The 400 amp service wire size for a house is 400 kcmil copper or 600 kcmil aluminum in a single run, or two parallel sets of 2/0 copper or 4/0 aluminum. Those sizes work because NEC 310.12 lets dwelling service conductors that carry the entire load have just 83% of the rating, which is 332 A. For a commercial 400 amp service, you size for the full 400 A: two sets of 3/0 copper or 250 kcmil aluminum are the usual choices.

At 400 A, the wire size is only half the question. You also have to decide between one big set and parallel sets, deal with how the utility meters it, and size the neutral and grounding conductors correctly. This guide walks through all of it, with worked examples built like exam questions.

400 amp service wire size chart

All values come from the 75°C column of NEC Table 310.16, the column you use with 75°C terminals. The wire ampacity chart guide shows how to read it.

SituationMinimumCopperAluminum
Dwelling, entire load, single set332 A400 kcmil (335 A)600 kcmil (340 A)
Dwelling, entire load, 2 parallel sets332 A2 × 2/0 (350 A)2 × 4/0 (360 A)
Commercial, full 400 A, single set400 A600 kcmil (420 A)—
Commercial, full 400 A, 2 parallel sets400 A2 × 3/0 (400 A)2 × 250 kcmil (410 A)
Commercial, load ≤ 360 A, 240.4(B)load—2 × 4/0 (360 A)

Notice what parallel sets buy you: two runs of 4/0 aluminum are far easier to pull and terminate than one 600 kcmil, and they use common lugs.

The 83% rule at 400 amps

NEC 310.12(A) covers dwelling services rated 100 through 400 A. Service conductors supplying the entire load of a one-family dwelling, or of an individual dwelling unit, are permitted an ampacity of not less than 83% of the service rating. 400 A is the top of that range.

Dwelling 400 A

0.83 × 400 A = 332 A

Single set, 75°C column:

  • Copper: 350 kcmil = 310 A (too small), 400 kcmil = 335 A ✓
  • Aluminum: 500 kcmil = 310 A (too small), 600 kcmil = 340 A ✓

Those are also the 400 A row of Table 310.12(A) in the 2023 NEC, which you may read directly when no correction or adjustment factors apply.

Two parallel sets: the ampacities add, so you need 332 A in total.

  • Copper: 2 × 1/0 = 300 A (too small), 2 × 2/0 = 350 A ✓
  • Aluminum: 2 × 3/0 = 310 A (too small), 2 × 4/0 = 360 A ✓

The rule needs all of it: dwelling, single-phase (120/240 V, or a 3-wire dwelling feeder from 208Y/120 V), entire load. A three-phase 400 A service never qualifies. And 310.12 does not cancel NEC 230.42(A): the conductors must still carry the calculated load, so a house that calculates above 332 A needs the full-size conductors. The moment you look at the feeder from a 200 A breaker to one of two panels, that conductor carries part of the load, so 310.12 no longer applies to it. Each of those feeders is sized from Table 310.16 at 200 A, as shown in the 200 amp service wire size guide.

Commercial 400 amp services: full rating and continuous loads

For a non-dwelling 400 A service there is no 83% shortcut. NEC 230.42(A) requires service conductors to carry the calculated load, with 125% of the continuous load plus the noncontinuous load. Feeders follow the same logic under NEC 215.2(A).

Then NEC 240.4(B) lets you round up to the next standard overcurrent device when the conductor ampacity does not match a standard rating and the device is 800 A or less. That is why two sets of 4/0 aluminum (360 A) may be protected at 400 A, but only when the calculated load is 360 A or less.

Worked example

Commercial 400 A service with continuous load

  1. 1

    The question

    A retail building has a calculated service load of 240 A continuous and 60 A noncontinuous, 208Y/120 V three-phase. The service disconnect is 400 A. Using two parallel sets of aluminum with 75°C terminals, what is the minimum conductor size?

  2. 2

    Required ampacity

    (240 × 1.25) + 60 = 300 + 60 = 360 A.

  3. 3

    Per set

    360 ÷ 2 = 180 A per set.

  4. 4

    Table 310.16, 75°C, aluminum

    3/0 Al = 155 A (too small). 4/0 Al = 180 A ✓. Total 360 A ≥ 360 A.

  5. 5

    Overcurrent protection

    360 A is not a standard rating. The next standard size is 400 A (NEC 240.6(A)), permitted by 240.4(B).

  6. ✓ Answer: Two sets of 4/0 aluminum, protected at 400 A, before any adjustment for the neutral being counted on a wye system (see 310.15(E)).

Parallel conductors: the rules in 310.10(G)

NEC 310.10(G) sets the conditions for running conductors in parallel. In short:

  1. Size 1/0 AWG and larger (with limited exceptions).
  2. Every paralleled conductor in a phase or the neutral must have the same length, same conductor material, same size, same insulation type, and be terminated in the same manner.
  3. If you use separate raceways or cables, they must have the same physical characteristics (do not mix one PVC run with one steel run for the same phase set).
  4. Each raceway must contain one conductor of every phase plus the neutral (and the EGC if there is one). Splitting phases between raceways causes induction heating in metal raceways; NEC 300.20(A) requires all conductors of a circuit to be grouped together.
CorrectRaceway 1Raceway 2A + B + N + EGC in eachWrongAll of AAll of BInduction heating, 300.20(A)Line ALine BNeutralEGC (feeders)
Correct parallel installation: each raceway carries a full set. Never group all of one phase in a single raceway.

One raceway or two? The adjustment factor decides

If you pull both parallel sets through a single raceway, you now have more than three current-carrying conductors, and NEC 310.15(C)(1) applies. The neutral of a single-phase 3-wire set carrying only unbalanced current is not counted (NEC 310.15(E)), so two sets give four current-carrying conductors: an 80% adjustment.

Worked example

Two sets of 4/0 Al in one raceway: does it still work?

  1. 1

    The question

    A 400 A one-family dwelling service uses two parallel sets of 4/0 aluminum XHHW-2 (90°C), both sets in one raceway, terminals rated 75°C. Is the installation adequate?

  2. 2

    Target

    0.83 × 400 = 332 A total.

  3. 3

    Adjust at 90°C

    4 current-carrying conductors → 80%. 4/0 Al at 90°C = 205 A × 0.80 = 164 A per conductor.

  4. 4

    Termination limit

    Compare with 4/0 Al at 75°C = 180 A. Use the lower: 164 A. Two in parallel: 2 × 164 = 328 A.

  5. ✓ Answer: No. 328 A is less than 332 A. Run each set in its own raceway (no adjustment, 2 × 180 = 360 A) or upsize.

The full adjustment method is in ampacity correction and adjustment factors.

Neutral and grounding conductor sizes at 400 amps

Neutral

The neutral may be reduced when the neutral load calculation of NEC 220.61 allows it, but never below the minimum in NEC 250.24(D)(1), which uses NEC Table 250.102(C)(1). With parallel sets in separate raceways, NEC 250.24(D)(2) sizes the neutral in each raceway is based on the ungrounded conductors in that raceway, and it can never be smaller than 1/0 AWG, the parallel minimum.

Grounding electrode conductor

NEC Table 250.66 uses the largest ungrounded service conductor, or for parallel sets, the sum of the areas of the corresponding conductors.

Service conductorsEquivalent areaGEC (Cu / Al)
1 × 400 kcmil Cu400 kcmil Cu1/0 Cu / 3/0 Al
1 × 600 kcmil Al600 kcmil Al1/0 Cu / 3/0 Al
2 × 2/0 Cu266.2 kcmil Cu2 AWG Cu / 1/0 Al
2 × 4/0 Al423.2 kcmil Al2 AWG Cu / 1/0 Al
2 × 3/0 Cu335.6 kcmil Cu2 AWG Cu / 1/0 Al
2 × 250 kcmil Al500 kcmil Al2 AWG Cu / 1/0 Al

2/0 copper is 133.1 kcmil (133,100 cmil) and 4/0 is 211.6 kcmil, from Chapter 9, Table 8. The usual electrode limits still apply: the part of a GEC going only to rods need not exceed 6 AWG copper, and only to a concrete-encased electrode need not exceed 4 AWG copper. Details are in the grounding electrode conductor sizing guide.

Equipment grounding conductor (feeders)

For a 400 A feeder, NEC Table 250.122 requires 3 AWG copper or 1 AWG aluminum. When the feeder is in parallel raceways, NEC 250.122(F) requires a full-size EGC in each raceway. The EGC sizing guide covers the parallel rule.

Exam-style practice

Exam-style question

A one-family dwelling has a 400 A, 120/240-volt single-phase service supplying the entire load. What is the minimum size single-set copper service conductor, with no correction or adjustment factors?

Pick an answer to see the explanation.

Exam-style question

Conductors run in parallel must generally be what minimum size?

Pick an answer to see the explanation.

Exam-style question

A 400 A feeder is installed as two parallel sets in two separate rigid metal conduits, and a wire-type EGC is required in each. What is the minimum size copper EGC in each conduit?

Pick an answer to see the explanation.

How to find this fast in the code book

Tab NEC 310.10(G) (parallel), NEC 310.12 and NEC Table 310.16 together, then NEC Table 250.66 and NEC Table 250.122. On parallel questions, write down three numbers before you look anything up: the required ampacity, the number of sets, and the number of current-carrying conductors per raceway. That order prevents most errors. You can read the current code text on the NFPA free access page.

→Choosing the conductor materialAluminum vs Copper Wire for Services and Feeders

For a service-by-service comparison, see the 100 amp service wire size guide and the 125 amp wire size guide. Then check your speed on these calculations with the free journeyman electrician practice test.