A Ufer ground is a concrete-encased electrode: at least 20 ft of 1/2-inch steel rebar or 4 AWG bare copper wire embedded in a concrete footing or foundation that sits in direct contact with the earth. The NEC covers it in 250.52(A)(3) and requires it to be used whenever it is present at a building. Because concrete holds moisture and touches a large area of soil, a Ufer usually outperforms a driven ground rod.

This guide covers where the name comes from, the exact 2023 NEC requirements, how to connect to it, why a vapor barrier disqualifies it, and how exams test it. By the end you will know whether a footing qualifies and what size conductor it needs.

What is a Ufer ground?

The NEC never uses the word "Ufer." Its term is concrete-encased electrode (often shortened to CEE). Electricians, inspectors and plan reviewers say "Ufer" after Herbert G. Ufer, whose field work proved the method.

The documented history is short and worth knowing:

  • 1942: footing electrodes were installed at 24 buildings in Arizona, near Tucson and near Flagstaff, with a target of 5 ohms maximum. Ufer recommended embedding No. 4 or larger copper in the building footing.
  • About 18 years of testing: the resistance was checked regularly with no servicing needed. In 1960 the readings ranged from 2.1 to 4.8 ohms, averaging 3.57 ohms, in dry desert soil where driven rods struggle.
  • 1968 NEC: concrete-encased electrodes first appeared in the Code, built on the 4 AWG copper concept. 1975 NEC: the steel reinforcing bar version was added.

Those figures come from two IAEI Magazine articles: Michael Johnston's concrete-encased electrodes and the grounding electrode system, which summarizes Ufer's IEEE paper, and Keith Lofland's concrete-encased electrodes: let's go vertical, which gives the Code editions. That 4 AWG copper from 1942 is still the copper option in NEC 250.52(A)(3) today.

Today the concrete-encased electrode is one of the eight electrode types in NEC 250.52(A), and in most new buildings it is the best electrode on site.

Why concrete makes a good electrode

A ground rod touches a thin column of soil around an 8 ft length of 5/8-inch steel. A footing touches the earth along its entire bottom and sides. Three things work in the Ufer's favor:

  1. Surface area. A footing presents far more contact area to the earth than any rod.
  2. Moisture. Concrete absorbs and holds moisture, so it stays conductive when the surrounding soil dries out.
  3. Depth and protection. The electrode sits below grade, protected from damage and from most frost and seasonal drying at the surface.

That is why the NEC does not ask a Ufer to pass a 25-ohm test or to be supplemented the way a single rod must be under NEC 250.53(A)(2). For the rod rules, see ground rod requirements.

NEC 250.52(A)(3): the concrete-encased electrode requirements

Broken down into a checklist:

RequirementRebar optionCopper option
Minimum length20 ft total20 ft
Minimum size1/2 in diameter (No. 4 bar)4 AWG bare copper
MaterialBare, zinc-galvanized, or other electrically conductive coated steelBare copper
SplicingPieces tied with usual steel tie wire, welded or exothermically weldedOne continuous conductor
Concrete coverAt least 2 inAt least 2 in
LocationHorizontal in a footing or foundation in direct contact with earth, or vertical foundation or structural members in direct contact with earthSame
Multiple CEEs at one buildingOnly one has to be bonded into the systemSame

Three details exam writers like:

  • Tie wire counts. Ordinary steel tie wire is an acceptable way to join rebar pieces into the 20 ft length. No welding is required.
  • Coating must be conductive. Galvanized rebar qualifies. Rebar with a nonconductive coating, such as epoxy-coated bar, does not meet the "bare, zinc-galvanized, or other electrically conductive coated" language.
  • Vertical counts too. A vertical foundation wall or pier in direct contact with the earth can qualify, not only a horizontal footing.
ServicepanelGradeFooting in contact with earth4 AWG Cu maxRebar stub-up250.68(C)(3)2 in min20 ft minimum1/2 in rebar or largeror 4 AWG bare copperno vapor barrier below
A concrete-encased electrode in a footing, with a rebar stub-up for the 4 AWG copper connection.

When a Ufer ground is required

NEC 250.50 requires all grounding electrodes described in 250.52(A)(1) through (A)(7) that are present at a building to be bonded together into the grounding electrode system. The concrete-encased electrode is 250.52(A)(3), so if a qualifying footing exists, it must be used.

The exception in 250.50 covers existing buildings: concrete-encased electrodes are not required to be part of the grounding electrode system where the rebar or copper is not accessible for use without disturbing the concrete. In other words, you do not have to jackhammer a footing on a service change.

In new construction, the timing problem is real. The electrode has to be identified and the connection point planned before the concrete is poured. Once it is poured with no stub-up and no connection, getting to the steel is the job of a jackhammer.

Vapor barriers and insulation: when concrete is not in contact with earth

An informational note to NEC 250.52(A)(3) explains that concrete installed with insulation, vapor barriers, films or similar items separating the concrete from the earth is not considered to be in direct contact with the earth.

That matters for slab-on-grade and insulated foundations. A slab poured over a poly vapor barrier is not a concrete-encased electrode, even if it is full of rebar. Look at the footing: if the footing itself is poured directly against the soil, it can still qualify even when the slab above it has a barrier.

Does this footing qualify? Quick scenarios

Use the 250.52(A)(3) checklist on each case. These are the situations that come up on plan review and on exam questions.

ScenarioQualifies?Why
24 ft of No. 4 (1/2 in) bare rebar, tied with steel tie wire, in a footing poured directly on soilYes20 ft or more, 1/2 in, tie wire is an accepted connection, earth contact
30 ft of No. 3 (3/8 in) rebar in a footingNoBar smaller than 1/2 in; use 4 AWG bare copper or larger bar instead
20 ft of 4 AWG bare copper laid in the footing, 3 in of concrete all aroundYesCopper option, 2 in or more of cover
Rebar in a slab poured over a poly vapor barrierNoBarrier separates the concrete from the earth
Epoxy-coated rebar in a footingNoCoating is not electrically conductive
Existing house, footing steel buried with no stub-up, service upgradeNot required250.50 exception: not accessible without disturbing the concrete

Connecting to a Ufer: stub-ups, clamps and 4 AWG copper

Conductor size: 250.66(B)

The portion of the grounding electrode conductor or bonding jumper connected only to a concrete-encased electrode is not required to be larger than 4 AWG copper (NEC 250.66(B)). That holds for a 100 A house or a 2000 A building. Aluminum is not practical for this connection: NEC 250.64(A) does not permit bare or covered aluminum GECs in direct contact with masonry or the earth. The full sizing method is in grounding electrode conductor sizing.

Worked example

Large service, small Ufer conductor

  1. 1

    The question

    A 600 A service uses two parallel sets of 350 kcmil copper. The electrodes are a concrete-encased electrode and the building's structural steel. Size the copper conductors.

  2. 2

    Equivalent area

    2 × 350 = 700 kcmil copper. Table 250.66, "Over 600 through 1100 kcmil" → 2/0 AWG copper.

  3. 3

    Structural steel

    No special limit → 2/0 AWG copper.

  4. 4

    Concrete-encased electrode

    NEC 250.66(B): the bonding jumper or GEC to the CEE alone is not required to be larger than 4 AWG copper.

  5. ✓ Answer: 2/0 AWG Cu to the steel, 4 AWG Cu to the Ufer. If one conductor continued from the Ufer on to the steel, it would have to be 2/0 Cu.

Connection methods

There are three common ways to connect:

  1. Rebar stub-up. NEC 250.68(C)(3) permits a rebar-type concrete-encased electrode with rebar extended to an accessible location above the foundation or footing, provided the extension is continuous with or tied to the electrode rebar, the extension is not in contact with the earth without corrosion protection, and the rebar is not used as a conductor to interconnect the electrodes of the grounding electrode system.
  2. Copper conductor out of the footing. With the 4 AWG bare copper option, the conductor laid in the footing can continue up and out as the GEC itself.
  3. Clamp inside the concrete. A clamp listed for concrete encasement attaches the GEC to the rebar before the pour (NEC 250.70). NEC 250.68(A) does not require connections to a concrete-encased or buried electrode to be accessible.

How to tell if a building has a Ufer ground

On an existing building you usually cannot see the electrode itself, only the connection. Look for these clues:

  • A conductor disappearing into concrete. A bare copper conductor (typically 4 AWG) coming out of the foundation wall, slab edge or a pier near the service, often inside the garage or right below the meter.
  • A rebar stub with a clamp. A short piece of rebar sticking out of the foundation with a listed clamp and a copper conductor on it.
  • The GEC routing. Follow the grounding electrode conductor from the service panel or meter. If one conductor goes into the concrete and another goes to rods or the water pipe, the one in the concrete is almost certainly the CEE connection.
  • Paperwork. Building plans, the foundation inspection record, or a "Ufer" or "CEE" note on the electrical permit.

If none of these exist and the footing steel cannot be reached without disturbing the concrete, the existing-building exception in NEC 250.50 applies, and the service is grounded with the other electrodes that are present, typically rods supplementing the water pipe.

Ufer ground vs ground rod

Ufer (concrete-encased electrode)Ground rod
NEC section250.52(A)(3)250.52(A)(5)
Minimum size20 ft of 1/2 in rebar or 4 AWG Cu8 ft, 5/8 in unless listed
Required when present?Yes (250.50)Installed when needed
25-ohm / supplement ruleNoYes, 250.53(A)(2)
Max conductor required4 AWG Cu (250.66(B))6 AWG Cu (250.66(A))
Can be added later?Only before the pourAnytime
Typical performanceLarge contact area, holds moistureDepends heavily on soil and moisture

A Ufer can also be the supplemental electrode that NEC 250.53(D)(2) requires for a metal underground water pipe, since the supplement can be any electrode from 250.52(A)(2) through (A)(8).

→The other common electrodeGround Rod Requirements: Length, Spacing and the 25-Ohm Rule

Exam questions on concrete-encased electrodes

Exam-style question

A concrete-encased electrode shall consist of at least ___ of steel reinforcing bar not less than 1/2 in in diameter.

Pick an answer to see the explanation.

Exam-style question

The grounding electrode conductor connected only to a concrete-encased electrode is not required to be larger than:

Pick an answer to see the explanation.

Exam-style question

The metallic components of a concrete-encased electrode shall be encased by at least ___ of concrete.

Pick an answer to see the explanation.

Common Ufer mistakes

Calling a slab over a vapor barrier a Ufer. Concrete separated from the earth does not qualify.

Pouring without a connection. If there is no stub-up, clamp or copper tail, the electrode is lost for practical purposes.

Using the stub-up rebar to interconnect electrodes. 250.68(C)(3) prohibits it.

Sizing the Ufer conductor from Table 250.66 alone. 4 AWG copper is the most it ever needs.

Assuming a Ufer needs a rod. The NEC does not require one; check local amendments.

Find it fast in the code book

Everything is in Part III of Article 250: the electrode in NEC 250.52(A)(3), the "if present" rule and the existing-building exception in NEC 250.50, conductor size in NEC 250.66(B), and connections in NEC 250.68 and NEC 250.70.