The 125 amp wire size for a feeder that must carry a full 125 A is 1 AWG copper or 2/0 aluminum, read from the 75°C column of Table 310.16. If the calculated load is lower, the next-size-up rule lets you use 2 AWG copper (up to a 115 A load) or 1/0 aluminum (up to a 120 A load) on a 125 A breaker. For a dwelling service that carries the entire house, the 83% rule brings it to 2 AWG copper or 1/0 aluminum.
125 A sits right where three rules meet: the 110.14(C) column switch above 100 A, the next-size-up rule, and the dwelling 83% rule. This guide shows how each one changes the answer, with worked examples and exam-style questions.
125 amp wire size chart
All ampacities come from NEC Table 310.16. "Max load" is the largest calculated load you can put on that conductor with a 125 A breaker.
| Conductor | 60°C | 75°C | 90°C | With a 125 A breaker |
|---|---|---|---|---|
| 3 AWG Cu | 85 A | 100 A | 115 A | Not permitted |
| 2 AWG Cu | 95 A | 115 A | 130 A | Max load 115 A (240.4(B)) |
| 1 AWG Cu | 110 A | 130 A | 145 A | Full 125 A |
| 1/0 Cu | 125 A | 150 A | 170 A | Full 125 A |
| 1 AWG Al | 85 A | 100 A | 115 A | Not permitted |
| 1/0 Al | 100 A | 120 A | 135 A | Max load 120 A (240.4(B)) |
| 2/0 Al | 115 A | 135 A | 150 A | Full 125 A |
The 75°C column is the one that normally applies at 125 A, as explained below. For the layout of the full table, see the wire ampacity chart guide.
Why 125 A uses the 75°C column
NEC 110.14(C)(1) sets the temperature column you may use, based on the weakest link: the terminals.
- (a) Circuits rated 100 A or less, or conductors 14 through 1 AWG: 60°C, unless the equipment is listed and marked for 75°C.
- (b) Circuits rated over 100 A, or conductors larger than 1 AWG: 75°C, as long as the conductor is rated 75°C or higher.
A 125 A feeder is over 100 A, so the 75°C column applies with THHN/THWN-2, XHHW-2 or SER. You never read the 90°C column for the final answer; it is only the starting point for correction and adjustment. The termination temperature ratings guide walks through every case.
The next-size-up rule at 125 amps
NEC 240.4(B) allows the next higher standard overcurrent device when all of these are true:
- The conductor is not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads.
- The conductor's ampacity does not correspond to a standard rating.
- The next higher standard rating is 800 A or less.
The standard sizes around this range, from NEC 240.6(A), are 100, 110, 125, 150 A. So:
- 2 AWG Cu = 115 A, not standard → next is 125 A. ✓
- 1/0 Al = 120 A, not standard → next is 125 A. ✓
- 3 AWG Cu = 100 A, is standard → max breaker 100 A. ✗
- 1 AWG Al = 100 A, is standard → max breaker 100 A. ✗
The catch: the conductor must still carry the calculated load. 240.4(B) moves the breaker up, not the ampacity. See standard breaker sizes and the NEC 240.4 guide for the full rule.
Continuous loads: the 125% step
For feeders, NEC 215.2(A) requires the conductor ampacity to be at least the noncontinuous load plus 125% of the continuous load, and NEC 215.3 applies the same 125% to the feeder breaker. Services follow the same logic in NEC 230.42(A). A continuous load runs for 3 hours or more.
125 A feeder with continuous load
- 1
The question
A feeder to a commercial panel supplies 80 A of continuous lighting load and 20 A of noncontinuous load, 75°C terminals. What is the minimum aluminum conductor and breaker size?
- 2
Minimum conductor ampacity
(80 × 1.25) + 20 = 100 + 20 = 120 A.
- 3
Table 310.16, 75°C, aluminum
1 AWG Al = 100 A (too small). 1/0 Al = 120 A ≥ 120 A. ✓
- 4
Breaker
Minimum rating 120 A by 215.3. 120 A is not a standard size; the next standard size is 125 A, permitted by 240.4(B).
125 amp dwelling service: the 83% rule
NEC 310.12(A) lets service conductors supplying the entire load of a one-family dwelling or an individual dwelling unit, on a single-phase 120/240-volt system, have an ampacity of not less than 83% of the service rating, for services from 100 through 400 A. NEC 310.12(B) does the same for a feeder that carries the entire load of the unit.
125 A dwelling service
0.83 × 125 A = 103.75 A → 2 AWG Cu (115 A) or 1/0 Al (120 A)
That shortcut is off for subpanel feeders, commercial buildings and three-phase systems. The 200 amp service wire size guide explains every condition in detail, and the utility and local amendments can still require more.
Ground wire size for 125 amps
| Conductor | Table | Answer |
|---|---|---|
| EGC for a 125 A feeder | NEC Table 250.122, 200 A row | 6 AWG Cu or 4 AWG Al |
| GEC, service with 2 AWG Cu or 1/0 Al | NEC Table 250.66 | 8 AWG Cu or 6 AWG Al |
| GEC, service with 1 AWG Cu or 2/0 Al | NEC Table 250.66 | 6 AWG Cu or 4 AWG Al |
Table 250.122 jumps from the 100 A row to the 200 A row, so any device above 100 A and up to 200 A uses 6 AWG copper. Table 250.66 is based on the service conductor size, not the breaker. The EGC sizing guide and GEC sizing guide cover both tables in depth.
Derating: when 1 AWG copper is not enough
Heat and bundling reduce ampacity. Start from the conductor's own temperature column, apply the factors, then compare with the 75°C termination limit.
125 A feeder across a hot roof space
- 1
The question
A 125 A feeder uses 1 AWG copper THHN, three current-carrying conductors in a raceway, through an area with a 45°C (113°F) ambient. Terminals are 75°C. Is 1 AWG still adequate?
- 2
Start at 90°C
1 AWG Cu at 90°C = 145 A.
- 3
Ambient correction
For a 90°C conductor at 41 to 45°C, the factor is 0.87. 145 × 0.87 = 126.15 A.
- 4
Termination limit
1 AWG Cu at 75°C = 130 A. Usable ampacity = the lower value, 126.15 A.
More examples, including more than three current-carrying conductors, are in the ampacity correction and adjustment factors guide.
Exam-style practice
Exam-style question
A feeder is protected by a 125 A circuit breaker and must carry a calculated load of 124 A. Terminals are rated 75°C. What is the minimum size copper conductor?
Pick an answer to see the explanation.
Exam-style question
What is the minimum size aluminum equipment grounding conductor for a feeder protected by a 125 A overcurrent device?
Pick an answer to see the explanation.
Exam-style question
1/0 aluminum conductors with an ampacity of 120 A supply a feeder with a calculated load of 118 A. What is the maximum standard overcurrent device permitted?
Pick an answer to see the explanation.
Voltage drop on a long 125 amp feeder
Ampacity keeps the insulation safe; it does not keep the voltage up at the far end. The NEC's 3% feeder and 5% total figures are informational notes, not requirements, but long feeders are where they matter.
Example: 100 A load, 240 V, 200 ft one way. Circular mils from Chapter 9, Table 8; K = 12.9 for copper and 21.2 for aluminum.
- 1 AWG Cu (83,690 cmil): (2 × 12.9 × 100 × 200) ÷ 83,690 = 516,000 ÷ 83,690 = 6.17 V, or 2.57%.
- 2/0 Al (133,100 cmil): (2 × 21.2 × 100 × 200) ÷ 133,100 = 848,000 ÷ 133,100 = 6.37 V, or 2.65%.
Both stay under 3% at that distance. If you upsize for voltage drop, remember that NEC 250.122(B) requires a wire-type EGC to grow in proportion. The voltage drop formula guide has the full method.
Mistakes that cost points
Picking 2 AWG copper for a full 125 A. It is a 115 A conductor. It only reaches a 125 A breaker through 240.4(B), with a load of 115 A or less.
Using 1 AWG aluminum. 100 A at 75°C, and 100 A is a standard size, so its maximum breaker is 100 A.
Reading Table 250.122 at the 100 A row. 125 A is above 100 A, so use the 200 A row.
Applying 83% to a subpanel. 310.12 needs the entire dwelling load.
Forgetting continuous loads. Multiply continuous loads by 125% before you open Table 310.16.
How to find this fast in the code book
For 125 A questions you need four places: NEC 110.14(C), NEC Table 310.16, NEC 240.4(B) with the list in NEC 240.6(A), and NEC Table 250.122. The code text is free to read on the NFPA free access page.
→Why aluminum is two sizes biggerAluminum vs Copper Wire for Services and FeedersSmaller and larger feeders follow the same method: see the 60 amp subpanel wire size and the 100 amp service and subpanel guide. Then practice under the clock with the free journeyman electrician practice test.