Transformer calculations on the journeyman exam come down to two skills. First, find the full-load current on each side: divide the kVA (in VA) by the voltage for single-phase, or by the voltage × 1.732 for three-phase. Second, apply Table 450.3(B) to size the overcurrent protection: 125% of primary current if you only protect the primary, or up to 250% on the primary when the secondary is also protected at 125%.
This guide covers both skills with every arithmetic step shown, adds the turns-ratio questions that usually come with them, and explains the secondary-conductor rule that trips up people who stop at Article 450.
Transformer basics you need for the math
A transformer moves power from one voltage to another. Apart from small losses, the VA going in equals the VA coming out. That one fact drives every calculation:
- If the voltage steps down, the current steps up by the same ratio.
- The kVA rating is the same on both sides; only volts and amps change.
- The turns ratio equals the voltage ratio: Np ÷ Ns = Vp ÷ Vs = Is ÷ Ip.
Turns ratio
Vp ÷ Vs = Np ÷ Ns = Is ÷ Ip
A 480 V to 120 V transformer has a 4:1 ratio. If the secondary carries 40 A, the primary carries 40 ÷ 4 = 10 A. Check with power: 120 × 40 = 4,800 VA = 480 × 10.
For three-phase systems, the line-to-line voltages are what you use in the current formula. If wye and delta voltages are still fuzzy, review delta vs wye before the protection section.
Full-load current: the two formulas
Single-phase
I = VA ÷ V
Three-phase
I = VA ÷ (V × 1.732)
Always convert kVA to VA first (× 1,000), and always use the line-to-line voltage of the side you are calculating. For a 480 V delta to 208Y/120 V transformer, the secondary voltage in the formula is 208, not 120.
Common three-phase sizes (480 V primary, 208 V secondary)
| kVA | Primary 480 V (A) | Secondary 208 V (A) |
|---|---|---|
| 30 | 36.1 | 83.3 |
| 45 | 54.1 | 124.9 |
| 75 | 90.2 | 208.2 |
| 112.5 | 135.3 | 312.3 |
| 150 | 180.4 | 416.4 |
Common single-phase sizes (480 V primary, 240 V secondary)
| kVA | Primary 480 V (A) | Secondary 240 V (A) |
|---|---|---|
| 10 | 20.8 | 41.7 |
| 15 | 31.3 | 62.5 |
| 25 | 52.1 | 104.2 |
| 37.5 | 78.1 | 156.3 |
| 50 | 104.2 | 208.3 |
Values are rounded to one decimal place. For a single-phase 120/240 V secondary, use 240 V for the full kVA.
Table 450.3(B): transformer overcurrent protection (1000 V and less)
NEC 450.3(B) sets the maximum overcurrent device for transformers rated 1000 V nominal or less, as a percentage of the transformer's rated current (not the load):
| Protection method | Primary current | Primary maximum | Secondary maximum |
|---|---|---|---|
| Primary only | 9 A or more | 125% (Note 1) | not required by 450.3 |
| Primary only | 2 A to less than 9 A | 167% | not required by 450.3 |
| Primary only | less than 2 A | 300% | not required by 450.3 |
| Primary and secondary | any | 250% | 125% (9 A or more, Note 1) or 167% (less than 9 A) |
Note 1: where 125% of rated current does not correspond to a standard rating of a fuse or breaker, the next higher standard rating is permitted. That allowance applies to the 125% values only. The 167%, 250% and 300% limits are absolute; round those down.
The other two notes matter less often but do show up:
- Note 2: where secondary protection is required, it may be up to six breakers or six sets of fuses grouped in one location, as long as their ratings added together don't exceed the single-device value.
- Note 3: a transformer with coordinated thermal overload protection by the manufacturer, arranged to interrupt the primary current, may have primary protection (in place of the 250% limit) up to 6 times rated current (impedance 6% or less) or 4 times (impedance over 6% up to 10%).
125%
primary only, next size up OK
250%
primary, when secondary is protected
125%
secondary, next size up OK
Worked example: 75 kVA, 480 V delta to 208Y/120 V
Full-load current
- 1
Primary
480 × 1.732 = 831.36. 75,000 ÷ 831.36 = 90.21 A
- 2
Secondary
208 × 1.732 = 360.26. 75,000 ÷ 360.26 = 208.19 A
Option A: primary-only protection
- 1
125% of primary current
90.21 × 1.25 = 112.77 A
- 2
Standard size?
112.77 A is not a standard rating. Note 1 permits the next higher standard size from 240.6(A): 125 A
Option B: primary and secondary protection
- 1
Primary maximum (250%)
90.21 × 2.50 = 225.53 A. 225 A is a standard size and does not exceed 225.53 A: 225 A
- 2
Secondary maximum (125%)
208.19 × 1.25 = 260.23 A. Not standard; Note 1 permits the next higher standard size: 300 A
Worked example: single-phase 25 kVA, 480 V to 120/240 V
Single-phase transformer protection
- 1
Full-load current
Primary: 25,000 ÷ 480 = 52.08 A. Secondary: 25,000 ÷ 240 = 104.17 A
- 2
Primary only
52.08 × 1.25 = 65.1 A → next standard size 70 A
- 3
Primary and secondary
Primary: 52.08 × 2.50 = 130.2 A → round down to 125 A. Secondary: 104.17 × 1.25 = 130.2 A → next higher standard size 150 A
Notice that 130.2 A appears twice, but the answers differ: 125 A for the primary (250% is a hard maximum) and 150 A for the secondary (125% gets Note 1's next size up). That contrast is a favorite exam setup.
Secondary conductors: the rule that comes after 450.3
Sizing the transformer's protection is not the end. The secondary conductors leave the transformer with no overcurrent device at their supply end, so they fall under NEC 240.21(C):
- 240.21(C)(1): a single-phase transformer with a 2-wire secondary, or a three-phase delta-delta with a 3-wire secondary, may have its secondary conductors protected by the primary device, provided the primary device does not exceed the secondary conductor ampacity multiplied by the secondary-to-primary voltage ratio (see also NEC 240.4(F)).
- 240.21(C)(2): the 10-foot secondary conductor rule.
- 240.21(C)(6): the 25-foot secondary conductor rule, with its own sizing condition.
- Other subsections cover industrial installations, outside secondary conductors and secondary conductors from a feeder-tapped transformer.
A 208Y/120 V or 120/240 V secondary is neither 2-wire nor delta-delta 3-wire, so its conductors can never rely on the primary device alone. The tap rules guide explains the 10- and 25-foot rules with their sizing conditions.
→Secondary conductor length limitsFeeder Tap Rules: The 10-Foot and 25-Foot Taps (NEC 240.21)For the grounding side, see main bonding jumper vs system bonding jumper and grounding electrode conductor sizing.
Going the other way: what kVA does the load need?
Some questions give you the load and ask for the transformer. Rearrange the same formulas:
Required kVA
Single-phase: V × I ÷ 1,000 · Three-phase: V × 1.732 × I ÷ 1,000
Sizing a transformer for a 150 A, 208Y/120 V load
- 1
Calculate the kVA
208 × 1.732 × 150 = 360.26 × 150 = 54,039 VA = 54.0 kVA
- 2
Pick a standard size
Common three-phase dry-type ratings around that value are 45 kVA and 75 kVA. 45 kVA is too small, so choose 75 kVA
Use the calculated load from Article 220 (after demand factors) as the current, not the sum of every breaker in the panel. The dwelling load calculation shows how that number is built for houses.
Mistakes that cost points on transformer questions
Forgetting 1.732 on three-phase (or dividing by 3). Three-phase current is VA ÷ (V × 1.732).
Using 120 V for a 208Y/120 V secondary. Use line-to-line voltage for three-phase kVA.
Rounding the 250% primary up. Only the 125% values get Note 1's next size up.
Sizing protection from the load instead of the transformer rating. Table 450.3(B) uses rated current.
Stopping at 450.3. Secondary conductors also need 240.21(C) protection.
Applying Table 450.3(B) to medium-voltage units. Transformers over 1000 V use Table 450.3(A).
Exam-style questions
Exam-style question
What is the full-load secondary current of a 45 kVA, three-phase transformer with a 208Y/120 V secondary?
Pick an answer to see the explanation.
Exam-style question
A 112.5 kVA, 480 V three-phase transformer has primary-only protection. What is the maximum standard-size primary overcurrent device?
Pick an answer to see the explanation.
Exam-style question
A 75 kVA, 480 V to 208Y/120 V transformer has primary and secondary protection. What is the maximum standard-size secondary overcurrent device?
Pick an answer to see the explanation.
Exam-style question
A single-phase transformer steps 480 V down to 120 V. The secondary load is 40 A. Ignoring losses, what is the primary current?
Pick an answer to see the explanation.
Where transformer calculations show up next
Transformers sit between the service-entrance conductors and the panels they feed, so expect them in feeder and service questions as well as in standalone items. Brush up on the three-phase side with single-phase vs three-phase power, and keep the standard breaker sizes list tabbed, because every 450.3(B) answer depends on it. If your load questions start from a building rather than a transformer, the dwelling load calculation guide is the pillar for this whole series.
Table 450.3(B) and its notes are in NFPA 70, available through the NFPA 70 page. Then time yourself on transformer questions with a free journeyman practice test.