The difference in grounded conductor vs grounding conductor is what each one carries. The grounded conductor is a circuit conductor that is intentionally grounded, almost always the white or gray neutral, and it carries the load's return current every time the circuit is on. A grounding conductor, such as the green or bare equipment grounding conductor, connects metal parts back to the source and carries current only when something goes wrong.

The two words differ by two letters, which is exactly why exams use them. This guide gives you the 2023 NEC definitions, the identification rules for each, where they are allowed to touch, and the field and exam mistakes that come from mixing them up.

The NEC definitions

All of these are in NEC Article 100 in the 2023 NEC:

  • Grounded conductor: a system or circuit conductor that is intentionally grounded.
  • Neutral conductor: the conductor connected to the neutral point of a system that is intended to carry current under normal conditions.
  • Equipment grounding conductor (EGC): the conductive path(s) that provides a ground-fault current path and connects normally non-current-carrying metal parts of equipment together and to the system grounded conductor or to the grounding electrode conductor, or both.
  • Grounding electrode conductor (GEC): a conductor used to connect the system grounded conductor or the equipment to a grounding electrode or to a point on the grounding electrode system.

Notice that "grounding conductor" on its own is shorthand. The NEC's working terms are equipment grounding conductor and grounding electrode conductor, and each has its own rules and sizing table.

Grounded conductorEquipment grounding conductorGrounding electrode conductor
Common nameNeutralGround, ground wireGround electrode wire
Carries current normally?YesNoNo
Carries current whenEvery time the load runsGround faultLightning, surges, some fault current
IdentificationWhite or gray (200.6)Green, green/yellow, or bare (250.119)Usually bare copper
ConnectsLoad back to the sourceMetal parts back to the sourceService or SDS to the electrodes
Sized byLoad (and 250.24(D) minimum at the service)OCPD rating, Table 250.122Service conductors, Table 250.66
Disconnected by a switch?Normally notNeverNever

For the sizing details, see equipment grounding conductor sizing and grounding electrode conductor sizing.

What each conductor carries

Service panelMBJ20 AMetal-casedapplianceHot (ungrounded)Grounded conductor (neutral)Equipment grounding conductorNormal: 12 A on hot12 A on neutral, 0 A on EGCFault: high current on EGCbreaker tripsGEC to electrode
Normal operation: load current returns on the grounded conductor. During a fault: current returns on the equipment grounding conductor, then crosses the main bonding jumper to the neutral.

Normal operation. A 120 V appliance draws 12 A. Current flows out on the hot (ungrounded) conductor and returns on the grounded conductor. The neutral carries the full 12 A. The EGC carries nothing.

During a ground fault. The hot touches the metal case. Current flows through the case, onto the EGC, back to the service, across the main bonding jumper to the neutral, and back to the transformer. Because the whole path is metal, the current is large enough to trip the breaker quickly. That fault path is the core idea in grounding vs bonding.

That is why the two conductors are treated so differently. The neutral is a current-carrying conductor that counts toward ampacity and must be sized for the load. The EGC is a safety path that must stay intact and unswitched, and is sized from the breaker so it can carry fault current briefly.

Not every grounded conductor is a neutral

On a 120/240 V single-phase system, the grounded conductor is connected to the transformer's center tap, the neutral point, so it is a neutral. Same for the common point of a 208Y/120 V or 480Y/277 V wye.

A corner-grounded delta system is the classic exception. There is no neutral point to ground, so one phase is intentionally grounded. That phase conductor is the grounded conductor, it must be identified white or gray, and it is not a neutral. Exam questions use this to test whether you know the definitions rather than the slang.

A 2-wire, 240 V circuit from a 120/240 V system has no grounded conductor at all: both conductors are ungrounded, and the only other conductor is the EGC.

How to identify the grounded conductor: 200.6 and 200.7

NEC 200.6(A) covers grounded conductors 6 AWG or smaller. They are identified by:

  • A continuous white outer finish, or
  • A continuous gray outer finish, or
  • Three continuous white or gray stripes along the entire length on other than green insulation.

NEC 200.6(B) covers grounded conductors 4 AWG or larger. The same methods apply, plus one more: at the time of installation, a distinctive white or gray marking at its terminations, encircling the conductor or its insulation. That is why you see black 4/0 aluminum with white tape at both ends used as the neutral on a service. For multiconductor cables, NEC 200.6(E) allows similar re-identification at terminations for 4 AWG and larger.

When two systems share an enclosure, such as 208Y/120 V and 480Y/277 V, NEC 200.6(D) requires their grounded conductors to be distinguished, for example white for one and gray for the other, or white with a colored stripe (not green), with the identification method documented or posted.

NEC 200.7 reserves white and gray for grounded conductors, with narrow exceptions. The most common one in the field is NEC 200.7(C)(1): the white conductor in a cable can be used as an ungrounded conductor if it is re-identified at each termination and wherever it is visible and accessible, with a color other than white, gray or green. In a switch loop, the re-identified white conductor may be used only for the supply to the switch, not as the return from the switch to the outlet.

How to identify the equipment grounding conductor: 250.119

NEC 250.119 allows the EGC to be bare, covered or insulated. If it is covered or insulated, it must have a continuous outer finish that is green or green with one or more yellow stripes. And the reverse rule: a conductor with green or green/yellow insulation shall not be used as an ungrounded or grounded circuit conductor.

For conductors 4 AWG and larger, NEC 250.119(A) permits an insulated conductor to be permanently identified as an EGC at the time of installation, at each end and at every point where it is accessible, by:

  1. Stripping the insulation from the entire exposed length,
  2. Coloring the insulation or covering green at the termination, or
  3. Marking the insulation or covering with green tape or green adhesive labels at the termination.

Smaller EGCs generally cannot be re-identified: a single black 12 AWG pulled in conduit cannot be taped green and called a ground. The narrow exception is NEC 250.119(B), which lets conductors in a multiconductor cable be re-identified as EGCs where conditions of maintenance and supervision ensure only qualified persons service the installation. Colors for every conductor, including the conventions for phase conductors, are in the electrical wire color code guide.

SizeGrounded conductor (white/gray)Equipment grounding conductor (green)
6 AWG and smallerFactory color or three stripes onlyFactory green or green/yellow, or bare
4 AWG and largerFactory color, stripes, or white/gray marking at terminationsFactory green, bare, or re-identified green at each end and where accessible

Where the neutral and ground may connect

The grounded conductor and the equipment grounding conductors are connected in one place per system:

  • At the service, through the main bonding jumper in the service disconnect enclosure (NEC 250.24(C)).
  • At a separately derived system such as a transformer, through the system bonding jumper (NEC 250.30(A)(1)).

Downstream, they stay apart. NEC 250.24(B) prohibits grounding connections to the grounded conductor on the load side of the service disconnect, and NEC 250.142(B) prohibits using the grounded conductor to ground equipment on the load side, except as permitted, for example for certain existing range and dryer circuits under NEC 250.140. Both jumpers are explained in main bonding jumper vs system bonding jumper.

→The one place neutral meets groundMain Bonding Jumper vs System Bonding Jumper: Where Neutral Meets Ground
Worked example

Spot the violations in a subpanel

  1. 1

    The situation

    A subpanel in a garage, fed from the house service with a four-wire feeder, has: the green bonding screw installed in the neutral bar; the feeder EGC landed on the neutral bar; and a single black 8 AWG conductor, pulled in the conduit and taped green at both ends, used as a branch-circuit EGC.

  2. 2

    Bonding screw

    Violation. The neutral-to-ground connection belongs only at the service; on the load side the neutral bar must be isolated (NEC 250.24(B), NEC 250.142(B)).

  3. 3

    EGC on the neutral bar

    Violation. The EGC lands on a separate equipment grounding bar bonded to the enclosure, not on the isolated neutral bar.

  4. 4

    Taped 8 AWG

    Violation. Individual conductors may be re-identified as EGCs only at 4 AWG and larger (NEC 250.119(A)). An 8 AWG EGC must be green, green/yellow, or bare.

  5. ✓ Answer: Three violations: remove the bonding screw, move the EGC to the ground bar, and replace the taped 8 AWG with a green, green/yellow or bare conductor.

Exam questions: grounded vs grounding

Exam-style question

A system or circuit conductor that is intentionally grounded is defined as the:

Pick an answer to see the explanation.

Exam-style question

A 4/0 AWG black insulated conductor is to be used as the grounded conductor of a service. How may it be identified?

Pick an answer to see the explanation.

Exam-style question

In a corner-grounded delta system, the intentionally grounded phase conductor is:

Pick an answer to see the explanation.

Exam-style question

A single insulated conductor run in a raceway may be re-identified as an equipment grounding conductor with green tape at each end and wherever accessible only if it is at least:

Pick an answer to see the explanation.

Common mistakes

Calling the neutral "the ground." On the exam, grounded means neutral (or another intentionally grounded conductor); grounding means EGC or GEC.

Bonding neutral and ground in a subpanel. One bond per system.

Assuming every grounded conductor is a neutral. Corner-grounded delta proves otherwise.

Re-identifying small EGCs with tape. Only 4 AWG and larger, except multiconductor cable under the qualified-person conditions of 250.119(B).

Using a white conductor as a switch return. In a switch loop, the re-identified white is the supply to the switch only.

Find it fast in the code book

Definitions: NEC Article 100. Grounded conductor identification and use: NEC Article 200, mainly 200.6 and 200.7. EGC identification: NEC 250.119, in Part VI of Article 250. The neutral-to-ground bond: NEC 250.24, NEC 250.28 and NEC 250.30 in Part II. Workplace rules mirror the same idea: OSHA's 29 CFR 1910.304 requires grounded and equipment grounding conductors to be identifiable and distinguishable from all other conductors.

This topic sits inside the grounding vs bonding hub. Once the vocabulary is automatic, try a timed free journeyman electrician practice test.