An ampacity correction factor is the multiplier you apply to a conductor's Table 310.16 ampacity when the ambient temperature is not 30°C (86°F), and an adjustment factor is the multiplier you apply when more than three current-carrying conductors share a raceway or cable. In the 2023 NEC, correction factors are in Table 310.15(B)(1)(1) and adjustment factors are in Table 310.15(C)(1). When both apply, you multiply by both.
This guide gives you both tables, the rules for counting conductors, the rooftop adder, and six worked examples, including the "work backward to find the wire size" question that shows up on many journeyman exams.
Correction vs adjustment: what each one fixes
Table 310.16 is built on two assumptions: an ambient of 30°C (86°F) and no more than three current-carrying conductors together. Each assumption has its own fix.
Correction factor
- Fixes: ambient temperature ≠ 30°C
- Section 310.15(B)
- Table 310.15(B)(1)(1)
- Can be above 1.00 in cold locations
- Depends on the insulation column
Adjustment factor
- Fixes: more than 3 current-carrying conductors
- Section 310.15(C)(1)
- Table 310.15(C)(1)
- Always 1.00 or less
- Same for every column
Derated ampacity
Ampacity = Table 310.16 value × correction factor × adjustment factor
Many people call both of these "derating." That is fine in conversation, but exam questions use the NEC terms. Correction = temperature. Adjustment = number of conductors.
Table 310.15(B)(1)(1): ambient temperature correction factors
These factors apply to the ampacities of Table 310.16, which are based on a 30°C ambient. (The companion Table 310.15(B)(1)(2) is based on 40°C and is used with ampacity tables that assume a 40°C ambient.)
| Ambient °C | Ambient °F | 60°C | 75°C | 90°C |
|---|---|---|---|---|
| 10 or less | 50 or less | 1.29 | 1.20 | 1.15 |
| 11–15 | 51–59 | 1.22 | 1.15 | 1.12 |
| 16–20 | 60–68 | 1.15 | 1.11 | 1.08 |
| 21–25 | 69–77 | 1.08 | 1.05 | 1.04 |
| 26–30 | 78–86 | 1.00 | 1.00 | 1.00 |
| 31–35 | 87–95 | 0.91 | 0.94 | 0.96 |
| 36–40 | 96–104 | 0.82 | 0.88 | 0.91 |
| 41–45 | 105–113 | 0.71 | 0.82 | 0.87 |
| 46–50 | 114–122 | 0.58 | 0.75 | 0.82 |
| 51–55 | 123–131 | 0.41 | 0.67 | 0.76 |
| 56–60 | 132–140 | — | 0.58 | 0.71 |
| 61–65 | 141–149 | — | 0.47 | 0.65 |
| 66–70 | 150–158 | — | 0.33 | 0.58 |
| 71–75 | 159–167 | — | — | 0.50 |
| 76–80 | 168–176 | — | — | 0.41 |
| 81–85 | 177–185 | — | — | 0.29 |
A dash means the conductor cannot be used at that ambient: the surrounding air is already at or near its insulation limit.
The correction equation
310.15(B) also gives an equation you may use instead of the table:
Correction by calculation
I′ = I × √[(Tc − Ta′) ÷ (Tc − Ta)]
Tc is the conductor temperature rating, Ta is the table's ambient (30°C) and Ta′ is the actual ambient. For a 90°C conductor at 40°C: √[(90 − 40) ÷ (90 − 30)] = √(50 ÷ 60) = 0.913, which the table rounds to 0.91. The equation can give a slightly higher result than the table, because each table row uses the hottest temperature in its range. Exams almost always expect the table.
Rooftop raceways and cables: 310.15(B)(2)
Raceways and cables exposed to direct sunlight on or above rooftops get very hot. Under NEC 310.15(B)(2), where the raceway or cable is less than 7/8 inch (23 mm) above the roof, you add 33°C (60°F) to the outdoor ambient before looking up the correction factor. Type XHHW-2 conductors are exempt from this adder by an exception.
The practical lesson: keep rooftop raceways at least 7/8 inch off the roof surface, on supports, and the adder no longer applies.
Table 310.15(C)(1): more than three current-carrying conductors
When more than three current-carrying conductors are in a raceway or cable, or single conductors and cables are installed together without maintaining spacing for a continuous length longer than 24 inches (600 mm), reduce the ampacity of each conductor:
| Number of current-carrying conductors | Percent of table value |
|---|---|
| 4–6 | 80% |
| 7–9 | 70% |
| 10–20 | 50% |
| 21–30 | 45% |
| 31–40 | 40% |
| 41 and above | 35% |
80%
4 to 6 conductors
70%
7 to 9 conductors
50%
10 to 20 conductors
Adjustment factors do not apply to conductors in raceways 24 inches or less in length, such as short nipples between enclosures. Other specific conditions and exceptions in 310.15(C)(1) and in the wiring-method articles (cable tray, for instance) are worth reading in the code book itself.
How to count current-carrying conductors
This is where most adjustment errors happen.
Ungrounded (phase) conductors always count.
Equipment grounding and bonding conductors never count, per NEC 310.15(F).
Neutrals, under NEC 310.15(E):
- A neutral that carries only the unbalanced current of other conductors of the same circuit does not count. Example: the neutral of a 120/240 V, 3-wire circuit, or of a balanced 3-phase, 4-wire circuit with linear loads.
- In a 3-wire circuit made of two phase conductors and the neutral of a 4-wire, 3-phase wye system, the neutral carries about the same current as the phase conductors, so it counts.
- On a 4-wire, 3-phase wye system where the major portion of the load is nonlinear (electronic drivers, computers, VFDs), harmonic currents add on the neutral, so it counts.
The method, step by step
- Count the current-carrying conductors.
- Find the ambient (and add the rooftop adder if it applies).
- Start at the Table 310.16 value in the column that matches the insulation (90°C for THHN/THWN-2/XHHW-2).
- Multiply by the correction factor and the adjustment factor.
- Compare with the Table 310.16 value in the termination column under NEC 110.14(C) (usually 60°C or 75°C). Use the lower number.
- Check NEC 240.4(D) for 14, 12 and 10 AWG, and NEC 240.4(B) if you round the breaker up.
The termination step is explained in detail in termination temperature ratings, NEC 110.14(C).
Worked examples
1. Correction only: hot mechanical room
- 1
The question
Three 8 AWG THHN copper conductors are in a raceway in a 45°C (113°F) ambient. Terminations are 75°C. What is the ampacity?
- 2
Start at 90°C
8 AWG copper, 90°C = 55 A
- 3
Correct
41–45°C row, 90°C column = 0.87. 55 × 0.87 = 47.85 A
- 4
Termination check
75°C column = 50 A. 47.85 A is lower.
2. Adjustment only: nine conductors
- 1
The question
Nine current-carrying 12 AWG THHN copper conductors share one raceway at 30°C. What is the ampacity of each, and can they be on 20 A breakers?
- 2
Start and adjust
90°C = 30 A. 7–9 conductors = 70%. 30 × 0.70 = 21 A
- 3
Check limits
75°C terminal limit = 25 A. 240.4(D) limit = 20 A. 21 A ≥ 20 A.
3. Both factors at once
- 1
The question
Six current-carrying 10 AWG THHN copper conductors are in one EMT raceway in a 40°C (104°F) ambient. Terminations are 75°C. What is the ampacity?
- 2
Factors
Correction (36–40°C, 90°C column) = 0.91. Adjustment (4–6) = 0.80.
- 3
Multiply
40 × 0.91 × 0.80 = 29.12 A
- 4
Check
75°C column = 35 A, higher. 240.4(D) = 30 A max breaker.
4. Rooftop conduit
- 1
The question
Three 6 AWG THWN-2 copper conductors run in a conduit laid directly on a roof (less than 7/8 inch above it). The design outdoor temperature is 35°C (95°F). What is the ampacity before the termination check?
- 2
Rooftop adder
35°C + 33°C = 68°C
- 3
Correct
66–70°C row, 90°C column = 0.58. 6 AWG at 90°C = 75 A. 75 × 0.58 = 43.5 A
5. Working backward: find the wire size
- 1
The question
A 40 A load is supplied by THHN copper conductors. There are 8 current-carrying conductors in the raceway and the ambient is 40°C. Terminations are 75°C. What is the minimum conductor size?
- 2
Combined factor
Correction 0.91 × adjustment 0.70 = 0.637
- 3
Required table value
40 ÷ 0.637 = 62.8 A needed in the 90°C column.
- 4
Pick and verify
8 AWG (55 A) is too small. 6 AWG (75 A): 75 × 0.637 = 47.8 A ≥ 40 A. Termination check: 6 AWG at 75°C = 65 A, so 47.8 A controls.
6. Counting the neutral
- 1
The question
A 208Y/120-volt, 3-phase, 4-wire feeder supplies mostly LED lighting drivers and computer loads. It has three 3 AWG THHN copper phase conductors, one 3 AWG THHN neutral and one EGC in a raceway at 30°C. What is the ampacity of each conductor?
- 2
Count
3 phase conductors + neutral (counts: major portion of the load is nonlinear) = 4 current-carrying conductors. EGC does not count.
- 3
Adjust
3 AWG at 90°C = 115 A. 115 × 0.80 = 92 A
- 4
Termination check
75°C column = 100 A. 92 A is lower.
NM cable and derating
NM cable conductors are 90°C rated, and NEC 334.80 lets you use the 90°C rating for derating purposes, provided the final ampacity does not exceed the 60°C value. 334.80 also requires adjustment factors where more than two NM cables containing two or more current-carrying conductors are installed without maintaining spacing through the same opening in wood framing that is to be sealed with thermal insulation, caulk or sealing foam, and in similar contact-with-insulation situations described in that section.
Because the 60°C cap is low, light derating often changes nothing for NM: 12/2 NM bundled at 80% gives 30 × 0.80 = 24 A, still above its 20 A cap.
Common mistakes
Derating from the 75°C or 60°C column when the insulation is 90°C. You lose capacity you are entitled to. Start at the insulation rating.
Skipping the termination check. Three 8 AWG THHN with no derating are not 55 A. The 75°C terminals cap them at 50 A.
Counting the EGC. Never.
Counting every neutral, or never counting any. Apply the three cases of 310.15(E).
Adding percentages instead of multiplying. A 0.91 correction and 0.80 adjustment combine to 0.728, not 0.71.
Using the wrong table. Table 310.15(B)(1)(1) is for the 30°C-based tables like 310.16. The 40°C table, 310.15(B)(1)(2), goes with tables that are based on 40°C.
Practice: correction and adjustment questions
Exam-style question
What is the ampacity of a 4 AWG THHN copper conductor in a 50°C (122°F) ambient, with three current-carrying conductors in the raceway and 75°C terminations?
Pick an answer to see the explanation.
Exam-style question
A raceway contains 14 current-carrying conductors. What adjustment factor applies?
Pick an answer to see the explanation.
Exam-style question
A raceway contains two 120/240-volt, 3-wire circuits: four ungrounded conductors, two neutrals carrying only the unbalanced current, and one equipment grounding conductor. How many current-carrying conductors are there for adjustment purposes?
Pick an answer to see the explanation.
How to find these tables fast
In the 2023 NEC, the correction tables sit in 310.15(B) and the adjustment table in 310.15(C), just before Table 310.16. Tab all three together. If your exam is on an older edition, the numbers differ: before the 2020 reorganization of Article 310, Table 310.16 was Table 310.15(B)(16) and the adjustment table was 310.15(B)(3)(a). Check your edition with which NEC edition does my state use.
→The table you derate fromWire Ampacity Chart: How to Read NEC Table 310.16Next steps
Every derating question starts from the wire ampacity chart (NEC Table 310.16). See derating applied to specific sizes in 10 gauge wire amps, 8 AWG wire ampacity and 12 vs 14 gauge wire, and remember that derating does nothing for long runs: that is what the voltage drop formula is for. Conduit fill and derating go hand in hand, so review conduit fill calculation too.