Delta vs wye is about how the three windings of a transformer or the three elements of a load are connected. In a wye, one end of each winding ties to a common neutral, so the voltage between lines is 1.732 (√3) times the winding voltage: 120 volts per winding gives 208 volts line to line. In a delta, the windings form a closed loop with no neutral point, so the line voltage equals the winding voltage, and the line current is 1.732 times the current in each winding.

This guide shows both connections side by side, the common US voltages each produces, the transformer combinations you will see, the NEC grounding rules that depend on them, and how to tell which one you are looking at with a meter. Worked examples cover the calculations the journeyman exam asks for.

Delta vs wye: the core difference

ABCN (neutral)WYEE line = 1.732 × E phaseI line = I phaseABCDELTAE line = E phaseI line = 1.732 × I phase
Wye (left) and delta (right): where the windings connect and how line values relate to phase values.

Two terms make every calculation clear:

  • Phase values are measured across one winding (or one load element).
  • Line values are measured between the line conductors (or in a line conductor).
WyeDelta
VoltageE line = 1.732 × E phaseE line = E phase
CurrentI line = I phaseI line = 1.732 × I phase
Neutral availableYes (center point)No (except high-leg delta center tap)
Common US systems208Y/120, 480Y/277240 V, 480 V 3-wire; 240/120 V high-leg

The 1.732 comes from the 120-degree spacing between the three phases. Two voltages 120 degrees apart do not add like numbers; their difference is √3 times either one. The single-phase vs three-phase guide shows the phasor picture behind it.

The wye (star) connection

In a wye, each winding sits between one line and the neutral. Each winding's voltage is the line-to-neutral voltage, and the voltage between any two lines is that times 1.732:

  • 120 V × 1.732 = 208 V (the 208Y/120-volt system)
  • 277 V × 1.732 = 480 V (the 480Y/277-volt system)

The current in each line is the same current that flows in its winding, because the line and the winding are in series.

Why commercial buildings use it: the neutral gives you two voltages from one service. A 208Y/120 panel feeds 3-phase motors at 208 V and receptacles at 120 V. A 480Y/277 service feeds motors at 480 V and fluorescent or LED lighting at 277 V, with a step-down transformer for 120-volt loads.

The neutral in a wye. On a perfectly balanced linear load, the three phase currents cancel and the neutral carries zero. On real loads it carries the imbalance. With heavy nonlinear loads (computers, LED drivers, VFDs), triplen harmonic currents add in the neutral instead of canceling, which is why the NEC counts the neutral as a current-carrying conductor on a 3-phase, 4-wire wye when the major portion of the load is nonlinear (NEC 310.15(E)(3)).

The delta connection

In a delta, each winding connects between two lines. The voltage across a winding is the line voltage. But each line conductor is fed by two windings at once, so the line current is the vector sum of two winding currents: 1.732 times the current in one winding.

Worked example

Delta-connected heater

  1. 1

    The question

    A 3-phase heater has three 10 kW elements connected in delta on a 240-volt system. What is the current in each element, and in each line?

  2. 2

    Element (phase) current

    Each element sees the full 240 V. I = P ÷ E = 10,000 ÷ 240 = 41.7 A.

  3. 3

    Line current

    I line = 1.732 × I phase = 1.732 × 41.67 = 72.2 A.

  4. 4

    Check with the 3-phase power formula

    Total 30,000 W ÷ (1.732 × 240) = 72.2 A. Same answer.

  5. ✓ Answer: 41.7 A in each element, 72.2 A in each line conductor.

Delta systems come in three forms in the field:

Delta typeWhat is groundedVoltage to ground
Ungrounded delta (3-wire)NothingNot fixed; ground detectors required
Corner-grounded deltaOne phase conductor0 V on the grounded phase, line voltage on the other two
High-leg (center-tapped) deltaCenter tap of one winding (neutral)120 V on two phases, about 208 V on the high leg

The high-leg delta is important enough to have its own guide. Ungrounded systems from 120 to 1000 volts need ground detectors under NEC 250.21(B), because a first ground fault does not trip anything.

A delta winding also has a useful side effect: triplen harmonic currents circulate inside the closed loop instead of flowing out on the lines. That is one reason the delta-wye transformer is the workhorse of commercial distribution.

Common US system voltages at a glance

SystemConnectionLine-to-lineLine-to-neutral or to ground
120/240 V single-phaseCenter-tapped single winding240 V120 V
208Y/120 VWye208 V120 V
480Y/277 VWye480 V277 V
240/120 V high-legDelta, center-tapped240 V120 V (A and C), about 208 V (B)
240 V or 480 V 3-wireDelta240 or 480 VDepends on grounding
600Y/347 VWye600 V347 V

The "Y" in a system name always means wye: 208Y/120 reads "208 volts line to line, wye-connected, 120 volts line to neutral". A delta system is written without the Y, such as 240/120 V for the high-leg delta. The NEC uses these same nominal values in calculations (NEC 220.5(A)); why they are 120 and not 110 is covered in 110 vs 120 volts.

Power formulas: the same for both

For any balanced 3-phase load:

3-phase power (delta or wye)

P = 1.732 × E line × I line × PF

and apparent power in kVA is the same formula without the power factor. You never need a "delta formula" and a "wye formula" if you work with line values. The connection only matters when a question asks about the current in a winding or the voltage across one element. For the power factor part, see power factor, kW and kVA.

Worked example

Delta-wye transformer currents

  1. 1

    The question

    A 75 kVA, 3-phase transformer is connected 480 V delta primary to 208Y/120 V secondary. What is the full-load line current on each side?

  2. 2

    Secondary

    I = 75,000 ÷ (1.732 × 208) = 208.2 A.

  3. 3

    Primary

    I = 75,000 ÷ (1.732 × 480) = 90.2 A.

  4. 4

    Inside the primary delta winding

    Winding current = line current ÷ 1.732 = 90.2 ÷ 1.732 = 52.1 A. Exam questions rarely ask this, but it is how the transformer manufacturer sizes the winding.

  5. ✓ Answer: About 208 A on the 208Y/120 secondary and 90 A on the 480 V primary lines.

The protection side of that transformer is in transformer calculations and 450.3.

Transformer connections you will see

Primary–secondaryWhere it is usedNotes
Delta–wyeCommercial step-down (480 V to 208Y/120) and many utility servicesCreates a neutral; 30° phase shift between primary and secondary
Wye–deltaStep-up applications, some industrial suppliesNo neutral on the secondary
Delta–deltaOlder industrial and the high-leg delta serviceCan run as open delta if one unit fails
Wye–wyeLess commonNeeds attention to grounding and harmonics
Open delta (two transformers)Rural and small 3-phase services, high-leg servicesCapacity is 57.7% of a full three-transformer bank

The 30-degree shift in a delta-wye transformer is why you cannot parallel a delta-wye unit with a delta-delta unit: their secondary voltages are out of phase.

Grounding: what the NEC requires for each

NEC 250.20(B) requires an ac system of 50 to 1000 volts to be grounded when any of these is true:

  1. It can be grounded so the maximum voltage to ground on the ungrounded conductors does not exceed 150 volts (120/240 V single-phase, 208Y/120 V).
  2. It is a 3-phase, 4-wire wye where the neutral is used as a circuit conductor (480Y/277 V, 208Y/120 V).
  3. It is a 3-phase, 4-wire delta where the midpoint of one phase winding is used as a circuit conductor (the high-leg delta).

A 480-volt, 3-phase, 3-wire delta meets none of those conditions, so it is permitted to be ungrounded (with ground detectors) or corner-grounded. The difference between the grounded conductor and the equipment grounding conductor matters here; see grounded vs grounding conductor.

How to tell delta from wye in the field

Read the transformer or switchboard nameplate first: a "Y" in the voltage rating means wye. If there is no nameplate, a meter will tell you:

ReadingWye (208Y/120)High-leg delta (240/120)Corner-grounded delta (480)
A–B, B–C, A–C208, 208, 208240, 240, 240480, 480, 480
A–N120120No neutral
B–N120about 208No neutral
C–N120120No neutral
Phase to ground120 each120, about 208, 1200 on the grounded phase, 480 on the others

Practice: delta vs wye exam questions

Exam-style question

In a 480Y/277-volt wye system, what is the voltage across each transformer secondary winding?

Pick an answer to see the explanation.

Exam-style question

A delta-connected 3-phase load draws 50 A in each phase element. What is the line current?

Pick an answer to see the explanation.

Exam-style question

Which of the following systems is NOT required to be grounded by NEC 250.20(B)?

Pick an answer to see the explanation.

The mistakes that cost points

Applying 1.732 to the wrong quantity. Wye: voltage changes, current does not. Delta: current changes, voltage does not.

Dividing when you should multiply. Line-to-line is always the bigger voltage in a wye (120 to 208). Line current is always the bigger current in a delta.

Mixing line and phase values in the power formula. Use line voltage and line current with 1.732, every time.

Assuming every 4-wire system is a wye. The high-leg delta is also 4-wire.

Using line voltage for voltage-to-ground questions. 208Y/120 is 120 V to ground.

Where to go next

Delta vs wye sits on top of the basics in basic electrical theory and the formulas in the electrical formulas cheat sheet. From here, read the high-leg delta guide for the special 4-wire delta, then test yourself on 3-phase questions with the free journeyman practice test.

→The 4-wire delta, explainedHigh-Leg Delta (Wild Leg): Voltage, Color Code and NEC Rules