A Class 1 Division 2 location (written Class I, Division 2 in the NEC) is an area where flammable gases or vapors are present only under abnormal conditions: they are normally confined in closed containers or piping, kept below ignitible levels by mechanical ventilation, or the area sits next to a Division 1 location. "Class I" names the hazard (gas or vapor); "Division 2" says how likely it is to be there.

This guide explains the whole classification system of NEC Article 500 the way the journeyman exam tests it: the three classes, the two divisions, material groups, temperature codes, how zones compare, the protection techniques, Class I wiring methods and the conduit seal rules. You will finish able to read a classification like "Class I, Division 1, Group D, T3" and know exactly what it demands.

What Class 1 Division 2 means

Under NEC 500.5(B)(2), a Class I, Division 2 location is one of these:

  1. Where volatile flammable gases, flammable liquid–produced vapors or combustible liquid–produced vapors are handled, processed or used, but are normally confined within closed containers or closed systems and can escape only through accidental rupture, breakdown or abnormal operation of equipment.
  2. Where ignitible concentrations are normally prevented by positive mechanical ventilation and could become hazardous only if the ventilation fails or operates abnormally.
  3. Where the area is adjacent to a Class I, Division 1 location and ignitible concentrations might occasionally be communicated to it, unless prevented by adequate positive-pressure ventilation from a clean-air source with effective safeguards against ventilation failure.

Typical Class I, Division 2 areas include the space around pumps, valves and flanges in closed piping systems, storage rooms with sealed drums of flammable liquid, and the envelope just outside a Division 1 area around a vent or a dispenser.

Class I, II and III: what is in the air

The class identifies the type of hazardous material. It is the first word of every classification.

ClassHazardTypical locations
Class IFlammable gases, flammable liquid–produced vapors, combustible liquid–produced vaporsRefineries, fuel dispensing, spray booths, paint mixing rooms, gas compressor stations
Class IICombustible dustGrain elevators, flour mills, coal handling, sugar and starch plants, metal powder processing
Class IIIIgnitible fibers or flyings (too large to stay suspended in air like dust)Textile mills, cotton gins, woodworking shops producing shavings, sawmills

The Class III materials are the ones people forget: they burn easily but are not normally in suspension in the air in quantities that would produce an explosive mixture.

Divisions 1 and 2: how often the hazard is there

The division applies inside each class. The exam usually tests the definitions, so learn the key phrase of each:

Division 1

  • Present in normal operation
  • Or frequently, from repair, maintenance or leakage
  • Class II: dust in suspension normally, or Group E metal dust in hazardous quantity
  • Class III: fibers handled, manufactured or used
  • Strictest equipment and wiring

Division 2

  • Present only under abnormal conditions
  • Normally confined in closed systems or kept out by ventilation
  • Or adjacent to a Division 1 area
  • Class III: fibers stored or handled outside manufacturing
  • Wider choice of equipment and wiring

For Class II, Division 1 covers dust in suspension in the air under normal operation, places where mechanical failure could produce explosive dust mixtures and simultaneously cause an ignition source, and any place where Group E (metal) dusts may be present in hazardous quantities. Division 2 covers dust that is suspended only through abnormal operation, and dust layers that could be put in suspension or could interfere with the dissipation of heat from electrical equipment.

For Class III, Division 1 is where ignitible fibers are handled, manufactured or used; Division 2 is where they are stored or handled other than in manufacturing.

Closed tankDiv. 1vent openingDivision 2Unclassifiedordinary wiringSeal where conduitcrosses a boundary
Classification around a vent from a closed process: Division 1 where vapor is present in normal operation, Division 2 around it. Actual distances come from the classification documentation or the occupancy article.

Material groups A through G

Within a class, gases and dusts are grouped by how they behave in an explosion (pressure, flame path, ignition energy). Equipment is listed and marked for specific groups, and it must be identified for the group actually present.

GroupClassTypical materials
AIAcetylene
BIHydrogen and gases of similar hazard
CIEthylene and gases of similar hazard
DIPropane, gasoline, natural gas, and many common solvents
EIIMetal dusts such as aluminum and magnesium
FIICarbonaceous dusts such as coal, carbon black, charcoal and coke
GIIOther combustible dusts such as flour, grain, starch, sugar, wood and plastics

Class III has no groups. A memory trick: Acetylene is first and hardest; the gas groups run A to D from most to least severe, then the dusts pick up at E with Electrically conductive metal dust.

Temperature codes (T-codes)

Electrical equipment gets hot, and a hot surface can ignite a gas without any spark. Equipment for classified locations is marked with a temperature class, the maximum surface temperature it can reach. The T-code must be below the autoignition temperature of the gas or vapor present (for dusts, the rules also account for dust layers).

T-codeMaximum surface temperature
T1450°C
T2300°C
T3200°C
T4135°C
T5100°C
T685°C

A higher T-number means a cooler surface. A T6 fixture is acceptable anywhere a T3 fixture is, but not the other way around. There are also intermediate classes (T2A through T4A) between the main ones.

Zones: the alternative system (Articles 505 and 506)

The NEC also recognizes the international-style zone system. For gases and vapors, it is in NEC 505; for combustible dusts and ignitible fibers, in NEC 506.

ZoneHazard presentClosest Division equivalent
Zone 0Gas or vapor continuously or for long periodsPart of Division 1
Zone 1Gas or vapor likely in normal operation, or frequently from repair or leakagePart of Division 1
Zone 2Gas or vapor not likely in normal operation, and only for a short time if it occursDivision 2
Zone 20Dust or fibers continuously or for long periodsPart of Division 1
Zone 21Dust or fibers likely in normal operationPart of Division 1
Zone 22Dust or fibers not likely, and only for a short timeDivision 2

Zone gas groups are IIC (acetylene and hydrogen), IIB (ethylene) and IIA (propane and similar). Note the order is reversed from the division groups: IIC is the most severe. A facility uses either the division system or the zone system for a given area, and equipment marked for one system can only be used in the other where the Code specifically allows it.

Protection techniques: what makes equipment safe

NEC 500.7 lists the protection techniques for the division system. The most common, and where they are acceptable:

TechniqueHow it worksAcceptable in
ExplosionproofEnclosure contains an internal explosion and cools escaping gasesClass I, Divisions 1 and 2
Dust-ignitionproofKeeps dust out and limits surface temperatureClass II, Divisions 1 and 2
DusttightKeeps dust outClass II, Division 2; Class III
Purged and pressurizedClean air or inert gas keeps the hazard outPer the type of purging, in any class and division it is identified for
Intrinsic safetyCircuit energy too low to ignite, even under faultAll classes and divisions
NonincendiveCannot ignite in normal operationDivision 2 locations, and Class III
Hermetically sealedSealed against the atmosphereDivision 2 (Class I and II) and Class III

Class I wiring methods

Class I, Division 1 (NEC 501.10(A)) permits, among others:

  • Threaded rigid metal conduit or threaded steel intermediate metal conduit
  • Type MI cable with fittings listed for the location
  • Type MC-HL and ITC-HL cable where permitted, with listed fittings
  • PVC and RTRC only under specific concrete-encased, underground conditions

Conduit is made up wrenchtight, and NPT threaded entries into explosionproof equipment need at least five threads fully engaged (NEC 500.8(E)). The one relaxation: listed explosionproof equipment with factory-threaded NPT entries may be made up with 4½ threads fully engaged. EMT, PVC above ground and NM cable are not Division 1 methods.

Class I, Division 2 (NEC 501.10(B)) permits every Division 1 method plus:

  • RMC and IMC with listed threaded or threadless fittings (in Division 2 the conduit no longer has to be threaded)
  • Enclosed gasketed busways and enclosed gasketed wireways
  • Type PLTC, PLTC-ER, ITC and ITC-ER cable
  • Type MC, MV, TC and TC-ER cable, with termination fittings listed for the location
  • Flexible connections where needed for vibration or movement: flexible metal fittings, FMC, LFMC and LFNC with listed fittings, or extra-hard-usage flexible cord

Is EMT allowed in Class I, Division 2? No. EMT does not appear in the 501.10(B) list, threaded or not. It is a classic trick question on Division 2 wiring. EMT does show up in the Class II, Division 2 list (NEC 502.10(B)) and in Class III (NEC 503.10), which is exactly why people misremember it for Class I.

Bonding. In any hazardous location, regardless of voltage, locknut-bushing and double-locknut connections cannot be relied on for bonding. Bonding jumpers or other approved means are required (NEC 250.100, NEC 501.30(A)). The basics are in grounding vs bonding.

Conduit seals in Class I locations

Seals stop gases and flames from traveling through the conduit system from one enclosure to another or out of the classified area. NEC 501.15 is the most tested section of Article 501.

Seals at enclosures (Division 1). A seal is required in each conduit entry into an explosionproof enclosure where:

  • the enclosure contains apparatus that may produce arcs, sparks or high temperatures in normal operation (switches, breakers, relays, fuses), or
  • the entry is trade size 2 or larger and the enclosure contains terminals, splices or taps.

The seal must be as close as practicable to the enclosure and not more than 18 inches from it (or as required by the enclosure marking).

Boundary seals. A seal is required in each conduit run leaving a Class I, Division 1 or Division 2 location. It may be on either side of the boundary, within 10 feet of it, with no union, coupling, box or fitting between the seal and the boundary (except listed explosionproof reducers at the seal).

Inside the seal.

  • Sealing compound thickness: not less than the trade size of the fitting and never less than 5/8 inch.
  • Conductor fill: not more than 25% of the cross-sectional area of rigid metal conduit of the same trade size, unless the seal is identified for a higher fill. Compare with the 40% rule in a normal conduit fill calculation.
  • No splices or taps in fittings intended only for sealing.
Class I, Division 1UnclassifiedXPswitchSeal: 18 in. max.Boundary seal:within 10 ftNo coupling, unionor box between sealand boundary
Class I, Division 1 sealing: within 18 inches of an arcing enclosure, and within 10 feet of the boundary where the conduit leaves.
Worked example

Where do the seals go?

  1. 1

    The question

    A 3/4-inch threaded RMC feeds an explosionproof motor starter (which contains arcing contacts) in a Class I, Division 1 area. The conduit then runs 30 feet to a panel in an unclassified room. Which seals are required?

  2. 2

    At the starter

    The starter contains arcing devices, so the conduit entry needs a seal regardless of size, not more than 18 inches from the enclosure.

  3. 3

    At the boundary

    The conduit leaves a Division 1 location, so it needs a boundary seal within 10 feet of the boundary on either side, with no coupling, union or box between the seal and the boundary.

  4. ✓ Answer: Two seals: one within 18 in. of the starter and one within 10 ft of the Division 1 boundary.

Who classifies the area, and the occupancy articles

Electricians install to a classification; they do not create it. NEC 500.4 requires that areas designated as hazardous (classified) locations be properly documented, and that the documentation be available to those who design, install, inspect, maintain or operate the electrical equipment. Classification is usually done by engineers using standards such as NFPA 497 (gases and vapors), NFPA 499 (dusts) or API RP 500 and 505 (petroleum facilities).

Some common occupancies have their classification built into the NEC itself:

ArticleOccupancy
511Commercial garages, repair and storage
513Aircraft hangars
514Motor fuel dispensing facilities (gas stations)
515Bulk storage plants
516Spray application, dipping, coating and printing

When a question names one of those occupancies, go straight to its article: the classified distances are in its tables, not in Article 500. OSHA applies the same classification framework to workplaces in 29 CFR 1910.307, which also requires that classified areas be documented.

Practice: hazardous location exam questions

Exam-style question

A room stores flammable liquids only in sealed drums, and vapors could escape only if a drum ruptures. The room is best described as:

Pick an answer to see the explanation.

Exam-style question

Grain dust in a flour mill falls into which class and group?

Pick an answer to see the explanation.

Exam-style question

In a Class I, Division 1 location, a seal is required where a conduit leaves the classified area. Where may it be located?

Pick an answer to see the explanation.

Exam-style question

Which of the following wiring methods is NOT permitted in a Class I, Division 2 location?

Pick an answer to see the explanation.

The mistakes that cost points

Mixing up class and division. Class is the material (gas, dust, fibers). Division is the likelihood. "Class 2 Division 1" is a dust location in normal operation, not a gas location.

Reading T-codes backwards. A higher T-number is a cooler surface. T6 (85°C) is the most restrictive class.

Mixing up the group order. Division groups go A (worst) to D for gases. Zone groups go IIA to IIC, with IIC the worst.

Using 18 inches for boundary seals. 18 inches is the enclosure seal. The boundary seal is within 10 feet.

Allowing EMT in Class I, Division 2. It is a Class II, Division 2 and Class III method, not a Class I method.

Forgetting that seals have their own fill limit. 25% of the RMC area, not 40%.

Classifying the area yourself. The exam may ask who is responsible: classification is documented by the owner or engineer; the installer follows it.

How to find it fast in the code book

Chapter 5 starts with Article 500 (definitions of classes and divisions, groups, protection techniques and marking), then 501 (Class I), 502 (Class II), 503 (Class III), 505 and 506 (zones), and the occupancy articles 511 through 516. Tab 500, 501 and 514 at minimum; highlight 500.5, 500.6, the T-code table in 500.8, 501.10 and 501.15. The code book tabbing guide shows a full Chapter 5 tab plan.

→Special topics hubWorking Clearance Around Electrical Panels: NEC 110.26

Hazardous locations sit in the same exam section as working clearance under 110.26 and emergency and standby systems, and the seal rules borrow from the conduit fill calculation. When you can classify a location and place every seal without looking, take a timed set on the free journeyman practice test.