The US electrical wire color code is simple: black, red and blue wires are hot, white or gray wires are neutral, and green or bare copper wires are ground. On 480-volt commercial systems, the hots are usually brown, orange and yellow with a gray neutral. Only some of this is actually required by the National Electrical Code: white or gray for the neutral, green or bare for the ground, and orange for the high leg of a delta system. The specific hot colors are a long-standing trade custom.
This guide answers the everyday question first (what each color means and what you can expect to find in a wall or panel), then gives the exact 2023 NEC rules in 200.6, 200.7, 250.119, 210.5(C), 215.12(C) and 110.15, and finally the standard color conventions for 120/240 V, 208Y/120 V and 480Y/277 V systems.
What each wire color means
| Color | What it usually is | Required or custom? |
|---|---|---|
| Black | Hot (ungrounded) conductor; L1 or phase A | Custom |
| Red | Hot; second leg of 240 V, a 3-way traveler, or phase B on 208Y/120 V | Custom |
| Blue | Hot; phase C on 208Y/120 V, also travelers and switch legs in conduit | Custom |
| White | Neutral (grounded conductor) | NEC color for the grounded conductor (200.6) |
| Gray | Neutral, often for a second system such as 480Y/277 V | NEC color for the grounded conductor (200.6) |
| Green or green/yellow | Equipment grounding conductor | Required for an insulated EGC (250.119) |
| Bare copper | Equipment grounding conductor or grounding electrode conductor | Permitted (250.119) |
| Orange | High leg of a 4-wire delta system, or phase B on 480Y/277 V | Required for the high leg (110.15); custom for 480 V |
| Brown | Phase A on 480Y/277 V | Custom |
| Yellow | Phase C on 480Y/277 V; also a common traveler or switch leg color | Custom |
Three rules sit underneath the table:
- White and gray are reserved for the grounded conductor (NEC 200.7(A)), with narrow exceptions.
- Green and green/yellow are reserved for equipment grounding; they cannot be used as a hot or a neutral (NEC 250.119).
- Any other color can be a hot. That is why you can find a pink or purple hot in a commercial building and it is still legal, as long as the building's identification scheme is followed.
Which colors the NEC actually requires
| Rule | What it requires | NEC 2023 |
|---|---|---|
| Grounded conductor identification | White, gray, or three white/gray stripes (plus marking at terminations for 4 AWG and larger) | 200.6 |
| Use of white and gray | Reserved for grounded conductors, with listed exceptions and re-identification rules | 200.7 |
| EGC identification | Bare, or green, or green with yellow stripes; green never used as a circuit conductor | 250.119 |
| Branch-circuit hots, more than one system | Identify by phase/line and system; post or document the method | 210.5(C) |
| Feeder hots, more than one system | Same, for feeders | 215.12(C) |
| High leg | Orange or other effective means wherever the neutral is also present | 110.15 |
The neutral: 200.6 and 200.7
Grounded conductors 6 AWG or smaller (NEC 200.6(A)) must have a continuous white or gray outer finish, or three continuous white or gray stripes along the entire length on insulation other than green.
Grounded conductors 4 AWG or larger (NEC 200.6(B)) can use the same methods, or be identified at the time of installation by a distinctive white or gray marking at the terminations, encircling the conductor. That is how a black 4/0 aluminum service conductor becomes a legal neutral: white tape at each end.
Two systems in one enclosure (NEC 200.6(D)): when grounded conductors of different systems are in the same raceway, box or enclosure, one system's neutral must be distinguishable from the other's. The usual answer: white for 208Y/120 V and gray for 480Y/277 V, or white with a colored stripe (other than green). The means of identification has to be documented in a manner readily available or permanently posted where the conductors of the different systems originate.
White used as a hot (NEC 200.7(C)(1)): a white or gray conductor that is part of a cable can be used as an ungrounded conductor if it is re-identified at each location where it is visible and accessible, by marking tape, painting or other effective means in a color other than white, gray or green. In a single-pole, 3-way or 4-way switch loop, the re-identified white may be used only as the supply to the switch, not as the return from the switch to the light.
The ground: 250.119
NEC 250.119 allows an equipment grounding conductor to be bare, covered or insulated. Individually covered or insulated EGCs must have a continuous outer finish that is green, or green with one or more yellow stripes. Conductors with green or green/yellow insulation shall not be used as ungrounded or grounded circuit conductors.
For 4 AWG and larger (NEC 250.119(A)), an insulated conductor of another color may be permanently identified as an EGC at each end and at every point where it is accessible, by stripping the insulation from the entire exposed length, coloring the insulation green at the termination, or marking it with green tape or green adhesive labels at the termination. Smaller individual conductors cannot be re-identified as grounds; the only exception is multiconductor cable in installations serviced only by qualified persons (NEC 250.119(B)).
The difference between the neutral and the ground is more than color; it is what each one carries. That is explained in grounded vs grounding conductor, and the bigger picture is in grounding vs bonding.
Hot conductors: 210.5(C) and 215.12(C)
The NEC does not assign colors to ungrounded conductors. It sets two different kinds of rules.
They must not look like a neutral or a ground. Because white and gray are reserved by NEC 200.7 and green by NEC 250.119, a hot must be some other color (or properly re-identified).
With more than one voltage system, they must be identified. Under NEC 210.5(C) for branch circuits and NEC 215.12(C) for feeders, where the premises wiring system has branch circuits or feeders supplied from more than one nominal voltage system, each ungrounded conductor must be identified by phase or line and system at all termination, connection and splice points. Permitted means include separate color coding, marking tape, tagging or other approved means. The method must be documented in a manner readily available or permanently posted at each branch-circuit panelboard or similar distribution equipment (for feeders, at each feeder panelboard or similar).
This is the rule that turns the common color conventions into something enforceable in a building with both 208Y/120 V and 480Y/277 V: the building picks a scheme (often black-red-blue and brown-orange-yellow) and posts it.
DC circuits. 210.5(C) and 215.12(C) also contain polarity identification rules for DC systems above 60 volts. The positive conductor is identified with red or a plus sign or the word POSITIVE or POS, and the negative with black or a minus sign or the word NEGATIVE or NEG, with marking methods that depend on conductor size. Check the subdivision for your edition before relying on details, since the DC requirements have been revised in recent cycles.
Identification in a building with two systems
- 1
The situation
A building has a 480Y/277 V service and a dry-type transformer supplying 208Y/120 V panels. Lighting circuits at 277 V and receptacle circuits at 120 V share some ceiling junction boxes.
- 2
Hots
More than one nominal voltage system → every ungrounded conductor identified by phase and system at all terminations, connections and splices (NEC 210.5(C)). Common scheme: brown/orange/yellow for 480Y/277 V, black/red/blue for 208Y/120 V.
- 3
Neutrals
Different systems' neutrals in the same box → distinguishable (NEC 200.6(D)). Common scheme: gray for 277 V circuits, white for 120 V circuits.
- 4
Posting
Document the scheme so it is readily available, or post it permanently at each branch-circuit panelboard, and do the same for feeders under NEC 215.12(C).
The orange high leg: 110.15
On a 4-wire delta system where the midpoint of one phase winding is grounded (the common 120/240 V high-leg or "wild-leg" delta), one phase measures about 208 V to ground instead of 120 V. Connect a 120 V load to it and the load is destroyed.
Related rules keep the high leg in a predictable place: in panelboards and switchboards it is generally the B phase (NEC 408.3(E)(1)), and the equipment must be field marked with a caution label stating which phase has the higher voltage to ground (NEC 408.3(F)(1)). The service-entrance conductor with the higher voltage to ground is also marked orange (NEC 230.56). The full explanation of the voltages is in high-leg delta, and the transformer connections behind it are in delta vs wye.
→Why one phase reads 208 V to groundHigh-Leg Delta (Wild Leg): Voltage, Color Code and NEC RulesNote the overlap: orange is the required high-leg marking on a 4-wire delta, and it is also the customary phase B color on 480Y/277 V systems, which have no high leg. In a building with both, the posted identification scheme under 210.5(C) is what prevents confusion.
Standard color conventions by system
These are the color schemes you will see on most jobs. They are conventions (and often specification or local code requirements), not NEC requirements, except where noted.
| System | Hots | Neutral | Ground |
|---|---|---|---|
| 120 V, 2-wire (from 120/240 V) | Black | White (required) | Green or bare (required) |
| 120/240 V, 1-phase, 3-wire | Black, red | White (required) | Green or bare (required) |
| 208Y/120 V, 3-phase, 4-wire | Black, red, blue | White (required: white or gray) | Green or bare (required) |
| 480Y/277 V, 3-phase, 4-wire | Brown, orange, yellow | Gray (required: white or gray) | Green or bare (required) |
| 120/240 V, 3-phase, 4-wire high-leg delta | Black, orange (high leg, required), red or blue | White (required: white or gray) | Green or bare (required) |
A memory aid many electricians use: "BOY" for 480 (brown, orange, yellow) and "black, red, blue" for 208. If a single panel's colors do not match the posted scheme, treat every conductor as unknown until you have tested it.
For the voltages behind these systems, see single-phase vs three-phase.
Wire colors outside the US: the IEC scheme
If you work on imported machinery, or you learned the trade in the UK or Europe, do not assume the colors mean the same thing. Europe and the UK use the harmonized IEC colors.
| Function | United States | UK and Europe (harmonized IEC colors) |
|---|---|---|
| Phase 1 / L1 | Black (custom) | Brown |
| Phase 2 / L2 | Red (custom) | Black |
| Phase 3 / L3 | Blue (custom) | Gray |
| Neutral | White or gray (required) | Blue |
| Ground | Green, green/yellow, or bare (required) | Green/yellow |
The trap is obvious: in IEC wiring, blue is the neutral, while in US wiring blue is a hot. Machines built to IEC standards often arrive with brown, black and gray phases and a blue neutral, so read the equipment's wiring diagram and test before connecting it to a US system. The UK adopted these colors in 2004, replacing red, yellow and blue phases with a black neutral, and older UK installations still show the old scheme. Canada has its own code (CSA C22.1); check it directly if you work there.
Cable jacket colors are a different code
Nonmetallic-sheathed cable (Romex-style NM-B) comes in colored jackets that tell you the conductor size, not the function. The common manufacturer scheme in the US is:
| NM-B jacket color | Conductor size | Typical circuit |
|---|---|---|
| White | 14 AWG | 15 A |
| Yellow | 12 AWG | 20 A |
| Orange | 10 AWG | 30 A |
| Black | 8 AWG and 6 AWG | Larger appliance circuits and feeders |
This is an industry convention adopted by cable manufacturers, not an NEC rule, and it applies to the outer jacket only. Inside, the conductor colors follow the rules above: black and red hots, white neutral, bare ground. To see which size goes on which breaker, read 12 vs 14 gauge wire.
Exam questions on wire colors
Exam-style question
On a 4-wire, delta-connected system where the midpoint of one phase winding is grounded, the conductor with the higher phase voltage to ground shall be marked with an outer finish that is:
Pick an answer to see the explanation.
Exam-style question
An insulated grounded conductor 6 AWG or smaller shall be identified by any of the following EXCEPT:
Pick an answer to see the explanation.
Exam-style question
Where a premises has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor shall be identified by:
Pick an answer to see the explanation.
Exam-style question
A conductor with green insulation may be used as:
Pick an answer to see the explanation.
Common wire color mistakes
Assuming hot colors are required. Black, red and blue are conventions. The NEC requires only that hots not be white, gray or green, plus identification where there is more than one system.
Using gray as a hot. Gray is a grounded conductor color under 200.6, not a phase color.
Taping a small conductor white or green. Re-identification at terminations is for 4 AWG and larger only (except the white-in-a-cable hot under 200.7(C)).
Using the re-identified white as the switch return. In a switch loop it is the supply only.
Confusing 480 V orange with the high-leg orange. Same color, different systems. Follow the posted scheme.
Trusting color instead of a meter. Always verify.
Find it fast in the code book
Neutral rules: NEC Article 200 (200.6, 200.7). Ground rules: NEC 250.119. Hot identification: NEC 210.5(C) for branch circuits and NEC 215.12(C) for feeders. High leg: NEC 110.15, with NEC 230.56 and NEC 408.3. OSHA carries the same principle into workplaces: 29 CFR 1910.304 requires grounded and equipment grounding conductors to be identifiable and distinguishable from all other conductors.
Wire colors connect to the whole grounding and bonding system; start from the grounding vs bonding hub for the rest. Then check yourself with the free journeyman electrician practice test.