NEC 110.14 covers electrical connections, and its most tested part, 110.14(C), limits conductor ampacity to the temperature rating of the terminals it lands on. That is why a 90°C THHN conductor is almost always sized from the 60°C or 75°C column of Table 310.16: circuits of 100 amps or less start in the 60°C column, circuits over 100 amps use the 75°C column, unless the equipment is listed and marked for something higher.

This guide breaks down every part of 110.14(C), shows how it interacts with derating, and works through the exam questions that are built on it. You will finish able to pick the correct ampacity column in seconds.

What NEC 110.14 covers

Section 110.14 is titled Electrical Connections. It has four parts you should know:

PartTopicWhat it requires
NEC 110.14(A)TerminalsA good connection without damaging the conductor; terminals for more than one conductor and terminals for aluminum must be identified for that use
NEC 110.14(B)SplicesSplicing devices identified for the use, or brazing, welding or soldering; splices and free ends insulated equivalent to the conductor
NEC 110.14(C)Temperature limitationsConductor ampacity coordinated with the lowest temperature rating of any termination, conductor or device
NEC 110.14(D)Terminal connection torqueTighten to the torque marked on the equipment or in the instructions, using an approved means (for example, a torque tool)

The rest of this guide focuses on 110.14(C), because it changes the answer to almost every conductor-sizing question.

Why terminal temperature matters

Table 310.16 tells you how much current a conductor can carry without overheating its insulation. It says nothing about the breaker or lug at each end.

Equipment is evaluated with conductors sized from a particular ampacity column. The conductor acts as a heat sink, drawing heat away from the terminal. If you use a smaller conductor sized from a hotter column, the terminal runs hotter than the equipment was evaluated for. Over time that degrades the connection, and failed connections are a classic source of heat damage in panels.

That second sentence is the code's permission to derate from the 90°C column. The first sentence is the cap. Every 110.14(C) question is a combination of the two.

In plain words: the weakest link in temperature sets the column.

The 100-amp dividing line: 110.14(C)(1)

Circuit 100 A or less,or 14 through 1 AWG?yesnoEquipment listed andidentified for 75°C?Equipment listed forhigher than 75°C?noyesnoyes60°C75°C75°CListedratingConductor insulation must be rated at least as high as the column used.
How 110.14(C)(1) picks the Table 310.16 column for equipment terminations.

110.14(C)(1)(a): 100 A or less, or 14 through 1 AWG

Termination provisions of equipment for circuits rated 100 amperes or less, or marked for conductors 14 AWG through 1 AWG, may be used only with one of the following:

  1. Conductors rated 60°C.
  2. Conductors with higher temperature ratings, as long as the ampacity is determined from the 60°C column.
  3. Conductors with higher temperature ratings at their higher ampacity, if the equipment is listed and identified for use with such conductors (for example, marked 75°C or 60/75°C).
  4. For motors marked with design letters B, C or D, conductors rated 75°C or higher, with the ampacity not exceeding the 75°C value.

Item 3 is the one that matters most in practice. Most modern breakers, panelboards and much of the equipment you connect to are marked 60/75°C or 75°C, which lets a THHN conductor be used at its 75°C ampacity.

110.14(C)(1)(b): over 100 A, or larger than 1 AWG

Termination provisions of equipment for circuits rated over 100 amperes, or marked for conductors larger than 1 AWG, may be used only with:

  1. Conductors rated 75°C.
  2. Conductors with higher temperature ratings, with the ampacity not exceeding the 75°C value, or not exceeding the ampacity at the higher rating if the equipment is listed and identified for that higher rating.

Where 310.12 fits in

The opening paragraph of 110.14(C)(1) says that, unless the equipment is listed and marked otherwise, the ampacities used to judge termination provisions are based on Table 310.16 as appropriately modified by 310.12. That is the link that lets a dwelling service or main feeder use the 83% rule of 310.12 without a separate termination check. For the details, see wire size for a 200 amp service.

110.14(C)(2): separately installed pressure connectors

Separately installed pressure connectors, such as split bolts, insulated multi-tap connectors and lugs added in the field, must be used with conductors at ampacities not exceeding the listed and identified temperature rating of the connector. Check the connector marking: some are rated 90°C, which can help in splices where derated 90°C ampacity is needed.

Worked examples

Worked example

100 A feeder: marked vs unmarked terminals

  1. 1

    The question

    A 100-ampere feeder uses THHN copper conductors in conduit with no derating. What is the minimum size (a) if all terminations are listed and marked 75°C, and (b) if any termination is unmarked?

  2. 2

    (a) 75°C terminations

    110.14(C)(1)(a)(3) allows the 75°C column. 3 AWG copper at 75°C = 100 A.

  3. 3

    (b) Unmarked termination

    Use the 60°C column. 3 AWG = 85 A, 2 AWG = 95 A, 1 AWG = 110 A.

  4. ✓ Answer: (a) 3 AWG copper. (b) 1 AWG copper. One unmarked lug costs you two sizes.
Worked example

200 A feeder over 100 A

  1. 1

    The question

    A 200-ampere feeder (not a dwelling service or main feeder) uses XHHW-2 copper. What is the minimum size?

  2. 2

    Pick the column

    Over 100 A: 110.14(C)(1)(b), 75°C column, even though XHHW-2 is rated 90°C.

  3. 3

    Look up

    2/0 = 175 A (too small). 3/0 = 200 A.

  4. ✓ Answer: 3/0 copper. Using the 90°C column (2/0 = 195 A, 3/0 = 225 A) would be a violation at the terminals.
Worked example

Derating with a terminal check

  1. 1

    The question

    Four current-carrying 8 AWG THHN copper conductors are in one raceway at 30°C. Terminations are 75°C. What is the ampacity? What if there were only three conductors?

  2. 2

    Four conductors

    Start at 90°C: 55 A. Adjustment for 4–6 conductors: 80%. 55 × 0.80 = 44 A. Terminal limit (75°C) = 50 A. 44 A is lower, so 44 A.

  3. 3

    Three conductors

    No adjustment: 55 A. But the terminal limit is 50 A. The lower number controls: 50 A.

  4. ✓ Answer: 44 A with four conductors; 50 A with three. The final ampacity is always the smaller of the derated value and the termination column value.

This two-step check, derate from the insulation column, then compare with the termination column, is the heart of ampacity correction and adjustment factors.

The NM cable twist

Type NM cable has 90°C conductors, but NEC 334.80 limits its ampacity to the 60°C value regardless of the terminal ratings. So even with 75°C breakers, 8 AWG NM is 40 A, not 50 A. 110.14(C) and 334.80 are separate limits and the lower one wins. 8 AWG wire ampacity walks through that case.

Common mistakes with 110.14(C)

Using the 90°C column as the final answer. It is a derating starting point. Unless the equipment is listed and identified for 90°C terminations, you cannot use those values at the terminals.

Checking only one end. The panel breaker may be 75°C, but the disconnect or equipment at the other end may be 60°C. The lowest one sets the column.

Forgetting the conductor itself. A 60°C conductor (TW, UF) can never be used at its 75°C ampacity, because it has none. The insulation rating must be at least as high as the column you use.

Mixing up the 100 A threshold. The test is the circuit rating (100 A or less) or the conductor size range marked on the terminal (14 through 1 AWG). A 100 A circuit is still under (C)(1)(a).

Quick reference: which column?

SituationColumn for final ampacity
15–100 A circuit, terminals unmarked60°C
15–100 A circuit, terminals marked 75°C or 60/75°C at both ends75°C (conductor must be 75°C or 90°C rated)
Over 100 A circuit75°C
Any NM or UF cable60°C (334.80, 340.80)
Motor with design letter B, C or D, 75°C or higher conductor75°C
Derating a 90°C conductorStart at 90°C, then cap at the termination column
Separately installed pressure connectorConnector's listed rating

Minimum conductor size by breaker and termination rating

This is the table you build in your head on every sizing question. It shows the smallest conductor whose Table 310.16 ampacity is at least the breaker rating, with no derating, and with the 240.4(D) small-conductor limits applied (that is why 30 A aluminum needs 8 AWG, not 10 AWG).

Circuit ratingCu, 60°C terminalsCu, 75°C terminalsAl, 60°C terminalsAl, 75°C terminals
15 A14 AWG14 AWG12 AWG12 AWG
20 A12 AWG12 AWG10 AWG10 AWG
30 A10 AWG10 AWG8 AWG8 AWG
40 A8 AWG8 AWG6 AWG8 AWG
50 A6 AWG8 AWG4 AWG6 AWG
60 A4 AWG6 AWG3 AWG4 AWG
70 A4 AWG4 AWG2 AWG3 AWG
80 A3 AWG4 AWG1 AWG2 AWG
90 A2 AWG3 AWG1/02 AWG
100 A1 AWG3 AWG1/01 AWG

Read across the 50 A and 60 A rows: the termination rating alone changes the answer by one or two sizes. Where the conductor ampacity falls just short of a standard breaker size, NEC 240.4(B) may allow the next size up for the breaker, but the conductor must still carry the calculated load. Over 100 A, the 75°C column applies anyway, so the table stops here; 125 amp wire size picks up from there.

How the exam words 110.14(C) questions

Termination questions are rarely labeled as such. Watch for these patterns:

  • "THHN" or "XHHW-2" with no mention of terminals. The 90°C insulation is bait. For a circuit of 100 A or less, a strict reading of 110.14(C)(1)(a) puts you in the 60°C column unless the question says the equipment is rated 75°C.
  • "Terminations rated 75°C" or "listed for 75°C." The writer is handing you the 75°C column. Use it, but never the 90°C column.
  • "Over 100 amperes." Go straight to the 75°C column, even if the insulation is 90°C.
  • Derating plus terminals. "Six current-carrying conductors" or "in an ambient of 45°C" means two numbers: the derated 90°C value and the termination-column value. The answer is the smaller one.
  • A choice equal to the 90°C value. It is almost always the distractor.

Practice: NEC 110.14(C) questions

Exam-style question

A 60-ampere circuit is installed with THHN copper conductors. The circuit breaker and the equipment are marked for 75°C terminations. What is the minimum conductor size, with no derating?

Pick an answer to see the explanation.

Exam-style question

Per 110.14(C)(1)(b), terminations for circuits rated over 100 amperes shall be used only with conductors rated at least:

Pick an answer to see the explanation.

Exam-style question

Six current-carrying 6 AWG THHN copper conductors are installed in one raceway at 30°C, terminating on 75°C-rated equipment. What is the allowable ampacity of each conductor?

Pick an answer to see the explanation.

How to find it fast in the code book

110.14 is in Article 110, Part I, near the front of the book. Tab it, because almost every ampacity question needs it. Keep the tab close to your Table 310.16 tab mentally: you go from one to the other constantly. For a full walk-through of the ampacity table itself, see the wire ampacity chart (NEC Table 310.16).

→The table 110.14(C) points you toWire Ampacity Chart: How to Read NEC Table 310.16

Next steps

See how 110.14(C) shapes specific sizes in 10 gauge wire amps and 12 vs 14 gauge wire, and how it decides feeder sizes in 125 amp wire size. Terminals on aluminum conductors bring their own issues, covered in aluminum vs copper wire.

Then check that you can apply it under exam pressure with the free journeyman practice test or the timed practice tests.