A conduit fill calculation tells you whether a set of conductors may legally share a raceway. You add up the cross-sectional area of every conductor, insulation included, and compare the total with the percentage of the raceway's internal area that Chapter 9, Table 1 allows: 40% for three or more conductors, 31% for two, 53% for one.

This guide works through the whole method the way the journeyman exam tests it: which table gives which number, the notes that change the answer, when Annex C does the work for you, and five worked examples from a single-size branch circuit to a mixed feeder and a nipple. By the end you should be able to size a raceway or check a fill in two to three minutes with your code book open.

What a conduit fill calculation is (and how it differs from box fill)

Conductors in a raceway need room for two reasons. First, they have to be pulled in without damage: a crowded conduit scrapes insulation and jams at bends. Second, they need room to shed heat. Chapter 9 sets the limits as a percentage of the raceway's cross-section.

Electricians and exam candidates mix this up with box fill all the time. The two methods have nothing in common except the word "fill":

Conduit fill (Chapter 9)

  • Compares AREAS in square inches
  • Conductor areas from Table 5 (or 5A, 8)
  • Raceway area from Table 4
  • Limit is a percentage: 53%, 31% or 40%
  • Annex C gives ready answers for one wire size

Box fill (314.16)

  • Compares VOLUMES in cubic inches
  • Allowance per conductor from Table 314.16(B)(1)
  • Box volume from Table 314.16(A) or the marking
  • Counts devices, clamps and grounds as items
  • Applies to 6 AWG and smaller

If the question mentions a box, think cubic inches and counting. If it mentions a conduit, tubing or nipple, think square inches and percentages. The full counting method for boxes is in our box fill calculation guide.

The 40% rule: Chapter 9, Table 1

Everything starts with Chapter 9, Table 1. It is short, and you should know it by heart:

Number of conductors or cablesMaximum fill (% of raceway area)
153%
231%
Over 240%
1 wire: 53%2 wires: 31%3 or more: 40%single conductor or cablelowest limit (jam risk)the everyday rule
Chapter 9, Table 1: the allowed fill depends on how many conductors share the raceway.

Why is two conductors stricter than three? Two round conductors side by side are as wide as two diameters but use little of the circle's area. At bends they tend to line up across the raceway and wedge. The 31% limit keeps the conduit wide enough that two conductors cannot jam.

The tables you need for every conduit fill calculation

Chapter 9 is a set of tables that work together. Know which one gives which number before exam day:

TableWhat it gives youWhen you use it
Chapter 9, Table 1Allowed fill percentage (53/31/40)Every calculation
Chapter 9, Table 4Internal area of each raceway type and trade size, already multiplied by 100%, 60%, 53%, 31% and 40%Every calculation
Chapter 9, Table 5Area of each insulated conductor (THHN, THW, XHHW, RHH and others)Mixed sizes, or checking Annex C
Chapter 9, Table 5AArea of compact conductorsCompact aluminum feeders
Chapter 9, Table 8Area of bare conductorsBare EGCs in the raceway
Annex CMaximum number of same-size, same-type conductors, ready-madeAll conductors identical

Table 4 is the one people misread. It is split by raceway article: EMT (Article 358), ENT (362), FMC (348), IMC (342), LFMC (350), RMC (344), PVC Schedule 80 and Schedule 40 (352), and others. Each raceway type has a different internal diameter for the same trade size. Pick the right sub-table first.

How to do a conduit fill calculation, step by step

Every exam question on conduit fill falls into one of two shapes: "how many conductors fit?" or "what size raceway is required?" Both use the same five steps.

  1. Identify the raceway type and trade size (EMT, PVC Schedule 40, RMC…). That decides which part of Table 4 you use.
  2. List every conductor, including the equipment grounding conductor, with its size and insulation type.
  3. Decide the shortcut. If every conductor is the same size and insulation type, go to Annex C. If not, continue.
  4. Add the areas. Look up each conductor in Table 5 (or 5A, or Table 8 for bare), multiply by the quantity, and add.
  5. Compare with Table 4. Use the 40% column for three or more conductors (31% for two, 53% for one, 60% for a short nipple). The total area of the conductors must be equal to or less than that number.

The conduit fill check

Σ (quantity × Table 5 area) ≤ Table 4 area at the allowed %

All conductors same sizeand same insulation?YESNOAnnex C table forthat raceway typeAdd Table 5 areas(5A compact, 8 bare)Compare with Table 453% · 31% · 40% · 60% nippleRead the max number
Decision flow for any conduit fill question.

Table 4: raceway areas for the sizes you will see most

These are the Table 4 values exam questions use most often. The 40% column is the one you will use nine times out of ten.

Trade sizeEMT total (in²)EMT 40%PVC Sch. 40 40%RMC 40%
1/20.3040.1220.1140.125
3/40.5330.2130.2030.220
10.8640.3460.3330.355
1-1/41.4960.5980.5810.610
1-1/22.0360.8140.7940.829
23.3561.3421.3161.363

Notice that PVC Schedule 40 holds slightly less than EMT of the same trade size, and RMC slightly more. Schedule 80 PVC, with its thicker wall, holds much less: its 3/4 trade size gives only 0.164 in² at 40%. Never assume one raceway type's numbers apply to another.

0.213 in²

3/4 EMT at 40% fill

0.346 in²

1 in. EMT at 40% fill

0.0133 in²

one 12 AWG THHN (Table 5)

Table 5: conductor areas for THHN/THWN-2

Table 5 lists the approximate area of each insulated conductor. THHN, THWN and THWN-2 share one set of dimensions, which is why they are the default on most exam questions:

Size (AWG/kcmil)Area (in²)SizeArea (in²)
140.00971/00.1855
120.01332/00.2223
100.02113/00.2679
80.03664/00.3237
60.05072500.3970
40.08243000.4608
30.09733500.5242
20.11584000.5863
10.15625000.7073

Insulation type matters a lot. A 12 AWG THW (thicker insulation) is listed at 0.0181 in², about 36% bigger than 12 AWG THHN. If a question says THW, RHH or XHHW, look up that row; do not reuse the THHN number. Our THHN vs THWN guide explains what the letters mean.

Worked examples, built like exam questions

Worked example

Same size: how many 12 AWG THHN in 3/4 EMT?

  1. 1

    The question

    What is the maximum number of 12 AWG THHN conductors permitted in trade size 3/4 EMT?

  2. 2

    Shortcut

    Every conductor is the same size and type, so Annex C, Table C.1 (EMT) applies directly: 16 conductors.

  3. 3

    Check it by calculation

    Table 4, EMT 3/4 at 40% = 0.213 in². Table 5, 12 AWG THHN = 0.0133 in². 0.213 ÷ 0.0133 = 16.02.

  4. 4

    Round

    The decimal (0.02) is less than 0.8, so round down to 16.

  5. ✓ Answer: 16 conductors. Annex C and the calculation agree, as they should.
Worked example

The 0.8 rounding rule: 14 AWG THHN in 3/4 EMT

  1. 1

    Divide

    0.213 ÷ 0.0097 = 21.96 conductors.

  2. 2

    Apply the note

    The notes to the Chapter 9 tables say that when the result has a decimal of 0.8 or larger, you may use the next higher whole number. 0.96 is larger than 0.8.

  3. ✓ Answer: 22 conductors, which is the value in Annex C, Table C.1.

The same rule cuts the other way. Ten AWG THHN in 3/4 PVC Schedule 40: 0.203 ÷ 0.0211 = 9.62. The decimal is under 0.8, so the answer is 9, not 10.

Worked example

Mixed sizes: is 3/4 EMT big enough?

  1. 1

    The question

    A run of EMT will contain six 12 AWG THHN, three 10 AWG THHN and one 10 AWG THHN equipment grounding conductor. What is the minimum trade size of EMT?

  2. 2

    Add the areas (Table 5)

    12 AWG: 6 × 0.0133 = 0.0798 in². 10 AWG (including the EGC): 4 × 0.0211 = 0.0844 in². Total = 0.1642 in².

  3. 3

    Compare with Table 4 (40%, ten conductors)

    1/2 EMT at 40% = 0.122 in². Too small. 3/4 EMT at 40% = 0.213 in². 0.1642 ≤ 0.213.

  4. ✓ Answer: Trade size 3/4 EMT. Annex C cannot be used here because the sizes are mixed.
Worked example

Feeder: four 1/0 THHN plus a 6 AWG EGC

  1. 1

    The question

    A 3-phase, 4-wire feeder uses four 1/0 THHN conductors (three phases and a neutral) and one 6 AWG THHN equipment grounding conductor in EMT. What is the minimum trade size?

  2. 2

    Areas

    1/0: 4 × 0.1855 = 0.7420 in². 6 AWG: 1 × 0.0507 = 0.0507 in². Total = 0.7927 in².

  3. 3

    Compare (40%)

    1-1/4 EMT = 0.598 in². Too small. 1-1/2 EMT = 0.814 in². 0.7927 ≤ 0.814.

  4. ✓ Answer: Trade size 1-1/2 EMT. Leave out the EGC and you would still need 1-1/2 (0.742 in²), but the exam expects you to count it.
Worked example

Nipple at 60%

  1. 1

    The question

    A 3/4 EMT nipple 18 inches long connects a panelboard to a wireway. How much conductor area may it contain?

  2. 2

    Apply the nipple note

    The nipple is not longer than 24 inches between enclosures, so it may be filled to 60%. Table 4, 3/4 EMT, 60% column = 0.320 in².

  3. 3

    How many 10 AWG THHN?

    0.320 ÷ 0.0211 = 15.17, so 15 conductors (decimal under 0.8). In a normal run of 3/4 EMT, the limit would be 10.

  4. ✓ Answer: 0.320 in² of conductors, or fifteen 10 AWG THHN. No ampacity adjustment for the number of conductors is needed in the nipple either.

The notes to Chapter 9 that change the answer

The percentages are only half of Chapter 9. The notes to the tables are where most of the exam traps live. These are the ones to highlight in your book:

Equipment grounding conductors count. Equipment grounding and bonding conductors installed in the raceway are included in the fill, using their actual dimensions. Insulated EGC: Table 5. Bare EGC: Table 8. Need help sizing that EGC? See equipment grounding conductor sizing (Table 250.122).

Nipples get 60%. A conduit or tubing nipple not longer than 24 inches between boxes, cabinets and similar enclosures may be filled to 60%, and the ampacity adjustment factors of NEC 310.15(C)(1) do not apply to it.

The 0.8 rounding rule. When calculating the maximum number of same-size conductors, use the next higher whole number only when the decimal is 0.8 or more. Annex C applies it at every percentage, including the 31% two-conductor limit. That is why Table C.1 lets two 6 AWG THHN into 1/2 EMT: 0.094 ÷ 0.0507 = 1.86, which rounds up to 2, even though 2 × 0.0507 = 0.1014 in² is slightly over 0.094 in².

Cables count as one conductor. A multiconductor cable, optical fiber cable or flexible cord of two or more conductors is treated as a single conductor. For a cable with an elliptical cross-section, use the major diameter as the diameter of a circle.

Assemblies of single conductors are not cables. Single insulated conductors twisted or bundled together without an overall covering are counted as individual conductors, not as one cable.

Sleeves are different. Table 1 applies to complete conduit or tubing systems. It is not intended for short sections of conduit or tubing used only to protect exposed wiring from physical damage.

A single cable in a conduit: the 53% case

A multiconductor cable counts as a single conductor, so a cable in its own raceway may fill 53%. That applies to a complete raceway run. A short sleeve used only to protect a cable from physical damage (Note 2) is not subject to Table 1 at all.

Worked example

One cable in EMT

  1. 1

    The question

    A multiconductor cable has an outside diameter of 0.50 in. What is the smallest EMT that may contain it as a complete raceway run?

  2. 2

    Cable area

    Area = π × d² ÷ 4 = 3.1416 × 0.25 ÷ 4 = 0.196 in².

  3. 3

    Compare with the 53% column

    1/2 EMT at 53% = 0.161 in². Too small. 3/4 EMT at 53% = 0.283 in². 0.196 ≤ 0.283.

  4. ✓ Answer: Trade size 3/4 EMT.

Fill is not the only limit: ampacity adjustment

A conduit can be legally filled and still have conductors that are too small. When more than three current-carrying conductors share a raceway longer than 24 inches, their ampacity must be reduced under NEC 310.15(C)(1):

Current-carrying conductorsAdjustment factor
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

So twenty-two 14 AWG THHN in 3/4 EMT may fit the fill rule, but if most of them are current-carrying they are derated to 45% of their table ampacity. On the job, that is usually the real limit. The full method is in ampacity correction and adjustment factors, and the base values come from the wire ampacity chart (Table 310.16).

Bends, pull points and the rest of the raceway

Fill limits assume a run that can actually be pulled. The raceway articles add a second limit: no more than 360 degrees of bends between pull points, for example NEC 358.26 for EMT, NEC 344.26 for RMC and NEC 352.26 for PVC. Every offset, kick and saddle counts toward that total, which is why the conduit bending basics guide tracks degrees on every bend.

When the run gets too long or the conductors are 4 AWG and larger, you add a pull box or junction box. Its size is not a fill calculation at all: it follows the straight-pull and angle-pull multipliers of 314.28, explained in our pull box sizing guide.

Two related limits are worth knowing for the exam:

  • Wireways: the sum of the conductor areas may not exceed 20% of the wireway's interior cross-section (NEC 376.22(A)).
  • Conduit bodies: a conduit body may not contain more conductors than the raceway attached to it is allowed to carry (NEC 314.16(C)(1)).

Practice: conduit fill exam questions

Exam-style question

What is the maximum number of 10 AWG THHN conductors permitted in trade size 1 EMT?

Pick an answer to see the explanation.

Exam-style question

An EMT run contains three 8 AWG THHN, one 8 AWG THHN neutral and one 10 AWG THHN EGC. What is the minimum trade size?

Pick an answer to see the explanation.

Exam-style question

Two conductors are installed in a raceway. What maximum percentage of the raceway's cross-sectional area may they occupy?

Pick an answer to see the explanation.

The mistakes that cost points on exam day

Using the wrong raceway sub-table. EMT, IMC, RMC, PVC 40 and PVC 80 all have different areas for the same trade size. Find the article number at the top of the Table 4 sub-table before you read a number.

Using the 100% column. Table 4 gives total area and pre-multiplied columns. Use the 40% column for three or more conductors. Do not multiply the 40% value by 0.40 again.

Using Annex C with mixed sizes or a different ground. Twelve 12 AWG THHN plus a 12 AWG THHN ground is fine for Annex C. Twelve 12 AWG THHN plus a 10 AWG ground is not.

Rounding the wrong way. 9.62 becomes 9. 21.96 becomes 22. Only 0.8 and above goes up.

Forgetting the nipple rule, or applying it to a long run. 60% is only for a nipple not longer than 24 inches between enclosures.

Treating fill as the ampacity check. A legal fill can still require heavy derating.

How to find conduit fill fast in the code book

Chapter 9 sits right after Article 840, near the back of the book, and Annex C follows the Chapter 9 tables. Put one tab on Chapter 9, Table 1 (the notes are on the same pages), one on the first page of Table 4, one on Table 5, and one on Annex C. Inside Annex C, flag the EMT table (C.1) and the PVC Schedule 40 table, because those two cover most exam questions. See how to tab your NEC code book for a full tab plan.

→Quick answers for 1/2, 3/4 and 1 inch EMTHow Many Wires Fit in 1/2, 3/4 and 1 Inch EMT? Conduit Fill Examples

Where conduit fill fits in the rest of the exam

Conduit fill is one of four calculations in this part of the exam. Box sizes come from box fill under 314.16, large boxes from pull box sizing under 314.28, and the field side of the raceway from conduit bending. For quick numbers on common EMT sizes, keep how many wires fit in 1/2, 3/4 and 1 inch EMT open on your phone.

→The other fill calculationBox Fill Calculation: NEC 314.16 With Worked Examples

The official text of Chapter 9 is in NFPA 70; NFPA offers free read-only access to the current edition through its NFPA 70 page. When you can do the examples above without looking, put yourself under the clock with the free journeyman practice test or a timed set on the practice tests page.