cu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°C
14*152025———
12*202530152025
10*303540253035
8405055354045
6556575405055
4708595556575
385100115657585
2951151307590100
111013014585100115
1/0125150170100120135
2/0145175195115135150
3/0165200225130155175
4/0195230260150180205
250215255290170205230
300240285320195230260
350260310350210250280
400280335380225270305
500320380430260310350
600350420475285340385
700385460520315375425
750400475535320385435
800410490555330395445
900435520585355425480
1000455545615375445500
1250495590665405485545
1500525625705435520585
1750545650735455545615
2000555665750470560630

*Overcurrent protection for these sizes is limited by NEC 240.4(D). See the section on small conductors below. The aluminum columns also apply to copper-clad aluminum. The code book table also lists 18 and 16 AWG copper in the 90°C column (14 A and 18 A); those sizes are for control and fixture wiring, not branch circuits.

Notice how the gain per size shrinks as conductors get bigger: going from 1500 to 1750 kcmil copper adds only 25 A at 75°C, and 1750 to 2000 kcmil adds just 15 A. A big conductor has less surface area per circular mil to shed heat, which is one reason large services and feeders are usually built from parallel sets of conductors instead of one huge conductor per phase.

How to read Table 310.16 in four moves

Every Table 310.16 lookup follows the same path:

  1. Pick the metal. Copper is on the left half, aluminum and copper-clad aluminum on the right half.
  2. Find the size in the left column (AWG up to 4/0, then kcmil).
  3. Pick the temperature column that matches the insulation type, and then check whether the terminations or the wiring method force you down to a lower column.
  4. Apply the limits: correction factors, adjustment factors, 240.4(D) for small conductors, and any article-specific rule (NM cable, services, motors).
Cu size60°C75°C90°C14 AWG15202512 AWG20253010 AWG3035408 AWG405055NM and UF cableunmarked terminals100 A or less75°C terminalsmost THHN in conduitover 100 ADerating start90°C insulationnot for terminals
Same conductor, three numbers. The column you may use depends on the insulation, the terminations and the wiring method.

What the 60°C, 75°C and 90°C columns mean

Each column is tied to the temperature rating of the conductor insulation. The table header lists the insulation types that belong in each column. The common ones:

ColumnTypical insulation typesWhere you see them
60°C (140°F)TW, UFUF cable, older installations; NM cable is held to this column by 334.80
75°C (167°F)THW, THWN, XHHW, RHW, USEWet-location building wire, service-entrance cable
90°C (194°F)THHN, THWN-2, XHHW-2, RHW-2, USE-2Most building wire sold today, often dual-rated THHN/THWN-2

The insulation type tells you the maximum column you could use. Many conductors carry two ratings: THHN/THWN-2 is 90°C in dry and wet locations, while plain THWN is 75°C in wet locations. If you are not sure what the letters mean, see THHN vs THWN vs THWN-2, which walks through Table 310.4.

The conditions behind every number in the chart

Table 310.16 values are only valid under the conditions stated in its title and in NEC 310.16:

  • Not more than three current-carrying conductors in the raceway, cable or earth. More than three means you apply adjustment factors from Table 310.15(C)(1).
  • Ambient temperature of 30°C (86°F). Any other ambient means you apply correction factors from Table 310.15(B)(1)(1).
  • In raceway, in cable, or directly buried in earth. Single conductors in free air use Table 310.17, which has higher values.
  • Voltage rating up to and including 2000 volts.

Change any of these and the table number is no longer your ampacity. That is the whole reason the derating tables exist.

Table 310.16 vs the other ampacity tables

Table 310.16 is the one you will use for nearly every building-wire question, but Article 310 has neighbors. Know which one a question is pointing at:

TableUse it forAmbient basis
310.16Up to three current-carrying conductors in raceway, cable or directly buried30°C (86°F)
310.17Single insulated conductors in free air30°C (86°F)
310.12120/240 V dwelling services and main feeders (the 83% rule)Built from 310.16
310.18 to 310.21High-temperature insulation, messenger-supported and bare overhead conductors40°C (104°F)

If a question says "in free air" or "single conductors," it is a 310.17 question and the numbers are higher. If it says "dwelling service," check whether 310.12 applies before you touch 310.16.

The asterisk: small-conductor limits in 240.4(D)

The asterisks on 14, 12 and 10 AWG send you to NEC 240.4(D). Unless a specific exception applies, the overcurrent protection for these conductors cannot exceed:

ConductorMax. overcurrent protection2023 NEC item
14 AWG copper15 A240.4(D)(4)
12 AWG copper20 A240.4(D)(6)
10 AWG copper30 A240.4(D)(8)
12 AWG aluminum / copper-clad aluminum15 A240.4(D)(5)
10 AWG aluminum / copper-clad aluminum25 A240.4(D)(7)

Items (1) through (3) cover 18 AWG copper (7 A), 16 AWG copper (10 A) and 14 AWG copper-clad aluminum (10 A), each only under specific conditions. The item numbers shifted in the 2023 edition when 14 AWG copper-clad aluminum was added as (3), so older study guides that cite "240.4(D)(5) for 12 AWG copper" are quoting the 2020 numbering.

So 12 AWG copper may be rated 25 A at 75°C or 30 A at 90°C, but on a general-purpose branch circuit it is still protected at 20 A. The higher table values matter only for derating: they give you headroom before the corrected ampacity falls below the breaker size.

The exceptions are listed in NEC 240.4(E) and NEC 240.4(G): tap conductors, motor circuits under Article 430, air-conditioning and refrigeration equipment under Article 440, and a few others. That is how a 10 AWG conductor can legally land on a 40-ampere HACR breaker when an air conditioner nameplate calls for it. The details for each size are in 10 gauge wire amps and 12 vs 14 gauge wire.

Terminations: why you usually can't use the 90°C column

The table is about the conductor. NEC 110.14(C) is about where the conductor lands. Terminals on breakers, panelboards and equipment have their own temperature ratings, and the conductor ampacity you use must not exceed what the termination can handle.

  • Circuits rated 100 A or less, or terminals marked for 14 through 1 AWG (NEC 110.14(C)(1)(a)): use the 60°C column, unless the equipment is listed and identified for higher-rated conductors (most modern breakers and panelboards are marked 60/75°C or 75°C).
  • Circuits rated over 100 A, or terminals marked for conductors larger than 1 AWG (NEC 110.14(C)(1)(b)): use the 75°C column, unless the equipment is listed and identified for a higher temperature.

That is why the bold numbers in practice are almost always in the 75°C column. The full rule, its sub-items and worked examples are in termination temperature ratings under NEC 110.14(C).

→The rule that picks your columnTermination Temperature Ratings: NEC 110.14(C) Explained

NM cable (Romex) and the 60°C column

Type NM cable conductors are 90°C rated, but NEC 334.80 says the ampacity of NM cable is that of 60°C conductors. The 90°C rating may be used for derating, as long as the final ampacity does not exceed the 60°C value. UF cable is also held to 60°C by NEC 340.80.

NM cableAmpacity (60°C)Typical breaker
14/2, 14/315 A15 A
12/2, 12/320 A20 A
10/2, 10/330 A30 A
8/2, 8/340 A40 A
6/2, 6/355 A50 A or 60 A*

*60 A is permitted for 6 AWG NM only through the next-size-up rule of NEC 240.4(B), where its conditions are met (not a multioutlet branch circuit for cord-and-plug loads, and the ampacity does not match a standard rating). That is exactly the kind of answer exam writers like.

This is the most common reason the "right" answer for a residential question differs from the one for THHN in conduit. 8 AWG wire ampacity: 40, 50 or 55 amps works through the difference in detail.

Correction and adjustment factors (derating)

When the conditions of the table change, you multiply the table value by one or two factors:

Derated ampacity

Ampacity = Table 310.16 value × correction factor × adjustment factor

  • Correction factor for ambient temperature other than 30°C: Table 310.15(B)(1)(1). Hotter than 86°F lowers ampacity; cooler raises it.
  • Adjustment factor for more than three current-carrying conductors in a raceway or cable: Table 310.15(C)(1). For example, 4–6 conductors = 80%, 7–9 = 70%, 10–20 = 50%.
  • Rooftop raceways and cables exposed to sunlight within 7/8 inch of the roof get an extra temperature adder under NEC 310.15(B)(2).

Start from the column that matches the insulation (usually 90°C for THHN), derate, then compare the result to the termination column. Use the smaller number. The step-by-step method, the full correction table and the neutral-counting rules are in ampacity correction and adjustment factors.

Worked example

Derating 10 AWG THHN

  1. 1

    The question

    Six current-carrying 10 AWG THHN copper conductors are in one EMT raceway in a 40°C (104°F) ambient. Terminations are rated 75°C. What is the ampacity?

  2. 2

    Start at 90°C

    10 AWG copper, 90°C column = 40 A

  3. 3

    Correct and adjust

    Correction at 40°C, 90°C column = 0.91. Adjustment for 6 conductors = 0.80. 40 × 0.91 × 0.80 = 29.12 A

  4. 4

    Check the termination column

    75°C column for 10 AWG = 35 A. 29.12 A is lower, so it controls.

  5. ✓ Answer: 29.12 A. The conductors may not serve a load above 29.12 A, and 240.4(D) still limits the overcurrent device to 30 A.

Copper vs aluminum on the chart

Aluminum's right-hand columns run roughly one to two sizes behind copper. For the same 75°C ampacity of about 100 A, you need 3 AWG copper or 1 AWG aluminum. For 150 A, 1/0 copper or 3/0 aluminum (3/0 Al is 155 A at 75°C).

Aluminum is lighter and much cheaper per ampere, which is why it dominates service-entrance and large feeder conductors. It needs terminals listed for aluminum (marked AL/CU) and correct torque. The trade-offs, including the history of small aluminum branch-circuit wiring, are in aluminum vs copper wire.

3 AWG Cu

100 A at 75°C

1 AWG Al

100 A at 75°C

3/0 Al

155 A at 75°C

Services, feeders and other special cases

Table 310.16 is the default, but several rules modify it:

  • Dwelling services and main feeders: NEC 310.12 allows conductors sized at 83% of the service or feeder rating for 120/240-volt single-phase dwelling services and the feeders that carry the whole dwelling load. Table 310.12 gives the sizes, for example 2/0 copper or 4/0 aluminum for 200 A. See wire size for a 200 amp service and wire size for a 400 amp service.
  • Subpanels and feeders that are not the main dwelling feeder use Table 310.16 directly. See what size wire for a 60 amp subpanel, 125 amp wire size and wire size for a 100 amp service or subpanel.
  • Two ampacities on one run: if part of a circuit runs through a hotter area, NEC 310.15(A) requires the lower ampacity, but an exception lets you use the higher one if the lower-ampacity portion is not longer than 10 feet or 10% of the circuit length, whichever is less.
  • Continuous loads: branch circuits and feeders supplying continuous loads (3 hours or more) must have an ampacity of at least 125% of the continuous load before derating, per NEC 210.19 and NEC 215.2.

Step-by-step: sizing a conductor from the chart

Here is the method that works on every exam question:

  1. Find the load (or the overcurrent device rating the conductor must match).
  2. Apply 125% for continuous loads, if applicable.
  3. Choose the column using 110.14(C) and the wiring method (NM = 60°C).
  4. If there is derating, start from the insulation column and work it out.
  5. Pick the smallest conductor whose final ampacity is at least what you need.
  6. Check 240.4(D) for small conductors and 240.4(B) if you are rounding the breaker up.
  7. Check voltage drop if the run is long.
Worked example

Sizing for a 40 A continuous load

  1. 1

    The question

    A 40-ampere continuous load is supplied by THHN copper conductors in EMT with no derating. All terminations are rated 75°C. What is the minimum conductor size?

  2. 2

    Continuous load

    40 × 1.25 = 50 A

  3. 3

    75°C column

    10 AWG = 35 A (too small). 8 AWG = 50 A.

  4. ✓ Answer: 8 AWG copper, protected by a 50-ampere breaker.
Worked example

Same load, NM cable

  1. 1

    The question

    The same 40-ampere continuous load is wired with NM cable. What size?

  2. 2

    60°C column (334.80)

    Need 50 A. 8 AWG NM = 40 A (too small). 6 AWG NM = 55 A.

  3. ✓ Answer: 6 AWG NM cable. The cable type alone changed the answer by one size.
Worked example

A 150 A feeder in aluminum

  1. 1

    The question

    A 150-ampere feeder (not a dwelling main feeder) uses XHHW-2 aluminum conductors with 75°C terminations. What is the minimum size?

  2. 2

    Column

    Over 100 A: 75°C column, per 110.14(C)(1)(b).

  3. 3

    Look up

    2/0 Al = 135 A (too small). 3/0 Al = 155 A.

  4. ✓ Answer: 3/0 aluminum.

Common mistakes with the ampacity chart

Using the 90°C column for the final answer. It is for derating. The termination column almost always caps you lower.

Forgetting 240.4(D). "10 AWG is good for 40 amps" is true only in the 90°C column. As a branch circuit, it is 30 A.

Using the THHN answer for NM cable. NM is 60°C. 8 AWG NM is 40 A, not 50 A.

Applying derating to the 60°C or 75°C value when the insulation is 90°C. You lose capacity you were entitled to. Start at the insulation rating.

Counting conductors wrong. Equipment grounding conductors never count as current-carrying. Neutrals sometimes do. See the neutral rules in ampacity correction and adjustment factors.

Ignoring voltage drop. Ampacity keeps the wire from overheating. It says nothing about the voltage at the far end of a 200-foot run. Use the voltage drop formula and the NEC 3% and 5% recommendations.

Practice: Table 310.16 questions

Exam-style question

What is the allowable ampacity of 4 AWG THWN copper conductors in a raceway with three current-carrying conductors at 30°C, connected to terminals rated 75°C?

Pick an answer to see the explanation.

Exam-style question

A 12 AWG THHN copper conductor has a 90°C ampacity of 30 A. Unless an exception applies, what is the maximum rating of the overcurrent device protecting it?

Pick an answer to see the explanation.

Exam-style question

What is the ampacity of 8/2 with ground Type NM cable?

Pick an answer to see the explanation.

Exam-style question

Table 310.16 ampacities are based on an ambient temperature of:

Pick an answer to see the explanation.

How to find Table 310.16 fast in the code book

Table 310.16 sits in Article 310, Part II, a few pages after the correction and adjustment tables. On exam day you want to open the book to it in one move, so tab it and tab Table 310.15(B)(1)(1) and Table 310.15(C)(1) right next to it. Add tabs for 110.14(C) and 240.4(D), because almost every ampacity question touches one of them. A complete tab plan is in how to tab your NEC code book.

A quick memory trick for the copper 75°C column from 14 to 1 AWG: 20, 25, 35, 50, 65, 85, 100, 115, 130. Many electricians also remember that from 3 AWG to 3/0, the 75°C copper value goes up roughly 15 to 25 amps per step.

Every guide in the conductors and ampacity series

This chart is the hub for every conductor topic on the exam. Go deeper with each one:

The official text is published by NFPA as NFPA 70, the National Electrical Code. Check which edition your state's exam uses with which NEC edition does my state use, because table numbering in Article 310 changed in the 2020 edition.

Ampacity questions are on every journeyman exam, and most of them combine Table 310.16 with one more rule. Once you can run the seven-step method without looking, test yourself with the free journeyman practice test or the timed practice tests.