8 AWG wire ampacity is 40 amps, 50 amps or 55 amps for copper, depending on which temperature column of NEC Table 310.16 you are allowed to use. NM cable (Romex) is 40 A, THHN in conduit landed on 75°C-rated terminals is 50 A, and the 55 A figure is a 90°C value you use only as the starting point for derating.
The rest of this guide shows you how to tell which of the three numbers applies, with a decision chart, real circuits (ranges, EV chargers, subpanels), derating and voltage drop examples, and the exam traps built on this exact question.
8 AWG ampacity at a glance
| 8 AWG conductor | 60°C | 75°C | 90°C |
|---|---|---|---|
| Copper | 40 A | 50 A | 55 A |
| Aluminum / copper-clad aluminum | 35 A | 40 A | 45 A |
Source: 2023 NEC Table 310.16, not more than three current-carrying conductors, 30°C (86°F) ambient.
40 A
8 AWG Cu, NM cable or 60°C terminals
50 A
8 AWG Cu, THHN with 75°C terminals
55 A
8 AWG Cu, 90°C, derating only
Which number applies: the decision chart
The answer depends on three things: the wiring method, the termination ratings at both ends, and whether you are derating.
Case 1: NM cable (8/2, 8/3) is 40 A
Type NM conductors are 90°C rated, but NEC 334.80 says the ampacity of NM cable is that of 60°C conductors. For 8 AWG copper, that is 40 A. UF cable is held to 60°C as well by NEC 340.80.
Case 2: THHN/THWN in conduit with 75°C terminations is 50 A
For circuits of 100 A or less, or terminals marked for 14 through 1 AWG, NEC 110.14(C)(1)(a) starts you in the 60°C column, but lets you use the 75°C ampacity when the equipment is listed and identified for use with higher-rated conductors. Most modern breakers, panelboards and appliances are marked 60/75°C or 75°C. If both ends qualify, 8 AWG copper is 50 A.
If either end is unmarked or marked 60°C only, you are back to 40 A.
Case 3: 55 A is for derating
THHN is a 90°C insulation, so its 90°C ampacity of 55 A is where you start when you apply correction or adjustment factors. Whatever number you end up with must still not exceed the termination limit, normally 50 A. The details are in termination temperature ratings under 110.14(C).
8 AWG ampacity by wiring method
The same copper conductor ends up at different ampacities depending on how it is installed. Here is the quick lookup, assuming no derating and 75°C terminations where the method allows them:
| Wiring method | 8 AWG copper ampacity | Rule |
|---|---|---|
| NM-B cable (8/2, 8/3) | 40 A | NEC 334.80 |
| UF-B cable | 40 A | NEC 340.80 |
| TW or other 60°C conductors | 40 A | Table 310.16, 60°C column |
| THHN/THWN-2 in raceway | 50 A | 110.14(C)(1)(a)(3) |
| MC cable with 90°C conductors | 50 A | Table 310.16 with 110.14(C) |
| SE cable (SER) used for interior wiring, in thermal insulation | 40 A | NEC 338.10(B)(4) |
| Any method, one termination marked 60°C only | 40 A | 110.14(C)(1)(a)(2) |
Only the NM, UF and insulated-SE rows are cable-specific limits; every other row comes down to the termination rating. That is why the exam can ask the same "8 AWG" question three ways and expect three different answers.
How many watts can 8 AWG handle?
Amps times volts gives the maximum load. For a continuous load (three hours or more), the load is limited to 80% of the circuit rating:
| 8 AWG copper circuit | At 240 V | At 120 V | Continuous at 240 V |
|---|---|---|---|
| 40 A (NM or 60°C terminals) | 9,600 W | 4,800 W | 7,680 W (32 A) |
| 50 A (THHN, 75°C terminals) | 12,000 W | 6,000 W | 9,600 W (40 A) |
These are circuit limits, not a reason to skip the load calculation. Size from the nameplate or the calculated load, then check that the conductor and breaker cover it.
Breaker sizes for 8 AWG wire
8 AWG is not listed in NEC 240.4(D), so there is no special small-conductor cap. The general rule of NEC 240.4 applies: protect the conductor at its ampacity, with the next-size-up allowance of NEC 240.4(B) when the ampacity does not match a standard breaker size, the device is 800 A or less, and the circuit is not a multioutlet branch circuit supplying receptacles for cord-and-plug-connected portable loads.
| Situation | Ampacity | Typical breaker |
|---|---|---|
| 8 AWG NM cable | 40 A | 40 A |
| 8 AWG THHN, 60°C or unmarked terminals | 40 A | 40 A |
| 8 AWG THHN, 75°C terminals both ends | 50 A | 50 A |
| 8 AWG THHN, 6 conductors in conduit (55 × 0.80) | 44 A | 45 A permitted under 240.4(B) where its conditions are met |
| 8 AWG aluminum, 75°C terminals | 40 A | 40 A |
The full list of standard ratings, including 45 A, is in standard breaker sizes under 240.6(A).
Real circuits that use 8 AWG
Electric ranges
The NEC sets a 40-ampere minimum branch-circuit rating for household ranges rated 8¾ kW or more. A 40 A range circuit in 8/3 NM cable is the classic residential install. A 50 A range circuit needs 8 AWG THHN in conduit with 75°C terminals, or 6/3 NM. To figure out what a given range actually requires, see range load calculations with Table 220.55.
EV chargers
NEC 625.41 requires overcurrent protection for EV supply equipment to be sized for continuous duty, at not less than 125% of the equipment's maximum load. A charger that draws 40 A needs a 50 A circuit:
40 A EV charger in a garage
- 1
The question
A hardwired EV charger draws 40 A continuously at 240 V. What breaker and what copper conductor are required, (a) with THHN in EMT and 75°C terminals, and (b) with NM cable?
- 2
Breaker
40 A × 1.25 = 50 A minimum. Use a 50 A breaker.
- 3
(a) THHN in EMT
Need 50 A of ampacity. 8 AWG copper, 75°C column = 50 A. Works.
- 4
(b) NM cable
8 AWG NM = 40 A (60°C). Too small. 6 AWG NM = 55 A. Works.
Subpanels, welders, hot tubs and A/C units
8 AWG copper is common for 40 A and 50 A feeders to small subpanels, for welder receptacles and for spa equipment, always sized from the nameplate or the calculated load. For a subpanel, the same column logic applies; a 60 A subpanel needs a larger conductor, as shown in what size wire for a 60 amp subpanel.
Derating 8 AWG: worked examples
When there are more than three current-carrying conductors or the ambient is above 86°F, start from 55 A (90°C THHN) and apply the factors from Tables 310.15(B)(1)(1) and 310.15(C)(1).
Hot attic, three conductors
- 1
The question
Three 8 AWG THHN copper conductors run in a raceway through an area with a 45°C (113°F) ambient. Terminals are 75°C. What is the ampacity?
- 2
Correction
Table 310.15(B)(1)(1), 41–45°C row, 90°C column: 0.87. 55 × 0.87 = 47.85 A
- 3
Compare to the terminal limit
75°C column = 50 A. 47.85 A is lower.
Nine conductors in one conduit
- 1
The question
Nine current-carrying 8 AWG THHN copper conductors in one raceway at a 30°C ambient. What is the ampacity of each?
- 2
Adjustment
7–9 conductors: 70%. 55 × 0.70 = 38.5 A
For the full tables and the rules on counting neutrals, see ampacity correction and adjustment factors.
Voltage drop on 8 AWG
Longest one-way runs at or under 3% voltage drop for 8 AWG copper (16,510 cmil, K = 12.9, single-phase, rounded down):
| Load | At 120 V | At 240 V |
|---|---|---|
| 32 A | 71 ft | 143 ft |
| 40 A | 57 ft | 115 ft |
| 48 A | 47 ft | 95 ft |
K = 12.9 is a conventional approximation, so use these for planning and do the math for the actual job with the voltage drop formula. If the run is longer, go to 6 AWG and remember to increase the wire-type equipment grounding conductor proportionally under NEC 250.122(B).
8 AWG in conduit: stranding and fill
Two raceway rules come up with this size and no smaller one:
- 8 AWG is the size where stranding becomes mandatory in raceways. NEC 310.3(C) requires conductors 8 AWG and larger installed in raceways to be stranded, unless solid is specifically permitted or required elsewhere. Solid 8 AWG is still common as a bare grounding electrode conductor, which is not pulled in a raceway.
- Conduit fill. 8 AWG THHN has an area of 0.0366 in² (Chapter 9, Table 5). At 40% fill, that is 3 in 1/2-inch EMT, 6 in 3/4-inch EMT (5.82 rounds up under Chapter 9, Note 7) and 9 in 1-inch EMT. See conduit fill calculation for the method.
Other 8 AWG facts the exam uses
- Circular mils: 16,510 cmil (Chapter 9, Table 8).
- Box fill: 3.00 in³ per conductor (Table 314.16(B)(1)).
- Equipment grounding conductor: a 40 A or 50 A circuit needs at least 10 AWG copper (Table 250.122). 8 AWG copper becomes the EGC size at 100 A.
- Insulation: most 8 AWG building wire is dual-rated THHN/THWN-2. If you are not sure what the letters mean, see THHN vs THWN vs THWN-2.
- Aluminum: 8 AWG aluminum is a 40 A conductor at 75°C, which is why 6 AWG aluminum (50 A at 75°C) shows up where 8 AWG copper would be used. See aluminum vs copper wire.
Practice: 8 AWG questions
Exam-style question
A 50-ampere branch circuit is to be installed with Type NM cable. What is the minimum copper conductor size?
Pick an answer to see the explanation.
Exam-style question
What is the allowable ampacity of 8 AWG THHN copper conductors terminated on equipment listed for 75°C, with no derating?
Pick an answer to see the explanation.
Exam-style question
Six current-carrying 8 AWG THHN copper conductors are installed in one raceway at 30°C. All terminations are rated 75°C. What is the allowable ampacity of each conductor?
Pick an answer to see the explanation.
How to find it fast in the code book
Open Table 310.16 for the three ampacities, 110.14(C) for the column you can use, and 334.80 if the question mentions NM cable. Those three locations answer every 8 AWG question on the exam. For the whole table explained column by column, see the wire ampacity chart (NEC Table 310.16).
→Read the full chartWire Ampacity Chart: How to Read NEC Table 310.16Next steps
Compare 8 AWG with the size below it in 10 gauge wire amps, and see how the same column rules decide feeder sizes in wire size for a 100 amp service or subpanel. When the rules feel automatic, prove it under time pressure with the free journeyman practice test or the timed practice tests.