The master electrician exam is the licensing test for the top individual electrician license in most states. To sit for it you typically need a journeyman license held for a set period plus more supervised experience hours, and the exam itself is longer and more calculation-heavy than the journeyman exam: services and feeders, load calculations, motor feeders, transformers and special occupancies, usually open book with the NEC edition your state has adopted.

This guide covers eligibility with a verified example, compares master and journeyman formats using real bulletins, walks through the calculations that separate the two exams with full worked examples, and gives you a study plan that fits around a full-time job.

Who can sit for the master exam

Eligibility is set by each state, and the master license usually builds on the journeyman one. Texas is a clear example. To apply for a Texas master electrician license, TDLR requires:

  • A journeyman electrician license held for at least two years (journeyman industrial experience does not count).
  • 12,000 hours of on-the-job training under the supervision of a master electrician licensed in Texas.
  • An application, verified by TDLR, before you can schedule the exam.

Other states set different hours, years or license prerequisites, and some accept education or engineering experience toward part of the requirement. Your board's master license page is the authority. For the bigger picture of what each license allows, read journeyman vs master electrician.

How the master exam differs from the journeyman exam

Here is how two states' PSI bulletins compare the formats. They show the pattern: more items, more time, and more of it spent on calculations.

Texas journeymanTexas masterIowa journeymanIowa master
StructureKnowledge + calculations portionsKnowledge + calculations portionsSingle examSingle exam
Knowledge portion59 items, 130 min75 items, 150 min——
Calculations portion26 items, 110 min33 items, 170 min——
Total items85 (80 scored)108 (100 scored)88 (80 scored)110 (100 scored)
Time240 min total320 min total180 + 30 min240 + 30 min
Passing score70% on each portion70% on each portion70%70%

Sources: Texas electrician candidate bulletin (PSI) and Iowa electrical candidate bulletin (PSI). Bulletins change; check your current one before you plan your time.

The Texas outlines also show where the extra weight lands. The master calculations portion assigns 8 items to services and service equipment and 6 to motors and generators, against 4 and 2 on the journeyman calculations portion.

The results reflect that. In TDLR's fiscal year 2025 exam statistics, the master calculations portion recorded 753 passes out of 3,946 attempts (about 19%) and the master NEC portion 771 out of 3,472 (about 22%), compared with about 21% and 24% on the journeyman portions. Those counts include retakes, but the calculations portion is the hardest hurdle at both levels.

Some states also add a separate law, rules or business section to the master or contractor licensing process. If your state does, the content outline in your bulletin will list it, and it needs its own preparation.

What the master exam tests harder

Services and feeders. Sizing service and feeder conductors, overcurrent protection and the grounding electrode conductor, including parallel sets.

Load calculations. Dwelling calculations by both the standard and optional methods, plus multifamily and commercial loads. In the 2023 NEC these are in Article 220; in the 2026 edition they moved to Article 120 (220.52 becomes 120.52, Table 220.55 becomes Table 120.55, and so on). Texas master exams have used the 2026 NEC since September 1, 2026.

Motors. Not just one motor, but feeders supplying several motors and other loads, under 430.24 and the feeder protection rules.

Transformers. Full-load current, primary and secondary protection under 450.3, and the conductors on each side.

Special occupancies and systems. Hazardous locations, health care, emergency and standby systems, PV and EV charging.

If any of those are new to you, our guides on motor calculations, transformer calculations, the dwelling load calculation optional method and service-entrance conductors cover each topic step by step.

Worked example: a feeder supplying several motors

Worked example

Minimum feeder ampacity for three motors

  1. 1

    The question

    A 460-volt, three-phase feeder supplies three continuous-duty induction motors: 10 hp, 7½ hp and 5 hp. There is no other load. What is the minimum ampacity of the feeder conductors?

  2. 2

    Get the full-load currents from the table

    Use Table 430.250, not the nameplates (430.6(A)(1)). At 460 V: 10 hp = 14 A, 7½ hp = 11 A, 5 hp = 7.6 A.

  3. 3

    Apply 430.24

    Feeder ampacity = 125% of the largest motor FLC + the sum of the other motor FLCs. 1.25 × 14 = 17.5 A.

  4. 4

    Add the rest

    17.5 + 11 + 7.6 = 36.1 A.

  5. ✓ Answer: 36.1 A minimum feeder ampacity. Choose conductors from Table 310.16 with an ampacity of at least 36.1 A, respecting the termination temperature limits.

The usual mistakes: applying 125% to every motor, using nameplate currents, or using the 230-volt column by accident.

Worked example: transformer primary protection

Worked example

Primary-only protection for a 75 kVA transformer

  1. 1

    The question

    A 75 kVA, three-phase transformer has a 480-volt primary and a 208Y/120-volt secondary. It is protected on the primary side only. What is the maximum rating of the primary overcurrent device?

  2. 2

    Primary full-load current

    I = kVA × 1,000 ÷ (V × 1.732) = 75,000 ÷ (480 × 1.732) = 75,000 ÷ 831.4 = 90.2 A.

  3. 3

    Apply Table 450.3(B)

    For primary-only protection with a primary current of 9 A or more, the maximum is 125%: 90.2 × 1.25 = 112.8 A.

  4. 4

    Round per Note 1

    112.8 A is not a standard rating. Note 1 to Table 450.3(B) permits the next higher standard size from 240.6(A): 125 A.

  5. ✓ Answer: 125 A maximum primary overcurrent device.

Notice the rounding direction. Here the table note lets you go up to the next standard size, which is the opposite of a "how many conductors fit" question, where you always round down.

Practice: master-level questions

Exam-style question

A 460-volt, three-phase feeder supplies only two continuous-duty induction motors: 15 hp and 10 hp. What is the minimum feeder ampacity?

Pick an answer to see the explanation.

Exam-style question

What is the secondary full-load current of a 75 kVA, three-phase transformer with a 208Y/120-volt secondary?

Pick an answer to see the explanation.

Exam-style question

A service is supplied by two parallel sets of 3/0 AWG copper conductors per phase. What is the minimum size copper grounding electrode conductor to a building steel electrode, where no electrode-specific limit applies?

Pick an answer to see the explanation.

For more on that last table, see grounding electrode conductor sizing with Table 250.66.

→Go deeper on 450.3Transformer Calculations and Overcurrent Protection (NEC 450.3)

How master-level questions are built

Journeyman questions often test one rule: find the table, read the value. Master questions tend to chain two to four rules together, and each link is a place to lose the point. The two worked examples above show the pattern: a table lookup, then a percentage rule, then a rounding rule.

A reliable way to handle them on the note board:

  1. Name the final answer first. "Maximum primary OCPD in amperes" or "minimum feeder ampacity". Write it at the top.
  2. List the rules in the chain. For a motor feeder: Table 430.250 → 430.24 → Table 310.16 → 110.14(C). For a transformer: current formula → Table 450.3(B) → Note 1 → 240.6(A).
  3. Work each link and write the intermediate number. If you run out of time, a half-finished chain on the board is easy to pick back up on the second pass.
  4. Check the rounding rule last. Up to the next standard size, down for conductor counts, or no rounding at all.

Distractors are built from skipped links: the answer you get if you forget the 125%, use the nameplate, apply the single-phase formula, or round the wrong way. If your answer matches one of the choices on the first try, still check that you did not skip a step; the wrong answers are designed to be reachable.

A study plan for working journeymen

Most master candidates study around full-time work. Ten to twelve weeks of steady effort is a realistic frame; adjust it to your gaps.

WeeksFocusOutput
1–2Read your bulletin, buy and tab the right edition, take a timed diagnosticList of weak content areas
3–5Calculations by method: dwelling and commercial loads, services, feedersOne written method per calc type
6–7Motors, transformers, grounding for large servicesTimed calc sets at bulletin pace
8–9Special occupancies and systems, definitions, lookupsFaster index and tab work
10–12Full-length timed practice exams, review every missConsistent scores above the passing mark

If you are rusty on formulas, keep the electrical formulas cheat sheet open while you build your methods, then practice without it.

The mistakes that cost master candidates

Treating it as a longer journeyman exam. The extra items are mostly system-level calculations. Lookup speed alone will not carry you.

Memorizing answers instead of methods. Master questions change one variable and the memorized answer is wrong.

Rounding the wrong way. Overcurrent device questions often allow the next standard size up; conductor counts always round down.

Studying the wrong edition. Section numbers move. Confirm the edition with which NEC edition your state uses.

Ignoring the non-electrical parts. If your state adds law, rules or business content, it is scored like everything else.

After you pass

A master license usually brings new responsibilities: supervising journeymen and apprentices, pulling permits in many states, and in some states qualifying an electrical contractor business. Learn your state's rules for each before you take on that role.

If you are moving between states with a master license, agreements and conditions differ from journeyman ones: see electrician license reciprocity. For the path that leads here, read how to become a journeyman electrician. Then measure where you stand with our timed practice tests or the free journeyman practice test as a warm-up.