A high leg delta (also called a wild leg, red leg or stinger leg) is a 3-phase, 4-wire delta system in which one transformer winding is center-tapped and grounded to provide a neutral. Two phases measure 120 volts to that neutral, but the third, the high leg, measures about 208 volts. The system gives a shop or small commercial building both 120/240-volt single-phase power and 240-volt 3-phase power from one service.
This guide shows where that 208 volts comes from, which loads each voltage can serve, and every NEC rule tied to the high leg: orange marking, B-phase position, the caution label, breaker ratings and working space. Exam questions on this topic are easy points once you know the five rules.
What a high leg delta is
The supply is a delta-connected transformer bank, often two or three single-phase transformers. One winding, usually a larger "lighting" transformer, has a center tap. That center tap is grounded and run as the neutral. The other windings supply the 3-phase "power" part of the load.
Every side of the delta is 240 volts. The neutral sits in the middle of the A–C side, so A and C are each 120 volts from it, exactly like a normal 120/240-volt single-phase service. B is the far corner of the triangle.
Why the high leg reads about 208 volts
The voltage from the neutral to B is the height of an equilateral triangle with 240-volt sides:
High leg to neutral
240 × 0.866 = 120 × 1.732 = 207.8 V
That is why meters read "about 208". It is the same 1.732 that turns 120 volts into 208 volts in a wye system, but here it shows up between one phase and the neutral instead of between two phases. If that 1.732 still feels like magic, the delta vs wye guide and the single-phase vs three-phase guide walk through it.
120 V
A–N and C–N
≈ 208 V
B–N (the high leg)
240 V
between any two phases
What each voltage is used for
| Connection | Voltage | Use |
|---|---|---|
| A–N or C–N | 120 V | Receptacles, lighting, 120-volt equipment |
| A–C | 240 V single-phase | Water heaters, 240-volt single-phase equipment |
| A–B or B–C | 240 V single-phase | 240-volt loads (high leg used line to line only) |
| A–B–C | 240 V 3-phase | Motors, compressors, 3-phase equipment |
| B–N | about 208 V | Not used for loads |
All the 120-volt load comes off the A–C winding, which is why that transformer is larger than the others. The high leg is perfectly useful, but only line to line.
Closed delta and open delta banks
A utility can build the system two ways. A closed delta uses three single-phase transformers, one of them center-tapped. An open delta uses only two: the center-tapped "lighting" unit and one "power" unit. An open-delta bank can deliver only about 57.7% of the 3-phase capacity a full three-transformer bank of the same units would give, so it suits services where most of the load is single-phase and the 3-phase load is modest, such as a small shop with one or two motors.
Either way, the system is unbalanced by design: the A–C winding carries all the 120-volt load plus its share of the 3-phase load. That is normal, and it is why load calculations on these services put single-phase loads on A and C only.
The NEC rules for the high leg
| Rule | Section | What it requires |
|---|---|---|
| Orange marking | NEC 110.15 | Conductor or busbar with the higher voltage to ground marked orange or by other effective means, at each point where a connection is made if the neutral is also present |
| Service conductors | NEC 230.56 | Same orange (or other effective) marking on the service-entrance conductor with the higher voltage to ground, at each termination or junction point |
| B-phase position | NEC 408.3(E)(1) | In switchboards, switchgear and panelboards, the B phase is the one with the higher voltage to ground |
| Meter exception | NEC 408.3(E)(1), Exception | Equipment in the same section as the meter may match the metering phase arrangement |
| Caution label | NEC 408.3(F)(1) | Field marking: "CAUTION ___ PHASE HAS ___ VOLTS TO GROUND" |
| Must be grounded | NEC 250.20(B)(3) | A 3-phase, 4-wire delta with the midpoint of one winding used as a circuit conductor must be grounded |
B phase in the panel, C phase in the meter
NEC 408.3(E)(1) sets the bus arrangement A, B, C from front to back, top to bottom, or left to right, as viewed from the front, and makes B the high leg on a 3-phase, 4-wire delta. Utility metering equipment, however, is typically built with the high leg on the C (right-hand) position. The exception lets equipment in the same section as the meter follow the meter's arrangement. Everywhere else, the high leg lands on B.
That mismatch is why you have to identify the high leg at every termination: it may physically change position between the meter socket and the panelboard. Check your utility's service requirements for its meter-socket phasing.
Breakers, 120-volt loads and the slash-rating trap
In a 3-phase panelboard, single-pole spaces rotate A, B, C down each side. On a high-leg delta, every third single-pole space is on the high leg. A single-pole breaker in one of those spaces, connected to a 120-volt receptacle and the neutral, puts about 208 volts on that receptacle.
Breakers have a second problem. A breaker marked with a slash rating such as 120/240 V may only be applied where the voltage to ground of any conductor does not exceed the lower value and the voltage between conductors does not exceed the higher value (NEC 240.85). The high leg is about 208 volts to ground, more than 120, so a 120/240 V slash-rated breaker cannot be applied on it. Use breakers with a straight voltage rating suitable for the system for circuits that include the high leg.
How to identify the high leg in the field
Do not trust a panel schedule or tape color alone on an existing building. Confirm it with a meter, in this order:
- Read the labels. Look for the 408.3(F)(1) caution label on the panel and orange marking on the conductors at the main lugs.
- Measure each phase to neutral with a meter rated for the system. Two phases read about 120 V; the high leg reads about 208 V. Typical readings run a few volts either side of those values.
- Measure phase to phase. All three pairs should read about 240 V. If you see 208 V between phases instead, the system is a 208Y/120 wye, not a high-leg delta, and every phase is 120 V to neutral.
- Mark what you found. If the orange marking is missing at a termination you open, add it. If the caution label is missing, apply one.
| Meter reading | High-leg delta (240/120) | 208Y/120 wye |
|---|---|---|
| A to N | 120 V | 120 V |
| B to N | about 208 V | 120 V |
| C to N | 120 V | 120 V |
| Any phase to phase | 240 V | 208 V |
The fastest tell is phase to phase: 240 V means delta, 208 V means wye. The 208 V number appears in both systems, but in different places, which is exactly what exam writers exploit. The delta vs wye guide has the full comparison.
Single-phase 240 V loads that use the high leg
A 2-pole, 240-volt load can be connected A–B or B–C. It sees 240 V and works normally, because it never references the neutral. Designers still tend to put single-phase 240-volt loads on A–C when the lighting transformer has spare capacity, and spread larger ones across A–B and B–C to balance the power transformers. What you can never do is connect a 120/240-volt appliance that needs a neutral (a range or dryer with 120-volt controls) to a pair that includes B: its 120-volt parts would see 208 V.
Worked examples
High leg voltage
- 1
The question
A 240/120-volt, 3-phase, 4-wire delta has its neutral at the midpoint of the A–C winding. What is the nominal voltage from B to the neutral?
- 2
Apply the formula
120 × 1.732 = 207.8 V (or 240 × 0.866 = 207.8 V).
3-phase load on a high-leg service
- 1
The question
A 15 kW, 3-phase resistive heater is connected A–B–C on a 240/120-volt high-leg delta. What is the line current?
- 2
3-phase current
I = P ÷ (1.732 × E line) = 15,000 ÷ (1.732 × 240) = 36.1 A.
- 3
Does the high leg change it?
No. A 3-phase load connected line to line sees 240 V on all three phases. The 208 V only exists between B and the neutral.
Working space and color code on a high-leg system
Working space. The depth table in 110.26 uses voltage to ground. Because the high leg is about 208 volts to ground, high-leg delta equipment falls in the 151–600 volt row: 3 ft for Condition 1, 3½ ft facing a concrete wall (Condition 2), 4 ft facing other live parts (Condition 3). See working clearance under NEC 110.26.
Color code. Orange for the high leg is required. The NEC does not assign colors to the other phases; many electricians use black, orange and blue for A, B and C on 240/120-volt systems, but that is local custom. Where more than one nominal voltage system exists in a building, ungrounded conductors must be identified by phase and system with the method posted at each panelboard. The full rules are in the electrical wire color code guide.
Practice: high-leg delta exam questions
Exam-style question
On a 4-wire delta-connected system where the midpoint of one phase winding is grounded, the conductor with the higher phase voltage to ground shall be identified by:
Pick an answer to see the explanation.
Exam-style question
In a panelboard supplied by a 3-phase, 4-wire delta system, the phase with the higher voltage to ground shall be connected to which bus?
Pick an answer to see the explanation.
Exam-style question
A 120-volt lamp is connected from the high leg to the neutral of a 240/120-volt delta system. What voltage does it receive?
Pick an answer to see the explanation.
Exam-style question
A panelboard on a 240/120-volt, 3-phase, 4-wire high-leg delta faces a concrete wall. What is the minimum depth of working space?
Pick an answer to see the explanation.
The mistakes that cost points
Calling the high leg 240 V to ground. It is about 208 V to the neutral and to ground. 240 V is between phases.
Putting it on C in the panel. C is the usual position in the meter socket; B is required in panelboards and switchboards (outside the meter section).
Thinking orange is just custom. Orange (or other effective means) is required by 110.15. The other phase colors are custom.
Forgetting the label. 408.3(F)(1) requires the field-applied caution marking.
Using the 0–150 V working space row. The high leg puts the equipment in the 151–600 V row.
Where to go next
The high-leg delta is one of the three-phase configurations covered in basic electrical theory. Compare it with the wye systems in delta vs wye, then lock in the marking rules with the free journeyman practice test.
→Required colors vs customElectrical Wire Color Code: What the NEC Requires (and What's Just Custom)