How many lights on a 15 amp circuit? As many as the load allows: a 15 A, 120 V circuit can supply 1,800 watts, and if the lights stay on for 3 hours or more you should keep the load to 80%, or 1,440 W. Divide that by the watts per fixture: 14 fixtures at 100 W, 24 at 60 W, or 120 LED fixtures at 12 W. On a 20 A circuit, the 80% figure is 1,920 W.

The NEC has no rule that says "maximum 12 lights per circuit." What it has are rules for what load to assign to a luminaire, how continuous loads are treated, and how many circuits a building needs. This guide gives you the tables for common fixtures, shows the calculation step by step, and covers the limits that matter on a real job and on the journeyman exam.

The quick answer: lights per 15 A and 20 A circuit

These numbers use 120 V, the fixture's actual rated input, and round down. The 80% column is the one to use for lighting that stays on 3 hours or more.

Fixture rated input15 A at 100% (1,800 W)15 A at 80% (1,440 W)20 A at 100% (2,400 W)20 A at 80% (1,920 W)
150 W1291612
100 W18142419
60 W30244032
40 W45366048
15 W (LED)12096160128
12 W (LED)150120200160
9 W (LED)200160266213
1,440 W ÷ watts per lamp100 W1460 W2412 W LED1209 W LED160Bars to scale. Use the fixture's rated input, not the "equivalent" watts.
Lamps per 15 A, 120 V circuit at 80% (1,440 W), by lamp wattage.

The formula, step by step

Lights per circuit

Number of fixtures = (volts × amps × 0.80) ÷ VA per fixture, rounded down

Three steps every time:

  1. Circuit capacity: volts × breaker amps. 120 V × 15 A = 1,800 VA.
  2. Continuous or not: if the lights run 3 hours or more, multiply by 0.80. That comes from NEC 210.20(A), which requires the breaker to be at least 125% of a continuous load; 1 ÷ 1.25 = 0.80.
  3. Divide and round down: a fraction of a fixture would put you over the limit.
Worked example

Recessed LED downlights on a 15 A circuit

  1. 1

    The question

    A kitchen remodel uses LED downlights with a nameplate input of 0.13 A at 120 V. The lights are expected to be on for long periods. How many can be connected to one 15 A, 120 V circuit?

  2. 2

    Continuous capacity in amps

    15 A × 0.80 = 12 A.

  3. 3

    Divide by fixture current

    12 ÷ 0.13 = 92.3.

  4. ✓ Answer: 92 fixtures on paper. The switch or dimmer controlling them almost certainly has a lower LED rating, so check it before you design around that number.

Working in amps instead of watts is not just convenient. For LED drivers and ballasts, the NEC requires it.

What load does the NEC assign to a light fixture?

Two sections in Article 220 decide the number you divide by.

NEC 220.14(D), luminaires. An outlet supplying luminaires is calculated at the maximum volt-ampere rating of the equipment and lamps for which the luminaire is rated. A fixture marked "max 2 × 60 W" counts as 120 VA in a load calculation even if you install two 9 W LED lamps, because someone can put 60 W lamps back in.

NEC 220.18(B), inductive and LED lighting loads. For circuits supplying lighting units with ballasts, transformers, autotransformers or LED drivers, the calculated load is based on the total ampere ratings of those units, not the total watts of the lamps. Drivers and ballasts have a power factor below 1, so their volt-amperes are higher than their watts.

Worked example

LED troffers on a 277 V commercial circuit

  1. 1

    The question

    An office uses 2 × 4 LED troffers whose driver input is marked 0.30 A at 277 V. The lighting is continuous. How many troffers may be connected to a 20 A, 277 V branch circuit?

  2. 2

    Continuous capacity

    20 A × 0.80 = 16 A.

  3. 3

    Divide by the driver's ampere rating

    16 ÷ 0.30 = 53.3. Round down.

  4. ✓ Answer: 53 troffers. Using lamp watts instead of the driver's ampere rating is the mistake 220.18(B) is written to prevent.

Dwellings: lights are counted by square foot, not by fixture

In homes, you do not add up lighting outlets at all for the circuit count. NEC 220.41 sets a minimum unit load of 3 VA per square foot, which already includes the lighting outlets required by 210.70 and the general-use receptacles. NEC 210.11(B) then requires that load to be evenly proportioned among the multioutlet branch circuits.

Worked example

General lighting circuits for a 1,800 ft² house

  1. 1

    Load

    1,800 ft² × 3 VA = 5,400 VA.

  2. 2

    15 A circuits

    5,400 ÷ 1,800 = 3 circuits.

  3. 3

    20 A circuits

    5,400 ÷ 2,400 = 2.25, rounded up to 3 circuits.

  4. ✓ Answer: At least three general lighting and receptacle circuits, plus the 20 A circuits required by 210.11(C). The number of fixtures on each is not limited by the code.

Those circuits usually carry both lights and receptacles. Keeping lights and receptacles on separate circuits is a good design habit, because a tripped receptacle circuit then does not leave a room dark. It is not an NEC requirement. Related reading: how many outlets on a 20 amp circuit.

The limits that usually come first

On real jobs, the breaker is rarely what stops you. These do:

  • Switch and dimmer ratings. A dimmer's LED rating is usually far lower than its incandescent rating. The device's listing and instructions set the limit (NEC 110.3(B)).
  • LED driver inrush. Many drivers draw a short inrush current when switched on. Large groups on one breaker can cause nuisance trips, and some fixture manufacturers publish a maximum number of drivers per breaker. Follow it.
  • Voltage drop. Long runs of 14 AWG on a heavily loaded lighting circuit lose voltage. The NEC's 3% and 5% figures are recommendations in informational notes, covered in NEC voltage drop rules.
  • Fixed equipment sharing the circuit. If a bath fan or other fastened-in-place equipment shares a 15 A lighting circuit, it is limited to 50% of the rating (7.5 A) by NEC 210.23(B)(2).

Mixed circuits: lights plus fans, receptacles and other loads

Most residential circuits are not lights only. When a circuit carries a mix, add every load in the same unit, then compare with the circuit's capacity.

Worked example

Lights and a ceiling fan on a 15 A bedroom circuit

  1. 1

    The loads

    Suppose a bedroom circuit supplies six LED fixtures rated 15 W each, a ceiling fan rated 0.6 A, and receptacles where a 1,200 W hair dryer is sometimes used.

  2. 2

    Lights and fan in amps

    Lights: 6 × 15 W = 90 W, and 90 ÷ 120 = 0.75 A. Fan: 0.6 A. Total fixed lighting and fan load: 1.35 A.

  3. 3

    Add the largest plug-in load

    Hair dryer: 1,200 ÷ 120 = 10 A. That is under the 12 A limit for one cord-and-plug appliance on a 15 A circuit (210.23(B)(1)).

  4. 4

    Total

    1.35 + 10 = 11.35 A, under 15 A.

  5. ✓ Answer: The circuit works. The lights are a rounding error; the hair dryer is what sizes the circuit.

That is the real lesson of LED lighting: on modern circuits, the fixtures are almost never the problem. The plug-in heating appliances are.

How the exam words lighting questions

Journeyman exam questions on this topic usually give you four facts: the circuit voltage, the breaker size, the fixture rating (in VA, watts or amps) and whether the load is continuous. Watch for these signals:

  • "Store," "office," "warehouse," "parking lot," or "operates more than 3 hours": continuous, use 80%.
  • A fixture rating in amps at 277 V: work in amps, do not convert to watts.
  • "Ballast" or "driver": the ampere rating governs under 220.18(B).
  • "Dwelling" and "how many circuits": square footage × 3 VA, divided by circuit VA, rounded up.

The answer choices usually include the 100% result and the rounded-up result as distractors. Decide on the 80% and the rounding before you look at the choices.

10 A lighting circuits in the 2023 NEC

The 2023 NEC lists 10 A among the branch-circuit ratings in NEC 210.18, aimed at low-wattage LED lighting. A 10 A circuit may never supply receptacle outlets, and NEC 210.23(A) limits it to loads such as lighting outlets and, in dwellings, exhaust fans on bathroom or laundry room lighting circuits. At 120 V, a 10 A circuit carries 1,200 VA, or 960 VA at 80%. Confirm your state has adopted the 2023 edition before using this on an exam: which NEC edition your state uses.

Exam-style questions

Exam-style question

A store's lighting circuit is 15 A at 120 V. Each luminaire is rated 150 VA, and the lights operate for more than 3 hours at a time. What is the maximum number of luminaires on the circuit?

Pick an answer to see the explanation.

Exam-style question

When calculating the load of a circuit supplying LED luminaires with drivers, the calculated load is based on which value?

Pick an answer to see the explanation.

Exam-style question

How many luminaires with a driver input of 0.75 A may be connected to a 20 A, 277 V lighting branch circuit if the load is continuous?

Pick an answer to see the explanation.

Common mistakes

Using "equivalent" watts. Divide by the actual input, not the incandescent equivalent.

Using lamp watts for drivers and ballasts. 220.18(B) says amperes of the units.

Ignoring the fixture's maximum lamp rating in a load calculation. 220.14(D) uses the rating the luminaire is marked for.

Rounding up. 9.6 fixtures is 9 fixtures.

Forgetting the 80%. Commercial lighting is almost always continuous.

Where to look in the code book

Lighting load questions live in Article 220, Part II: 220.14(D) for luminaires and 220.18(B) for LED and ballast loads. The continuous-load rule is in 210.20(A), and the dwelling unit load in 220.41. Tab Part II of Article 220 and you have most of them on facing pages.

→Category hub: branch circuits and protectionBranch Circuits Explained: NEC Article 210 for the Exam

For the same math applied to appliances and heaters, read how many watts a 15 or 20 amp breaker can handle. For the full set of branch-circuit rules, start at the branch circuits guide to NEC Article 210. Then check your speed on the free journeyman practice test.