How many watts on a 20 amp circuit? A 20 amp breaker on a 120 volt circuit can supply 2,400 watts (20 A × 120 V). If the load runs for three hours or more, such as a space heater, EV charger or store lighting, keep it to 80%: 1,920 watts. A 15 amp breaker supplies 1,800 watts, or 1,440 watts continuous. On a 240 V circuit, double those numbers.

That answers the everyday question. This guide gives you the full chart for 15 to 50 A breakers, explains where the 80% comes from in the NEC, shows why watts and volt-amperes are not always the same, and works through the heater and appliance questions that show up on the journeyman exam.

Watts per breaker size: the chart

All values use nominal voltages and round to the watt. The 80% columns apply to continuous loads.

Breaker120 V max120 V at 80%240 V max240 V at 80%
15 A1,800 W1,440 W3,600 W2,880 W
20 A2,400 W1,920 W4,800 W3,840 W
30 A3,600 W2,880 W7,200 W5,760 W
40 A——9,600 W7,680 W
50 A——12,000 W9,600 W

40 and 50 A circuits at 120 V exist but are uncommon, so they are left out.

Watts at 120 V100%80% continuous15 A1,8001,44020 A2,4001,92030 A3,6002,880Watts = volts × amps · continuous = 80% of the rating
Watts available on 15, 20 and 30 A circuits at 120 V: full rating vs 80% for continuous loads.

The formula: watts = volts × amps

Single-phase power

Watts = Volts × Amps

That is the power formula, P = E × I, from Ohm's law and the power wheel. Rearranged, it tells you the current a load will draw:

Current from watts

Amps = Watts ÷ Volts

Two rules for using it correctly:

Use nominal voltage. NEC 220.5(A) says calculations use nominal system voltages such as 120, 120/240, 208Y/120, 240, 480Y/277 and 480 V. You may measure 118 V or 123 V at a receptacle, but the exam and the load calculation use 120 V. The background is in 110 vs 120 volts explained.

Three-phase adds √3. For a three-phase circuit, multiply by 1.732: a 20 A, 208 V three-phase circuit carries 208 × 20 × 1.732 = 7,205 VA. More in single-phase vs three-phase power.

Where the 80% comes from

People say "only load a breaker to 80%" as a rule of thumb, but in the NEC it comes from two specific places.

Continuous loads, NEC 210.20(A). A continuous load is one where the maximum current is expected to continue for 3 hours or more (Article 100). The branch-circuit breaker must be rated at least the noncontinuous load plus 125% of the continuous load. Since 1 ÷ 1.25 = 0.80, a standard breaker can carry a continuous load of only 80% of its rating. An exception allows 100% only when the whole assembly, including the breaker, is listed for 100% operation.

One plug-in appliance, NEC 210.23(B)(1). On 15 and 20 A circuits, any one cord-and-plug-connected appliance not fastened in place may not be rated more than 80% of the circuit: 12 A on 15 A, 16 A on 20 A. This applies whether or not the load is continuous.

A third limit covers hard-wired equipment: NEC 210.23(B)(2) caps fastened-in-place equipment other than luminaires at 50% of the rating (7.5 A or 10 A) when the circuit also feeds lights or plug-in loads.

Worked examples with real appliances

Worked example

Space heaters on a 20 A circuit

  1. 1

    The question

    A homeowner wants to run two 1,500 W portable heaters from receptacles on the same 20 A, 120 V circuit. Will it work?

  2. 2

    Current per heater

    1,500 ÷ 120 = 12.5 A. One heater is within the 16 A single-appliance limit of 210.23(B)(1).

  3. 3

    Both heaters

    2 × 12.5 = 25 A, more than the 20 A rating.

  4. ✓ Answer: No. One heater per 20 A circuit, with little else on it. Two heaters will trip the breaker.

The same heater on a 15 A circuit is an interesting case. 12.5 A is more than the 12 A that 210.23(B)(1) allows for one cord-and-plug appliance on a 15 A circuit. In practice that is why a heater in a bedroom on a 15 A circuit is the classic nuisance trip: the heater alone uses most of the circuit, and any lamp or charger pushes it over.

Worked example

Electric baseboard heat at 240 V

  1. 1

    The question

    A 4,000 W, 240 V baseboard heater is on its own branch circuit. Fixed electric space-heating equipment is considered a continuous load (NEC 424.4(B)). What is the minimum breaker, and the minimum copper conductor?

  2. 2

    Current

    4,000 ÷ 240 = 16.67 A.

  3. 3

    Apply 125%

    16.67 × 1.25 = 20.8 A. A 20 A breaker is too small; the next standard size is 25 A.

  4. 4

    Conductor

    12 AWG copper is limited to 20 A protection by 240.4(D), so it cannot go on a 25 A breaker. 10 AWG copper (30 A at 60°C) works.

  5. ✓ Answer: 25 A, 2-pole breaker with 10 AWG copper.
Worked example

Maximum continuous load on a 30 A, 240 V circuit

  1. 1

    The question

    What is the largest continuous resistive load, in watts, permitted on a 30 A, 240 V branch circuit with a standard breaker?

  2. 2

    Full rating

    30 × 240 = 7,200 W.

  3. 3

    80% for continuous

    7,200 × 0.80 = 5,760 W.

  4. ✓ Answer: 5,760 W. A 5,500 W water heater (22.9 A) fits; a 6,000 W element (25 A, needing a 31.25 A breaker) does not.

A 240 V appliance on a 208 V circuit: fewer watts than the label

Commercial buildings and apartment complexes are often served by 208Y/120 V systems, so a "240 V" water heater or baseboard heater may end up on 208 V between two phases. A resistive load's power changes with the square of the voltage, because its resistance stays the same:

Resistive load at a different voltage

P(new) = P(rated) × (V(new) ÷ V(rated))²

Worked example

4,000 W heater rated 240 V, connected at 208 V

  1. 1

    Voltage ratio

    208 ÷ 240 = 0.8667.

  2. 2

    Square it

    0.8667² = 0.7511.

  3. 3

    New power

    4,000 × 0.7511 = 3,004 W. Current: 3,004 ÷ 208 = 14.4 A.

  4. ✓ Answer: About 3,000 W at 14.4 A. The heater draws less current, not more, and puts out about 25% less heat.

The exam uses this to test whether you understand that a resistor does not "pull harder" at lower voltage. Motors behave differently, which is why motor questions use the NEC tables instead.

How to check a circuit you already have

For a real circuit in a house or shop, the method is the same as on the exam:

  1. Identify the breaker and its rating, and the voltage (one handle at 120 V, a 2-pole breaker at 240 V).
  2. List every load that can run at the same time, from nameplates. Use amps where the nameplate gives them.
  3. Convert watts to amps at the circuit voltage and add them up.
  4. Compare: total under the rating for short-time loads, under 80% for anything that runs 3 hours or more, and no single plug-in appliance over 80%.

If the total is close to the limit, move a heavy load to another circuit rather than upsizing the breaker. The breaker protects the wire, and the wire size does not change because the load grew.

Watts vs volt-amperes: when they are not the same

For resistive loads, watts equal volt-amperes: heaters, toasters, incandescent lamps, water heater elements. For motors, LED drivers, compressors and electronic power supplies, the current is out of step with the voltage. The power factor (PF) is less than 1, and:

Real vs apparent power

Watts = Volts × Amps × PF

A breaker trips on current, not watts. If a 1,000 W load has a power factor of 0.8, it draws 1,000 ÷ (120 × 0.8) = 10.4 A, not 8.3 A. That is why the NEC calculates LED and ballast loads from their ampere ratings (NEC 220.18(B)) and motors from the full-load current tables. For the theory, see power factor, kW and kVA.

Exam-style questions

Exam-style question

What is the maximum continuous load, in volt-amperes, on a 20-ampere, 120-volt branch circuit protected by a standard circuit breaker?

Pick an answer to see the explanation.

Exam-style question

A cord-and-plug-connected appliance, not fastened in place, is to be connected to a 15-ampere, 120-volt general-purpose branch circuit. What is the maximum rating of the appliance?

Pick an answer to see the explanation.

Exam-style question

A 7,200-watt, 240-volt fixed electric space heater is supplied by an individual branch circuit. What is the minimum standard overcurrent device rating?

Pick an answer to see the explanation.

Common mistakes

Using 110 V or 220 V. The NEC uses nominal 120 V and 240 V. Using 110 V gives the wrong amps.

Applying 80% to everything. The 80% continuous rule is for loads that run 3 hours or more. A noncontinuous circuit may carry its full rating, but no single plug-in appliance may exceed 80%.

Treating watts as amps for motors. Motors and electronics need the nameplate current or the NEC tables.

Forgetting the small-conductor cap. A 25 A breaker requires at least 10 AWG copper because 240.4(D) limits 12 AWG to 20 A. See 12 vs 14 gauge wire.

Where to find it in the code book

The rules behind every number on this page are in Article 210, Part II: 210.20(A) for continuous loads and 210.23 for permissible loads. Nominal voltages are in 220.5(A). Tab those two spots and you can answer any "how many watts" question in seconds.

→Category hub: branch circuits and protectionBranch Circuits Explained: NEC Article 210 for the Exam

If your question is really about how many receptacles to install, read how many outlets on a 20 amp circuit. For fixtures, see how many lights on a circuit. Both build on the branch circuits guide to NEC Article 210. Then put the formulas to work on the free journeyman practice test.