The wire size for a 100 amp service is 4 AWG copper or 2 AWG aluminum when it is a dwelling service supplying the entire house at 120/240 volts, single-phase. That smaller size is allowed because NEC 310.12 only requires those conductors to have 83% of the service rating. For a 100 amp subpanel feeder, or for any service that does not qualify, you need 3 AWG copper or 1 AWG aluminum.

The difference between those two answers is exactly what the journeyman exam tests. After this guide you will know which rule applies, how to read the right column in Table 310.16, how termination ratings and the next-size-up rule change the answer, and how to size the grounding conductors that go with it.

Wire size for 100 amp service: the quick chart

Here is the whole answer on one screen. All sizes assume conductors rated 75°C or higher (THHN/THWN-2, XHHW-2, SER) landing on terminals rated 75°C, which is what most meter sockets, panelboards and breakers in this range are marked for.

InstallationRule that appliesCopperAluminum
Dwelling service, entire load, 120/240 V 1ØNEC 310.12(A), 83% = 83 A4 AWG (85 A)2 AWG (90 A)
Dwelling main feeder, entire loadNEC 310.12(B), 83% = 83 A4 AWG (85 A)2 AWG (90 A)
100 A subpanel feeder (part of the load)Table 310.16, 75°C3 AWG (100 A)1 AWG (100 A)
Commercial or three-phase 100 A serviceTable 310.16, 75°C3 AWG (100 A)1 AWG (100 A)
100 A subpanel fed with Type NM cableNEC 334.80, 60°C column1 AWG (110 A)—

The ampacities in parentheses come straight from NEC Table 310.16. If you want to see how that table is laid out, column by column, read the wire ampacity chart guide for Table 310.16.

Why a 100 amp service can use 4 AWG copper: the 83% rule

NEC 310.12 covers single-phase dwelling services and feeders. It applies to one-family dwellings and to the individual dwelling units of two-family and multifamily dwellings, supplied by a single-phase, 120/240-volt system. In the 2023 NEC it also covers a single-phase dwelling feeder made of two ungrounded conductors and a neutral from a 208Y/120-volt system, which is common in apartment buildings.

The logic: a house almost never pulls its full service rating for long, and its load is spread across many circuits. So the code lets you size the conductors for 83% of the rating instead of 100%.

310.12 dwelling service

Minimum ampacity = 0.83 × service rating

For 100 A: 0.83 × 100 = 83 A. Now go to the 75°C column of Table 310.16 and find the first size that reaches 83 A. (The 2023 NEC also prints the results in Table 310.12(A), usable when no correction or adjustment factors apply. Its 100 A row says the same thing.)

  • Copper: 6 AWG is 65 A (too small), 4 AWG is 85 A. 85 ≥ 83, so 4 AWG copper works.
  • Aluminum: 3 AWG is 75 A (too small), 2 AWG is 90 A. 90 ≥ 83, so 2 AWG aluminum works.

The same 83% applies to a feeder that carries the entire load of the dwelling unit, for example the feeder from a meter-main to the only panel in the house (NEC 310.12(B)). It never applies to a feeder that carries only part of the load.

→Same rule, the most common service sizeWire Size for a 200 Amp Service: The 83% Rule (NEC 310.12)

When the 83% rule is off the table

You must go back to Table 310.16 at 100% whenever any of these is true:

  1. The building is not a dwelling (shop, office, store, church).
  2. The conductors do not carry the entire load: a feeder to a subpanel, a garage panel, a second panel.
  3. The system is three-phase, or otherwise not one of the two single-phase systems 310.12 names (120/240 V, or a 3-wire feeder from 208Y/120 V).
  4. The rating is outside 100 through 400 A.

If correction or adjustment factors apply (hot ambient, more than three current-carrying conductors in a raceway), you cannot read the answer from Table 310.12(A). You derate the conductor normally, starting from its own temperature column (90°C for THHN or XHHW-2), and the corrected ampacity, capped by the 75°C termination value, must still reach 83% of the rating. The ampacity correction and adjustment factors guide walks through that math.

Wire size for a 100 amp subpanel

A subpanel feeder is the most common trap on this topic. It is a feeder, it does not supply the entire dwelling load, so 310.12 is out. Size it from Table 310.16 at 100% of the load, and protect it under NEC 240.4.

Dwelling servicesupplies the entire houseMeterMain100 A0.83 × 100 = 83 A4 Cu or 2 AlSubpanel feedersupplies part of the loadMainpanelSub100 A100% = 100 A3 Cu or 1 Al
The same 100 A rating gives two different wire sizes depending on what the conductors supply.

Which temperature column? 110.14(C)

NEC 110.14(C)(1) sets the column you are allowed to use. For circuits rated 100 A or less, or conductors 14 AWG through 1 AWG, the default is the 60°C column, unless the equipment is listed and marked for 75°C. Most panelboards and breakers sold today are marked 60/75°C or 75°C, which lets you use the 75°C column with 75°C or 90°C conductors.

That gives you these options for a full 100 A feeder:

Conductor60°C ampacity75°C ampacityOK for 100 A?
4 AWG Cu70 A85 ANo
3 AWG Cu85 A100 AYes, at 75°C
2 AWG Cu95 A115 AYes
1 AWG Cu110 A130 AYes, even at 60°C
2 AWG Al75 A90 AOnly with 240.4(B), load ≤ 90 A
1 AWG Al85 A100 AYes, at 75°C
1/0 Al100 A120 AYes, even at 60°C

The termination temperature ratings guide (110.14(C)) explains why a 90°C THHN conductor is still sized from the 75°C column.

The next-size-up rule, and its limit

NEC 240.4(B) lets you protect a conductor with the next higher standard overcurrent device when the conductor's ampacity does not match a standard rating, the device is 800 A or less, and the circuit is not a multi-outlet branch circuit for cord-and-plug loads.

So 2 AWG aluminum (90 A) can go on a 100 A breaker only if the calculated load is 90 A or less. And 4 AWG copper (85 A) can never go on 100 A as a feeder: the next standard size above 85 A is 90 A, per NEC 240.6(A). See the full list in standard breaker sizes.

NM cable to a 100 A subpanel

Type NM cable is limited to the 60°C column by NEC 334.80, whatever the insulation inside it. At 60°C, 1 AWG copper is 110 A, so 1 AWG copper NM handles 100 A outright. 2 AWG copper NM (95 A) can be used on a 100 A breaker only through 240.4(B), with a calculated load of 95 A or less. Type SE cable (SER) used for interior wiring is different: under NEC 338.10(B)(4) it may use its 75°C rating, except where it is installed in thermal insulation, where it is limited to the 60°C column. So 1 AWG aluminum SER is a 100 A feeder in open joists but only 85 A where it runs through an insulated wall or attic.

Ground wire size for a 100 amp service or subpanel

A 100 A job usually needs one or two grounding conductors, and they come from two different tables. The equipment grounding conductor sizing guide and the grounding electrode conductor sizing guide cover each table in depth.

ConductorSized fromCopperAluminum
EGC in a 100 A feederNEC Table 250.122 (OCPD = 100 A)8 AWG6 AWG
GEC for 4 AWG Cu / 2 AWG Al serviceNEC Table 250.66 (2 AWG Cu or 1/0 Al or smaller)8 AWG6 AWG
GEC to ground rods onlyNEC 250.66(A)6 AWG max needed4 AWG max needed

Two details the exam likes:

  • Subpanel: the feeder is four-wire (two hots, neutral, EGC). The neutral and grounds are separated in the subpanel, and the main bonding jumper is only at the service. See main bonding jumper vs system bonding jumper.
  • Upsized feeders: if you increase the ungrounded conductors for voltage drop, NEC 250.122(B) requires a wire-type EGC to be increased in proportion to the circular-mil increase.

Worked examples, built like exam questions

Worked example

100 A dwelling service, copper

  1. 1

    The question

    A one-family dwelling has a 100 A, 120/240-volt single-phase service. The service-entrance conductors supply the entire load. No correction or adjustment factors apply. What is the minimum size copper THWN-2 service conductor?

  2. 2

    Check that 310.12 applies

    One-family dwelling, single-phase 120/240 V, entire load, 100 A is within 100 to 400 A. Yes.

  3. 3

    Apply 83%

    0.83 × 100 A = 83 A minimum ampacity.

  4. 4

    Table 310.16, 75°C column, copper

    6 AWG = 65 A (too small). 4 AWG = 85 A ≥ 83 A.

  5. ✓ Answer: 4 AWG copper.
Worked example

100 A feeder to a detached garage, aluminum

  1. 1

    The question

    A 100 A breaker in the house panel feeds a subpanel in a detached garage. Conductors are aluminum XHHW-2 in PVC conduit, terminals are rated 75°C, and the calculated load is 96 A. What size ungrounded conductors and EGC are required?

  2. 2

    Pick the rule

    The feeder supplies only the garage, not the entire dwelling, so 310.12 does not apply. Size from Table 310.16 at 75°C.

  3. 3

    Conductors

    2 AWG Al = 90 A. The load is 96 A, which is more than 90 A, so 240.4(B) cannot help. 1 AWG Al = 100 A ≥ 96 A.

  4. 4

    EGC

    Table 250.122 at 100 A: 8 AWG Cu or 6 AWG Al. PVC is not an EGC, so a wire-type EGC is required.

  5. ✓ Answer: 1 AWG aluminum ungrounded conductors, an aluminum neutral sized for the neutral load, and a 6 AWG aluminum EGC.
Worked example

Hot attic: does 3 AWG THHN still work?

  1. 1

    The question

    A 100 A subpanel feeder uses three current-carrying 3 AWG copper THHN conductors in a raceway through an area with a 40°C (104°F) ambient. Terminals are rated 75°C. Is 3 AWG still enough?

  2. 2

    Start at 90°C

    THHN is a 90°C conductor: 3 AWG at 90°C = 115 A.

  3. 3

    Correct for ambient

    Ambient correction factor for a 90°C conductor at 36 to 40°C = 0.91. 115 × 0.91 = 104.65 A.

  4. 4

    Check the termination limit

    At the 75°C terminals, 3 AWG copper is limited to 100 A. The usable ampacity is the lower value, 100 A.

  5. ✓ Answer: Yes. 100 A usable ampacity is enough for a 100 A feeder.

Voltage drop on a long 100 amp feeder

Table 310.16 only protects the insulation from heat. It does not guarantee usable voltage at the far end. The NEC treats voltage drop for feeders as a recommendation in informational notes (3% on a feeder, 5% feeder plus branch circuit), not a requirement, but long runs are where customers notice it.

Example: 3 AWG copper (52,620 cmil), 150 ft one way, 80 A load, 240 V, K = 12.9:

VD = (2 × 12.9 × 80 × 150) ÷ 52,620 = 309,600 ÷ 52,620 = 5.88 V, which is 5.88 ÷ 240 = 2.45%.

Run the full method in the voltage drop formula guide and read where the 3% and 5% come from.

Exam-style practice

Exam-style question

A feeder from a dwelling's main panel supplies a 100 A subpanel in an addition. Terminals are rated 75°C. What is the minimum size copper conductor for a 100 A rated feeder?

Pick an answer to see the explanation.

Exam-style question

A one-family dwelling has a 100 A, 120/240-volt service. The service conductors supply the entire load. What is the minimum ampacity required of the service conductors?

Pick an answer to see the explanation.

Exam-style question

What is the minimum size copper equipment grounding conductor for a feeder protected by a 100 A circuit breaker?

Pick an answer to see the explanation.

Mistakes that cost points

Using 83% for a subpanel. 310.12 only applies to conductors that carry the entire dwelling load.

Using 80% instead of 83%. The dwelling factor is 83%. 80% is a different idea, tied to continuous loads.

Reading the 90°C column for the final answer. The 90°C column is for derating math. The final ampacity is limited by the terminations, usually 75°C.

Forgetting that NM is 60°C. Cable type changes the column, not just the conductor.

Sizing the EGC from the conductor size. Table 250.122 is based on the breaker rating. Table 250.66 is based on the service conductor size.

How to find this fast in the code book

On exam day you need three spots: NEC 310.12 (right before the ampacity tables), NEC Table 310.16, and NEC Table 250.122. Tab all three. Most 100 A questions are answered by asking one thing first: "Does this conductor carry the entire dwelling load?"

For the next size up, read the 200 amp service wire size guide or the 60 amp subpanel wire size guide. The full code text is free to read on the NFPA free access page. Then test yourself under the clock with the free journeyman electrician practice test.