THHN vs THWN comes down to two things: temperature and water. THHN is rated 90°C in dry and damp locations. THWN is rated 75°C in dry and wet locations. THWN-2 combines the best of both: 90°C in dry and wet locations. That is why most building wire on the shelf is printed THHN/THWN-2: one conductor, legal in either place.

The letters look like alphabet soup, but each one means something, and the exam tests them. After this guide you will be able to decode any insulation marking, know where each type is allowed, and see exactly how the rating changes an ampacity calculation.

THHN vs THWN vs THWN-2 at a glance

These ratings are from NEC Table 310.4(1), "Conductor Applications and Insulations Rated 600 Volts," in the 2023 NEC.

TypeMax. temperatureLocationsTable 310.16 column
THHN90°CDry and damp90°C
THWN75°CDry and wet75°C
THWN-290°CDry and wet90°C
THW75°CDry and wet75°C
THHW75°C wet / 90°C dryWet and dry75°C wet, 90°C dry
XHHW75°C wet / 90°C dry and dampWet, dry, damp75°C wet, 90°C dry
XHHW-290°CDry and wet90°C

What the letters mean

The type letters are trade designations. Read them left to right.

THWN-2Thermo-plasticHeatresistantHH = 90°CWetlocationsNylonjacket90°Cwet and dryTHHN: no W = not for wet locations. HH = 90°C.
Decoding THWN-2, letter by letter.
  • T = thermoplastic insulation.
  • H = heat-resistant, rated 75°C. HH = high heat-resistant, rated 90°C.
  • W = rated for wet locations.
  • N = nylon outer jacket (it slides through conduit and resists abrasion and some oils).
  • X (as in XHHW) = cross-linked synthetic polymer insulation, no nylon jacket needed.
  • -2 = rated 90°C in wet locations too.

So THHN reads "thermoplastic, high heat, nylon": 90°C, no wet rating. THWN reads "thermoplastic, heat, wet, nylon": 75°C, wet OK. Add -2 and THWN climbs to 90°C wet.

Dry, damp and wet: where each type is allowed

Article 100 defines three location types, and they decide which insulation you can use.

  • Dry location: not normally subject to dampness or wetness. Most interior walls and ceilings.
  • Damp location: partially protected and subject to moderate moisture, such as under canopies, roofed open porches, and some basements.
  • Wet location: underground, in concrete or masonry in direct contact with the earth, subject to saturation, or exposed to the weather without protection.

Two rules move a lot of installations into the "wet" column that people do not expect:

That means:

InstallationLocation typeTHHN only?THWN / THWN-2?
EMT inside a heated buildingDry✓✓
Raceway in a basement with moderate moistureDamp✓✓
PVC underground to a detached garageWet✗✓
EMT on an outside wallWet✗✓
Conduit in a slab on gradeWet✗✓

How THHN vs THWN changes ampacity

Insulation type decides which column of NEC Table 310.16 you start from:

Size (Cu)75°C (THWN, THW)90°C (THHN, THWN-2)
14 AWG20 A25 A
12 AWG25 A30 A
10 AWG35 A40 A
8 AWG50 A55 A
6 AWG65 A75 A

Two limits keep you from simply using the bigger number:

  1. Terminations, NEC 110.14(C): most equipment is rated 60°C or 75°C. The final ampacity cannot exceed the column of the terminal rating. See termination temperature ratings.
  2. Small conductors, NEC 240.4(D): 14, 12 and 10 AWG copper are limited to 15, 20 and 30 A overcurrent protection. See 10 gauge wire amps.

So why buy 90°C wire? Because correction and adjustment factors are applied to the conductor's own temperature column. Starting from 90°C leaves more ampacity after derating.

Worked example

Nine current-carrying 12 AWG conductors in one EMT

  1. 1

    The question

    Nine current-carrying 12 AWG copper conductors share one EMT in a dry location, 30°C ambient. Compare the adjusted ampacity of THHN and THWN.

  2. 2

    Adjustment factor

    7 to 9 current-carrying conductors: 70% (NEC 310.15(C)(1)).

  3. 3

    THHN (90°C)

    30 A × 0.70 = 21 A.

  4. 4

    THWN (75°C)

    25 A × 0.70 = 17.5 A.

  5. ✓ Answer: THHN: 21 A, enough for a fully loaded 20 A circuit (still capped at 20 A by 240.4(D)). THWN: 17.5 A, less than 20 A.
Worked example

Wet location: why the -2 matters

  1. 1

    The question

    Four current-carrying 10 AWG copper conductors run in EMT on an outdoor wall (a wet location) at 30°C ambient, 75°C terminals. Compare THWN and THWN-2.

  2. 2

    THWN: 75°C in wet locations

    35 A × 0.80 (4 to 6 conductors) = 28 A.

  3. 3

    THWN-2: 90°C in wet locations

    40 A × 0.80 = 32 A. Compare with the 75°C termination value of 35 A: 32 A is lower, so 32 A stands.

  4. ✓ Answer: THWN-2 keeps 32 A; THWN drops to 28 A. A dual-marked THHN/THWN-2 conductor in a wet location is used at its THWN-2 rating.

The ampacity correction and adjustment factors guide covers ambient temperature, rooftop raceways and the neutral rules.

Why most wire is dual-rated THHN/THWN-2

Manufacturers build one insulation system that passes the tests for several types and print all of them on the jacket. A typical example is copper building wire sold as THHN/THWN-2, like Southwire's SIMpull THHN/THWN-2 specification sheet. When a conductor carries more than one marking, you apply the rating that matches the location: THHN in dry and damp locations, THWN-2 in wet ones.

What you should still check on the printing:

  • The type letters actually include a W before you pull it into underground or outdoor raceway.
  • The -2 if you are counting on 90°C in a wet location. Some reels, especially in the small sizes, are printed THHN/THWN without the -2, and that conductor is only 75°C when wet.
  • The conductor material (copper or aluminum) and size.

Other types you will see next to THHN and THWN

XHHW and XHHW-2. Cross-linked polyethylene insulation, no nylon jacket. XHHW is 90°C dry and damp, 75°C wet; XHHW-2 is 90°C dry and wet. It is tougher against abrasion and cold, and it is the common choice for aluminum feeders and service conductors in conduit.

THW and THHW. Older thicker thermoplastic types. THW is 75°C wet and dry. THHW is 90°C dry but only 75°C wet, so it behaves like XHHW.

Cables are different. NM, UF and SE cable have their own articles and their own ampacity limits. Type NM, for example, is held to the 60°C column by NEC 334.80 even though the conductors inside are usually 90°C. The individual-conductor ratings in this guide apply to conductors pulled in raceway.

Does insulation type change conduit fill?

Yes. Conduit fill uses the area of each insulated conductor from Chapter 9, Table 5, and the nylon-jacketed types are thinner. THHN, THWN and THWN-2 share one row in that table. For 12 AWG, that row gives 0.0133 in², while THW and XHHW are 0.0181 in², about 36% larger. Same wire size, same ampacity column for THWN and THW, but fewer THW conductors fit in the same raceway.

That is one more reason THHN/THWN-2 dominates commercial work: it fits more circuits in a given conduit and pulls more easily. The step-by-step method is in the conduit fill calculation guide, and quick answers for common sizes are in how many wires fit in 3/4 EMT.

Exam-style practice

Exam-style question

Which conductor insulation type is NOT permitted in a wet location?

Pick an answer to see the explanation.

Exam-style question

The interior of a PVC conduit installed underground is considered what type of location?

Pick an answer to see the explanation.

Exam-style question

What is the maximum operating temperature of a THWN conductor in a wet location?

Pick an answer to see the explanation.

Mistakes that cost points

Calling conduit a dry location. Underground and outdoor raceways are wet locations by rule.

Using the 90°C value as the final answer. Terminals almost always limit it to 75°C or 60°C.

Forgetting the -2. A THWN (no -2) conductor in a wet location is a 75°C conductor.

Mixing up H and HH. One H is 75°C; two H is 90°C.

How to find this fast in the code book

Tab NEC Table 310.4(1) for insulation types and the header row of NEC Table 310.16, where the same type letters are grouped under each temperature column. Add NEC 300.5(B) and NEC 300.9 for the wet-location rules. The code text is free to read on the NFPA free access page.

→The pillar: reading Table 310.16Wire Ampacity Chart: How to Read NEC Table 310.16

Conductor type also changes how many wires fit in a raceway, so pair this with the conduit fill calculation guide and aluminum vs copper wire. Then test yourself with the free journeyman electrician practice test.