Pull box sizing under NEC 314.28 comes down to two multipliers. For a straight pull, the box must be at least 8 times the trade size of the largest raceway long. For an angle pull, U pull or splice, the distance from each raceway entry to the opposite wall must be at least 6 times the largest raceway in the row, plus the trade sizes of the other raceways in that row on the same wall. Those rules apply when conductors are 4 AWG or larger.
The multipliers are easy to remember. What costs points on the exam is applying them to the right wall, the right row and the right raceways. This guide works through every case with diagrams and worked examples, then gives you exam-style questions built on the usual traps.
When 314.28 applies (and when box fill does)
There are two completely different methods for sizing boxes, and the conductor size decides which one you use.
| Conductors in the box | Method | Section |
|---|---|---|
| 6 AWG and smaller | Volume: count items × in³ per conductor | NEC 314.16 |
| 4 AWG and larger (insulated) | Dimensions: 8× or 6× the raceway trade size | NEC 314.28 |
The reason for the rule is bending space. Large conductors cannot be bent tightly without damaging insulation, and they need room to be pulled in and out of the box without being forced. Box fill for small conductors is covered in the box fill calculation guide. In practice, 314.28 boxes show up on services and feeders: the conductors from the 400 amp service wire size guide, or the large conductors described in service-entrance conductors, are exactly the sizes it covers.
Straight pulls: the 8× rule
A straight pull is when conductors enter one wall and leave through the opposite wall.
Straight pull, 314.28(A)(1)
Length ≥ 8 × trade size of the largest raceway
Only the largest raceway counts, and only in the direction of the pull. Nothing is added for the other raceways.
Straight pull with mixed raceways
- 1
The question
A pull box has a 3-inch and a 2-inch conduit entering the left wall and a 3-inch and a 2-inch conduit leaving the right wall, all carrying 4/0 AWG conductors in straight pulls. What is the minimum box length?
- 2
Largest raceway
3 inches.
- 3
Multiply
8 × 3 = 24 inches.
The 8× rule fixes only the length. The width must still be enough to fit the raceways and their locknuts and bushings, plus any angle-pull requirement in the other direction.
Angle pulls, U pulls and splices: the 6× rule
An angle pull is when conductors enter one wall and leave through an adjacent wall. A U pull is when they enter and leave through the same wall. A splice box is sized the same way.
Angle or U pull, 314.28(A)(2)
Distance to opposite wall ≥ (6 × largest raceway in the row) + sum of the other raceways in that row on the same wall
Rules that go with it:
- Measure from each wall that has raceway entries to the opposite wall.
- Work row by row. Each row is calculated individually, and the row that gives the largest distance is used.
- Only add the raceways on the same wall, in the same row.
Angle pull with three raceways per wall
- 1
The question
A junction box has one 3-inch and two 2-inch conduits in a single row on the left wall, and one 3-inch and two 2-inch conduits in a single row on the bottom wall. Conductors are 250 kcmil and make angle pulls between the two walls. Find the minimum horizontal and vertical dimensions.
- 2
Left wall to right wall
(6 × 3) + 2 + 2 = 18 + 4 = 22 inches.
- 3
Bottom wall to top wall
The bottom wall has the same raceways: (6 × 3) + 2 + 2 = 22 inches.
- 4
Spacing between same-conductor entries
The two 3-inch conduits carry the same conductors, so the distance between those entries must be at least 6 × 3 = 18 inches.
The distance between raceway entries
NEC 314.28(A)(2) also says the distance between raceway entries enclosing the same conductor must be at least 6 times the trade size of the larger raceway. Field references measure it between the nearest edges of the two entries. This gives the conductor a gradual bend inside the box instead of a sharp kink near the bushing.
U pulls
In a U pull, the conductors enter and leave through the same wall. The 6× rule still applies, measured from that wall to the opposite wall.
U pull with two 2½-inch conduits
- 1
The question
Two 2½-inch conduits on the same wall carry the same 3/0 AWG conductors in a U pull. No other raceways are on that wall. What is the minimum distance to the opposite wall, and the minimum spacing between the two entries?
- 2
Depth to the opposite wall
(6 × 2.5) + 2.5 = 15 + 2.5 = 17.5 inches.
- 3
Between the entries
6 × 2.5 = 15 inches.
Multiple rows on one wall
When raceways are stacked in more than one row on a wall, calculate each row by itself, then use the row that gives the largest distance.
Two rows on the same wall
- 1
The question
The left wall of a pull box has two rows of conduits for angle pulls. Row 1: two 3-inch. Row 2: three 2-inch. What is the minimum distance from the left wall to the right wall?
- 2
Row 1
(6 × 3) + 3 = 18 + 3 = 21 inches.
- 3
Row 2
(6 × 2) + 2 + 2 = 12 + 4 = 16 inches.
Cables, removable covers and smaller listed boxes
Cables. When cables enter the box instead of raceways, convert each cable to the minimum trade size raceway required for the number and size of conductors in the cable, then use that trade size in the formulas. That conversion uses the conduit fill calculation method from Chapter 9.
Entry opposite a removable cover. An exception to 314.28(A)(2) applies when a raceway or cable entry is in the wall of a box or conduit body opposite a removable cover. The distance from that wall to the cover may follow the one-wire-per-terminal column of NEC Table 312.6(A), which is much smaller than 6×.
Smaller listed boxes. NEC 314.28(A)(3) permits boxes or conduit bodies smaller than the 8× and 6× dimensions, but only for combinations of conductors that are less than the maximum conduit fill Chapter 9, Table 1 allows for the raceways used, and only when the box or conduit body is listed for, and permanently marked with, the maximum number and maximum size of conductors permitted. No marking, no reduction.
Large boxes. NEC 314.28(B) requires conductors in pull or junction boxes with any dimension over 6 ft to be cabled or racked up in an approved manner.
Exam-style practice
Exam-style question
A pull box has a 4-inch conduit entering one end and a 4-inch conduit leaving the opposite end, carrying 500 kcmil conductors. What is the minimum length of the box?
Pick an answer to see the explanation.
Exam-style question
For an angle pull, the left wall of a box has one 2½-inch, one 2-inch and one 1½-inch conduit in a single row. What is the minimum distance from the left wall to the opposite wall?
Pick an answer to see the explanation.
Exam-style question
Two 3-inch conduits containing the same conductors enter adjacent walls of a junction box. What is the minimum distance between the two raceway entries?
Pick an answer to see the explanation.
Mistakes that cost points
Using 314.28 for 6 AWG conductors. It starts at 4 AWG. Below that, use box fill.
Multiplying every raceway by 6. Only the largest raceway in the row is multiplied; the others are added.
Adding raceways from the wrong wall. Same wall, same row only.
Adding rows together. Each row is calculated separately; the larger result wins.
Forgetting the spacing between entries. Many questions ask for that 6× distance, not the box size.
How to find this fast in the code book
314.28 sits in Article 314, Part II, a few pages after box fill in NEC 314.16. Tab NEC 314.28(A) and write "8× straight, 6× angle/U + others same wall/row" on the tab. For a second explanation from a trade source, EC&M's NEC requirements for sizing junction boxes and pull boxes walks through the same rules.
→The pillar for raceway sizingConduit Fill Calculation: NEC Chapter 9, Step by StepPull boxes go hand in hand with raceway layout, so read conduit bending basics next, and see how many wires fit in 3/4 EMT for quick fill answers. Then test yourself with the free journeyman electrician practice test.