Aluminum vs copper wire comes down to one trade: aluminum is lighter and usually cheaper, but it conducts less current for the same size, so you install a bigger conductor, typically about two AWG sizes larger. 4/0 aluminum does roughly the job of 2/0 copper. Both materials are fully recognized by the NEC and sized from their own columns in Table 310.16.
For electricians, the real question is not which metal is "better" but where each one belongs and how to install it so it lasts. This guide compares ampacity, size, weight, voltage drop and grounding, then covers the termination rules that decide whether an aluminum job passes inspection.
Aluminum vs copper wire size chart (75°C)
Every value below comes from the 75°C columns of NEC Table 310.16, the columns you use with 75°C terminals on services and feeders. The table header covers "aluminum or copper-clad aluminum" in the same column, so copper-clad aluminum uses the aluminum ampacities.
| Copper | Ampacity | Aluminum equivalent | Ampacity |
|---|---|---|---|
| 6 AWG | 65 A | 4 AWG | 65 A |
| 4 AWG | 85 A | 2 AWG | 90 A |
| 3 AWG | 100 A | 1 AWG | 100 A |
| 2 AWG | 115 A | 1/0 | 120 A |
| 1 AWG | 130 A | 2/0 | 135 A |
| 1/0 | 150 A | 3/0 | 155 A |
| 2/0 | 175 A | 4/0 | 180 A |
| 3/0 | 200 A | 250 kcmil | 205 A |
| 4/0 | 230 A | 300 kcmil | 230 A |
| 350 kcmil | 310 A | 500 kcmil | 310 A |
| 400 kcmil | 335 A | 600 kcmil | 340 A |
| 500 kcmil | 380 A | 750 kcmil | 385 A |
The "two sizes" rule is only a memory aid. Above 4/0 it stops lining up cleanly (250 kcmil Cu is 255 A, but 350 kcmil Al is only 250 A), so always read the table. For how the columns and footnotes work, see the wire ampacity chart guide.
Why aluminum needs a bigger conductor
Aluminum has higher resistance than copper for the same cross-section. Commonly cited values put aluminum's conductivity at about 61% of copper's. More resistance means more heat at the same current, and Table 310.16 is a heat table: it limits current so the insulation does not exceed its temperature rating. So for the same ampacity, aluminum needs more circular mils.
Weight goes the other way. Aluminum's density is roughly 30% of copper's (about 2.70 vs 8.96 g/cm³). Even with the larger cross-section, 4/0 aluminum weighs roughly half as much as 2/0 copper per foot. On a 400 A service or a long feeder, that difference shows up in the pull, the supports and usually in the price.
Copper
- Smaller conductor for a given ampacity
- Tolerant terminations, fits device screws
- Standard for 15 and 20 A branch circuits
- Heavier and usually more expensive per ampere
- K = 12.9 for voltage drop
Aluminum
- About 2 AWG sizes larger for similar ampacity
- Needs AL-rated lugs and correct torque
- Standard for services, large feeders, SER
- Lighter and usually cheaper per ampere
- K = 21.2 for voltage drop
NEC rules that apply only to aluminum
Conductor material, NEC 310.3(B). Aluminum building wire covered by Article 310 must be made of an AA-8000 series electrical-grade aluminum alloy, for the solid small sizes and for stranded conductors marked with the common building-wire insulations (THHN, THWN, XHHW, SE and others) up through 1000 kcmil. This alloy is what separates modern aluminum building wire from older branch-circuit aluminum.
Minimum size, NEC 310.3(A). The smallest general-purpose conductor is 14 AWG copper or 12 AWG aluminum or copper-clad aluminum.
Small-conductor overcurrent limits, NEC 240.4(D). 12 AWG aluminum is limited to 15 A, and 10 AWG aluminum to 25 A. Compare with 20 A and 30 A for the same copper sizes. See 12 vs 14 gauge wire for the copper side of that rule.
Devices. Switches and receptacles rated 20 A or less that connect directly to aluminum must be listed and marked CO/ALR (NEC 404.14(C), NEC 406.3(C)). Terminals on 15 A and 20 A receptacles that are not marked CO/ALR are for copper and copper-clad aluminum only (NEC 406.3(D)).
Grounding electrode conductors, NEC 250.64(A). Bare, covered or insulated aluminum GECs may not be in direct contact with masonry or the earth, or in corrosive conditions, and outdoors they may not be terminated within 18 in. (450 mm) of the earth.
Terminations: where aluminum jobs succeed or fail
Aluminum forms a hard, insulating oxide layer as soon as it is exposed to air, and it expands and contracts more than copper as it heats and cools. A connection that is loose, under-torqued or made on the wrong terminal can heat up over time. That is why every aluminum rule above is about the connection.
Field checklist:
- Read the lug. Look for AL/CU (or AL7CU / AL9CU) on the lug or the equipment label. Most panel, meter-socket and breaker lugs in service sizes are dual-rated.
- Strip without nicking. Damaged strands reduce the cross-section exactly where the heat is.
- Wire-brush and apply antioxidant when the lug or connector manufacturer calls for it. 110.14 requires any compound used to be suitable for the use.
- Torque to the listed value using an approved means, normally a calibrated torque screwdriver or wrench, as required by NEC 110.14(D). Not "good and tight".
- Never mix copper and aluminum under one screw or in one connector unless it is identified for that.
Grounding conductors: copper and aluminum columns
Both grounding tables have a copper and an aluminum column, and the exam likes to make you pick the wrong one.
| OCPD rating | EGC copper | EGC aluminum |
|---|---|---|
| 20 A | 12 AWG | 10 AWG |
| 60 A | 10 AWG | 8 AWG |
| 100 A | 8 AWG | 6 AWG |
| 200 A | 6 AWG | 4 AWG |
| 400 A | 3 AWG | 1 AWG |
Values from NEC Table 250.122. The grounding electrode conductor follows NEC Table 250.66, which also has an aluminum column: for example, 4/0 aluminum service conductors need a 4 AWG copper or 2 AWG aluminum GEC. Full details: equipment grounding conductor sizing.
Voltage drop: copper vs aluminum
Aluminum's higher resistance also shows up in voltage drop. The single-phase formula uses K = 12.9 for copper and K = 21.2 for aluminum (approximate values per circular-mil-foot).
200 A feeder, 150 feet: 3/0 Cu vs 250 kcmil Al
- 1
The question
A 240 V single-phase feeder carries 160 A over 150 ft (one way). Compare voltage drop for 3/0 copper (167,800 cmil) and 250 kcmil aluminum (250,000 cmil), both rated about 200 A at 75°C.
- 2
Copper
VD = (2 × 12.9 × 160 × 150) ÷ 167,800 = 619,200 ÷ 167,800 = 3.69 V → 3.69 ÷ 240 = 1.54%.
- 3
Aluminum
VD = (2 × 21.2 × 160 × 150) ÷ 250,000 = 1,017,600 ÷ 250,000 = 4.07 V → 1.70%.
The method is detailed in the voltage drop formula guide.
When to choose aluminum, when to choose copper
Aluminum makes sense for service-entrance conductors, large feeders (roughly 100 A and up), long runs, and parallel sets, where weight and cost add up and every lug is rated AL/CU.
Copper makes sense for branch circuits, tight enclosures and small terminals, motor and equipment connections with copper-only terminals, and any place where the larger aluminum conductor will not fit the lug or the raceway.
Look at the conduit too. A larger aluminum conductor can push you into the next raceway size, so check the conduit fill calculation before you commit.
Mistakes that cost points
Reading the copper column for an aluminum question. The two columns sit side by side in Table 310.16. One slip of the eye and 2/0 becomes the answer for aluminum at 175 A, which is wrong.
Assuming "two sizes larger" is exact. It is a memory aid. 4/0 Cu (230 A) pairs with 300 kcmil Al (230 A), but 250 kcmil Cu (255 A) needs more than 350 kcmil Al (250 A).
Forgetting the small-conductor limits. 240.4(D) gives aluminum lower maximum breaker sizes than copper of the same gauge.
Using the copper column of Table 250.122 for an aluminum EGC. A 200 A feeder needs a 4 AWG aluminum EGC, not 6 AWG.
Treating every lug as dual-rated. Look for the AL/CU marking on the lug or the equipment. If it is not there, the terminal is for copper only.
Exam-style practice
Exam-style question
A feeder requires an ampacity of 175 A using conductors with 75°C insulation and terminals. What is the minimum size aluminum conductor?
Pick an answer to see the explanation.
Exam-style question
What is the maximum overcurrent protection for a 12 AWG aluminum conductor, unless specifically permitted elsewhere?
Pick an answer to see the explanation.
Exam-style question
A 15 A receptacle is to be connected directly to aluminum branch-circuit conductors. What marking must the receptacle have?
Pick an answer to see the explanation.
How to find this fast in the code book
The material rules are scattered, so tab them together: NEC 110.14 (terminations), NEC 310.3 (material and minimum size), NEC Table 310.16, NEC 240.4(D) and NEC 250.64(A). On every sizing question, circle the word "copper" or "aluminum" before you open a table. The code text is free to read on the NFPA free access page.
→Where 2/0 Cu and 4/0 Al meetWire Size for a 200 Amp Service: The 83% Rule (NEC 310.12)For applied examples, compare the 100 amp service wire size and the 400 amp service wire size guides. Then test yourself with the free journeyman electrician practice test.